- 05000362/LER-1994-001-01, :on 940416,channel B Containment Emergency Sump Level Lumigraph Indicator 3LI-9389-2 Observed W/No Light Bars Illuminated.Caused by Failure of Level Signal Converter 3LY-9389-2.Failed Signal Converter Replaced + ( :on 940416,channel B Containment Emergency Sump Level Lumigraph Indicator 3LI-9389-2 Observed W/No Light Bars Illuminated.Caused by Failure of Level Signal Converter 3LY-9389-2.Failed Signal Converter Replaced )