- 05000316/LER-1980-031-03, /03L-0:on 800902,bistable for Containment Pressure hi-hi Protection Set II Tripped at 3.1005 Psig,Exceeding Limiting Conditions for Operation.Caused by Instrument Drift.Bistable Adjusted & Returned to Svc + (/03L-0:on 800902,bistable for Containment Pressure hi-hi Protection Set II Tripped at 3.1005 Psig,Exceeding Limiting Conditions for Operation.Caused by Instrument Drift.Bistable Adjusted & Returned to Svc)