- 05000304/LER-1980-020-03, /03L-0:on 800507,maint Personnel Found Steam Generator 2A Pressure Channel 2P-516 Low by 2.6%,exceeding Channel Accuracy.Caused by Instrument Drift of Transmitter. Transmitter Recalibr + (/03L-0:on 800507,maint Personnel Found Steam Generator 2A Pressure Channel 2P-516 Low by 2.6%,exceeding Channel Accuracy.Caused by Instrument Drift of Transmitter. Transmitter Recalibr)