- 05000311/LER-1982-154-03, /03L-0:on 821213,during Routine Channel Function Test,Steam Generator Steam Pressure Channel III Bistable Setpoint Observed Less than 480 Psig.Caused by Failure of Capacitor Incomparator 2PC 526 C/D.Capacitors Replaced + (/03L-0:on 821213,during Routine Channel Function Test,Steam Generator Steam Pressure Channel III Bistable Setpoint Observed Less than 480 Psig.Caused by Failure of Capacitor Incomparator 2PC 526 C/D.Capacitors Replaced)