- 05000327/LER-1986-010-01, :on 860406,fuse Inadvertently Dislodged, Starting Diesel Generators 1A-A & 2A-A.Caused When Assistant Unit Operator Attempted to Verify Fuse Size.Procedure Will Be Revised to Add Caution Re Fuse Removal + ( :on 860406,fuse Inadvertently Dislodged, Starting Diesel Generators 1A-A & 2A-A.Caused When Assistant Unit Operator Attempted to Verify Fuse Size.Procedure Will Be Revised to Add Caution Re Fuse Removal )