- 05000318/LER-1981-006-03, /03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested + (/03L-0:on 810113 Diesel Generator 12 Switchgear Would Not Close in on 21 4-kV Bus Per Tech Spec.Caused by High Resistance at Secondary Disconnect.Continuity of Closing Circuit Interlocks Verified & Switchgear Tested)