- ML19305B336 (redirect page) (← links)
- 05000219/LER-1980-061-03, /03L-0:on 801217,snubbers - 19/11,19/12 & 19-13 on Containment Spray & Core Spray Sys Common Suction Header Failed to Lock Up in Compression Mode.Caused by Main Piston Seal Failures.Snubbers Replaced (← links)
- 05000219/LER-1980-061, Forwards LER 80-061/03L-0 (← links)
- 05000219/LER-1980-050-03, /03L-0:on 801106,containment Spray Sys Drywell Pressure Switches IP-15A,IP-15B,IP-15C & IP-15D Found to Trip at Greater than Allowable Tech Spec Values.Caused by Instrument Repeatability.Switches Adjusted (← links)
- 05000219/LER-1980-050, Forwards LER 80-050/03L-0 (← links)
- 05000219/LER-1980-040-03, /03L-0:on 800904,north Core Spray Sys Snubber 51/6 Failed to Lock in Either Tension or Compression Directions. Caused by Loose Socket Head Screws Permitting Hydraulic Fluid to Leak.Snubber Replaced & Screws Tightened (← links)
- 05000219/LER-1980-040, Forwards LER 80-040/03L-0 (← links)
- 05000219/LER-1980-042-03, /03L-0:on 800911,high Drywell Switches IP-15A, IP-15B & IP-15C Tripped at Value Greater than 2.0 Psig as Specified in Tech Specs.Caused by Instrument Drift.Switches Adjusted to Trip within Tech Spec Limit (← links)
- 05000219/LER-1980-041, Forwards LER 80-041/03L-0 (← links)
- 05000219/LER-1980-038-03, /03L-0:on 800826,during Surveillance Testing of Reactor Triple Low Water Level sensors,RE18B Tripped at Level Less Conservative than Tech Spec Limits.Caused by Sensor Repeatability.Sensor Reset within Prescribed Limits (← links)
- 05000219/LER-1980-038, Forwards LER 80-038/03L-0 (← links)
- 05000219/LER-1980-039-03, /03L-0:on 800829,during Low Pressure Main Steam Line Functional Test & calibr,RE23B & 23D Pressure Switches Actuated at Valve Above Tech Spec Limits.Caused by Instrument Repeatability.Switches Reset to Desired Limit (← links)
- 05000219/LER-1980-039, Forwards LER 80-039/03L-0 (← links)
- 05000219/LER-1980-051-03, /03L-0:on 801108,daily Surveillance Checks Not Made of Linear Heat Generation Rate,Average Planar Linear Heat Generation Rate & Max Critical Power Ratio.Caused by Personnel Error.Insps Performed (← links)
- 05000219/LER-1980-051, Forwards LER 80-051/03L-0 (← links)
- 05000219/LER-1980-052-03, /03L-0:on 801118,reactor Triple Low Water Level Indicator Switches RE-18A & RE-18D Tripped at Manometer Readings Higher than Tech Spec Limit.Caused by Sensor Repeatability.Switches Reset (← links)
- 05000219/LER-1980-052, Forwards LER 80-052/03L-0 (← links)
- 05000219/LER-1980-047-03, /03L-0:on 801101,while Performing Core Spray Sys Instrument Channel Calibr & Test,High Drywell Pressure Switches Tripped Above Tech Spec Limit.Cause Attributed to Instrument Repeatability.Switches Adjusted (← links)
- 05000219/LER-1980-047, Forwards LER 80-047/03L-0 (← links)
- 05000219/LER-1980-049-01, /01T-0:on 801105,when Isolation Condenser B Was Removed from Svc to Repair Steam Leak,Vent Isolation Valves V-14-1 & V-14-19 Apparently Failed to Close.Cause Undertermined.Stem Packing Replaced & Tested (← links)
- 05000219/LER-1980-049, Forwards LER 80-049/01T-0 (← links)
- 05000219/LER-1980-048-03, /03L-0:on 801029,during Functional Testing,Snubber 23-7 Failed to Lock Up in Tension Direction.Cause Unknown. Snubber Replaced (← links)
- 05000219/LER-1980-048, Forwards LER 80-048/03L-0 (← links)
- 05000219/LER-1980-043-03, /03L-0:on 800925,during Routine Surveillance, Reactor Triple Low Water Level Sensor RE18D Tripped at Level Less Conservative than Tech Specs.Caused by Sensor Repeatability.Sensor Reset (← links)
- 05000219/LER-1980-043, Forwards LER 80-043/03L-0 (← links)
