- 05000366/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000328/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000339/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000333/LER-1982-060, Forwards LER 82-060/04T-0 +
- 05000387/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000315/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000325/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000373/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000369/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000302/LER-1978-060, Forwards LER 78-060/03L-0 +
- 05000302/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000317/LER-1982-060, Forwards LER 82-060/04X-0 +
- 05000219/LER-1982-060, Forwards LER 82-060/03L-0.Detailed Event Analysis Encl +
- 05000395/LER-1983-060, /03L-0:on 831117,investigation Into Previously Submitted LER 83-060 Revealed Four Testable Components Not Tested on Quarterly Basis.Caused by Inadequate Procedure.Test Procedures Revised +
- 05000335/LER-1982-060, Forwards LER 82-060/03L-0 +
- 05000346/LER-1982-060, Revised LER 82-060/03T-1:on 821111,during Steam & Feedwater Sys (SFS) Rupture Control Monthly test,48-volt Dc Power Supply in SFS Channel 2 Failed.Caused by Component Failure. Channel 2 re-energized +
- 05000387/LER-1983-060, Forwards LER 83-060/03L-0 +
- 05000458/LER-1986-060, Forwards Info Re Items Identified Subsequent to 861110 Conference Re Insp Rept 50-458/86-36.Addl Info Available in LER 86-60,submitted on 861113 +
- 05000304/LER-1978-060, Forwards LER 78-060/03L-0 +
- 05000321/LER-1982-060, Forwards LER 82-060/01T-0 +
- 05000327/LER-1987-060, :on 870827,inadvertent Diesel Generator Start Occurred.Caused by Inadequate Procedure During Shutdown Board 1B-B Maint.Energized Studs on Shutdown Board 1B-B Taped to Prevent Shorting Studs Together +
- 05000424/LER-1987-060, :on 871026,control Room Isolation Occurred. Caused by Inadequate Procedure.Lab Standing Order Issued to Provide Instructions for Resetting Setpoints W/O Activating High Level Alarm +
- 05000352/LER-1987-060, :on 871029,two Reactor Encl Isolations Occurred Due to Decreased Pressure Between Encl & Outside Atmosphere. Caused by Lack of Adequate Valve Tagging Sys.Mod 5561 Prepared to Correct Air Sys Deficiencies +
- 05000461/LER-1987-060, :on 871002,automatic Reactor Trip Occurred Due to Misoperation of non-class 1E 125 Volts Dc Breaker.Caused by Nonlicensed Operator.Nonlicensed Operator Counseled.One Line Diagram Relabeled +
- 05000440/LER-1987-060, :on 870822,turbine Bldg/Heater Bay Vent Radiation Monitor Found to Have Been Inoperable for Approx 19 H.Caused by Personnel Error Due to Inattention to Detail. Tagging Error Corrected & Noble Gas Sample Drawn +
- 05000456/LER-1987-060, :on 871206,reactor Manually Tripped.Caused by Blockage of Condensate/Condensate Booster Pump Suction Strainers.Walkdown of Condensate Sys Performed to Look for Piping/Hanger Damage +
- 05000440/LER-1986-060, :on 860610,Div 2 Diesel Generator (D/G) Test Reclassified as Valid Test & Failure.Caused by Incorrect Determination of Effect of Previous Maint on Governor Performance.Task Force Established to Monitor D/G Starts +
- 05000482/LER-1986-060, :on 861025,effluent Sample Flow to Unit Vent Sys Particulate & Iodine Sampler Gt RE-21A Isolated.Caused by Inadequate Calibr Procedure.Procedure Revised to Preclude Recurrence +
- 05000528/LER-1986-060, :on 861114,annunciator Alarm SG Isol VLV Trbl Annunciated in Control Room.Caused by Low Air Pressure in MSIV SG-UV-171.Train Air Reservoir B Repressurized +
- 05000327/LER-1986-060, :on 861229,control Room Isolation Occurred. Caused by Loose Connection of Plug on Wire Lead of Filter Capacitor.Connection Resoldered & Monitor Operability Verified +
- 05000354/LER-1986-060, :on 860816,suppression Pool Level Violated Tech Spec Limit.Caused by Sensing Loop Installation Error, Resulting in Incorrect Calculation of Calibr Data.Level Increased to within Tech Spec Limits +
