- 05000277/LER-1976-024-03, /03L:on 760408,control Room Radiation Monitor RIS-0760A Failed in Low Count Direction.Caused by Logic Chip Vibrating Out of Socket.Logic Chip Reinserted & Unit Operated Properly + (/03L:on 760408,control Room Radiation Monitor RIS-0760A Failed in Low Count Direction.Caused by Logic Chip Vibrating Out of Socket.Logic Chip Reinserted & Unit Operated Properly)