- 05000219/LER-1980-032-01, /01T-0:on 800806,both Containment Spray Pump Compartment Doors Found Open.Caused by Lack of Administrative Controls.Engineering Evaluation Planned Re Effective Controls of Access Through Water Tight Doors (← links)
- 05000219/LER-1980-032, Forwards LER 80-032/01T-0 (← links)
- 05000219/LER-1980-030-03, /03L-0:on 800716,during Valve Operability Test, Electromagnetic Relief Valve D Failed to Open.Plant Shut Down.Caused by Deficient Maint Procedure.Valve Plunger & Pilot Valve Operating Lever Clearance Adjusted (← links)
- 05000219/LER-1980-030, Forwards LER 80-030/03L-0 (← links)
- 05000219/LER-1980-029-03, /03L-0:on 800711,during Plant Startup,Core Spray Pumps & Diesel Generators Started,Due to High Drywell Pressure Sensor Actuation.Caused by Instrument Setpoint Shift.Plant Shut Down & Sensors Recalibr (← links)
- 05000219/LER-1980-029, Forwards LER 80-029/03L-0 (← links)
- 05000219/LER-1980-031-03, /03L-0:on 800716,snubber 75/23 Failed to Lock Up in Tension Direction.Cause Attributed to Component Failure. Snubber Was Replaced with Operable Spare (← links)
- 05000219/LER-1980-031, Forwards LER 80-031/03L-0 (← links)
- 05000219/LER-1980-035-03, /03L-0:on 800814,during Containment Spray Sys Automatic Actuation Test,High Drywell Pressure Switches IP-15A & IP-15D Tripped at Higher than Specified Setpoint of 2 Psig.Caused by Instrument Repeatability (← links)
- 05000219/LER-1980-035, Forwards LER 80-035/03L-0 (← links)
- 05000219/LER-1980-063-03, /03L-0:on 801217,reactor Triple Low Water Level Indicator Switch RE-18A Tripped High.Caused by Instrument Drift.Switch Reset (← links)
- 05000219/LER-1980-063, Forwards LER 80-063/03L-0 (← links)
- 05000219/LER-1980-062-03, /03L-0:on 801218,control Rod Driveline Pump NCO8A Failed in Svc.Caused by Failure of Pump Shaft Outboard of Balancing Disc.Pump Internals & Motor Replaced (← links)
- 05000219/LER-1980-062, Forwards LER 80-062/03L-0 (← links)
- 05000219/LER-1980-059-03, /03L-0:on 801215,discovered That Main Station & Diesel Generator Monthly Battery Surveillance Tests Not Performed as Scheduled on 800801 & 1121.Caused by Personnel Error.Administrative Controls Implemented (← links)
- 05000219/LER-1980-059, Forwards LER 80-059/03L-0 (← links)
- 05000219/LER-1980-060-03, /03L-0:on 801211,during Routine Testing,Pipe Break Sensors for Isolation Condenser Condensate Return Lines Tripped Higher than Tech Spec.Caused by Instrument Drift. Switches Reset (← links)
- 05000219/LER-1980-060, Forwards LER 80-060/03L-0 (← links)
- 05000219/LER-1980-058-03, /03L-0:on 801211,snubbers 19/6 & 19/7 on Containment Spray & Core Spray Sys Failed Lockup Test.Caused by Piston Seal Failures.Snubbers Replaced (← links)
- 05000219/LER-1980-058, Forwards LER 80-058/03L-0 (← links)
- 05000219/LER-1980-054-03, /03L-0:on 801130,core Spray Sys 1 Removed from Svc to Inspect Pumps Sprayed W/Water Due to Leaking Pipes. Caused by Water Leaking Into Motor Lead Connection Box Due to Worn Cover Gaskets & Open Ended Conduit (← links)
- 05000219/LER-1980-054, Forwards LER 80-054/03L-0 (← links)
- 05000219/LER-1980-053-03, /03L-0:on 801130,limiting Operating Condition Occurred When Control Rod Driveline Pumps NC08A & NC08B Removed from Svc to Repair Leaks.Caused by Personnel Action. Pipe Replaced & Pumps Returned to Svc (← links)
- 05000219/LER-1980-053, Forwards LER 80-053/03L-0 (← links)
- 05000219/LER-1980-056-03, /03L-0:on 801204,main Steam Line High Flow Sensors RE-22C & RE-22G Tripped Above Tech Spec Levels.Caused by Instrument Repeatability.Sensor RE-22C Reset.Microswitch in Sensor RE-22G Replaced (← links)