- 05000498/LER-1988-060, :on 881013,automatic Actuation of Control Room Ventilation to Recirculation Mode Occurred.Caused by High Level Readings on Hydrochloric Acid Channel of Single Toxic Gas Analyzer.Automatic Actuation Removed +
- 05000413/LER-1985-060, :on 851010,both motor-driven Auxiliary Feedwater Pumps Automatically Started After Main Feedwater Pump Tripped on High Discharge Pressure.Caused by Unidentified Primary Coolant Sys Leak +
- 05000366/LER-1978-060-03, /03L-0 on 781031:during Procedure HNP-2-10531 & Reactor in Run Mode,The 2R43-S001 C Diesel Failed to Reach 250 RPM W/In 7 Seconds,Due to Faulty Elec Speed Switch Signal +
- 05000366/LER-1978-060, Forwards LER 78-060/03l-0 +
- 05000316/LER-1978-060-03, /03L-0 on 780809:with Reactor Pwr at 97% Computer Failed to Printout All F Scans. Investgation Determined Cause to Be Apdms Computer (Encl to 7809190234) +
- 05000482/LER-1987-060, :on 871222,P-4 Turbine Trip on Reactor Trip Function Not Incorporated Into Surveillance Testing Program & Not Tested.Caused by Personnel Error.Sts IC-215 Revised on 871224 to Include Surveillance Testing +
- 05000397/LER-1985-060, :on 851117,automatic RWCU Sys Isolation Occurred Due to RWCU High Delta Flow Exceeding Trip Setpoint.Cause Attributed to Air in Sensing Lines.Rwcu Sys Returned to Svc in Blowdown Mode +
- 05000315/LER-1985-060, :on 851111,ESF Actuation Occurred Which Resulted in Safety Injection & Steam Line Isolation.Caused by Testing Performed on Steam Flow Instruments & Auxiliary Feedwater Sys.Procedure Revised +
- 05000361/LER-1985-060, :on 851109,reactor Tripped Due to Dnbr/Local Power Density Trip Signals on Reactor Protection Sys.Caused by Hot Channel Axial Shape Index Reaching Core Protection Calculator Auxiliary Trip Setpoint +
- 05000325/LER-1985-060, :from 851031-1103 & on 851105,sampling of Main Condenser Offgas Treatment Sys & Explosive Gas Monitoring Sys Not Conducted.Caused by Personnel Failure.Caution Tags Affixed to Reactor Turbine Gauge Board +
- 05000454/LER-1985-060, :on 850616,refueling Water Storage Tank (RWST) Water Temp 103 F.Caused by Personnel Error in Not Observing Procedures for Placing RWST Heater Pump in & Out of Svc.New Procedure Being Written +
- 05000458/LER-1985-060, :on 851224,reactor Scrammed on Low Vessel Level 3 When Running Feedwater Pump Tripped & Discharge Valve on Standby Pump Failed to Open.Caused by Pump Bearing Failure & Incorrect Torque Switch Setting in Valve +
- 05000373/LER-1985-060-01, :on 850813,ammonia & Chlorine Detectors for Train a of Control Room/Auxiliary Electrical Equipment Room HVAC Sys Tripped.Caused by Momentary Loss of Power to Sys. Power Restored +
- 05000528/LER-1985-060, :on 850809,discovered That Chemical & Vol Control Sys Letdown Snubbers Not Functionally Tested within 12 Months Prior to Installation,Per Tech Spec 4.7.9(h). Caused by Inadequate Administrative Controls +
- 05000482/LER-1985-060, :on 850807,reactor Trip & Feedwater Isolation Initiated Along W/Auxiliary Feedwater Actuations & Steam Generator Blowdown & Sample Isolation.Turbine Trip Caused by Moisture Separator Reheater Control Problem +
- 05000352/LER-1985-060, :on 850623,fire Watch Patrol Failed to Inspect Diesel Generator Bay B within 1 H Limit.Caused by Inoperable Card Reader to Prevent Access to Area.Fire Watch Switched +
- 05000361/LER-1984-060, :on 841002,inflatable Seals Between Spent Fuel Storage Pool & Spent Fuel Shipping Container Pit Partially Deflated.Caused by Low Svc Air Pressure.Design Change Will Be Installed & Procedures Will Be Revised +
- 05000373/LER-1984-060-01, :on 840929,Div 1 High Steam Flow Isolation Received During Attempt to Reopen 1E51-F008 RCIC Outboard Isolation.Caused by Differential Pressure Created by Cooling Differences Upstream.Outboard Isolation Reset +
- 05000327/LER-1984-060, :on 840921,23,24,28,29 & 30,auxiliary Bldg Isolations Occurred.Caused by Spikes on Spent Fuel Pool Radiation Monitors.Signal Reset.Spent Fuel Pool Water Cleaned +