Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000321/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000366/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000327/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000416/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000331/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000237/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000395/LER-1982-055, Forwards LER 82-055/03L-0.Detailed Event Analysis Encl +
- 05000334/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000333/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000338/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000259/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000339/LER-1982-055, Forwards LER 82-055/01T-0 +
- 05000272/LER-1982-055, Forwards LER 82-055/03L-0.Detailed Event Analysis Encl +
- 05000315/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000302/LER-1978-055, Forwards LER 78-055/03L-0 +
- 05000369/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000316/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000335/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000317/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000416/LER-1983-055, Forwards LER 83-055/03L-0 +
- 05000346/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000387/LER-1982-055, Forwards LER 82-055/03L-0 +
- 05000387/LER-1983-055, Forwards LER 83-055/03L-0 +
- 05000296/LER-1982-055, Forwards Updated LER 82-055/03X-1 +
- 05000000/LER-1986-055, Forwards LER 86-055-00 Re Physical Security Event.Withheld (Ref 10CFR73.21) +
- 05000366/LER-1983-055, Updated LER 83-055/03X-1:on 830713 & 21,RCIC Pump 2E51-C002 Would Not Deliver 600 Gpm Required Tech Spec Flow.Caused by Unadjusted Electric Governor Remote Actuator.Actuator Adjusted.W/Amended +
- 05000327/LER-1987-055, :on 870217,Rev 0 to Significant Condition Rept SQNEEB8743 Issued Re Loss of Water Supply to Auxiliary Feedwater Sys.Caused by Design Deficiencies for Installation of Instrument Lines.Change Notices Issued +
- 05000440/LER-1987-055, :on 870729,reactor Protection Sys Actuation Occurred Due to Trip Signal Generated by Neutron Monitoring Sys Aprm.Caused by Misposition of Switch S-3 on APRM Card. Failed APRM Card Replaced & Tested +
- 05000352/LER-1987-055, :on 871002,nonconformance W/Fire Safe Shutdown Requirements Identified.Caused by Procedure Deficiency.Flow Switch Relays Removed & Flow Switch Deenergized.App R Review Evaluated +
- 05000424/LER-1987-055, :on 870318,RHR Discharge Valves (1-HV-8809A & 1-HV-8809B) Temporarily Closed Per Procedure Resulting in Loss of Availability of One RHR Pump.Caused by Personnel Error.Operations Evaluation Program Revised +
- 05000456/LER-1987-055, :on 870927,28 & 1002,Train B Containment Ventilation Isolation Signal Annunciated in Main Control Room.Caused by Defective Detector.Monitors Plastic Covering Rearranged & Temporary Warning Signs Posted +
- 05000461/LER-1987-055, :on 870921,reactor Protection Sys (RPS) Automatically Actuated.Caused by Faulty Reactor Feed Pump B Net Positive Suction Head Function Generator Card.Card Replaced & Calibr +
- 05000458/LER-1986-055, :on 860831,reactor Scrammed Due to Loss of Reactor Protection Sys Bus a Concurrent W/Failure of Sys Backup Scram Circuitry B.Caused by Failure of Cooling Tower Feeder Transformer.Mod Request Generated +
- 05000528/LER-1986-055, :on 861106,Surveillance Test 36ST-9SA02 Identified as Incomplete,Per Tech Spec 4.0.2.Caused by Inability to Position Control Room Intake Damper Due to Actuator Malfunction.Actuator Adjusted +
- 05000423/LER-1986-055, :on 861106,emergency Diesel Generator B Did Not Start within Required 10 During Surveillance Testing. Caused by Low Lube Oil & Jacket Water Temp.Another Start Performed After Lube Oil & Temps Increased +
- 05000413/LER-1986-055, :on 861004,diesel Generator 1A Started on Blackout Signal During Automatic Transfer Test of 6,900-volt Normal Auxiliary Power Sys.Cause Undetermined.Diesel Generator 1A Secured & Test Reperformed +
- 05000354/LER-1986-055, :on 860805,during Cold Shutdown,Channel a Primary Containment Isolation Occurred.Caused by Procedural Deficiency.Instrumentation & Control Procedures Revised to Include Logic Status Verification +
- 05000327/LER-1986-055, :on 861201,during Cold Shutdown,Auxiliary Bldg Isolation (Abi) Occurred W/O Associated Relays Sealed In. Cause Probably Due to Spike on Radiation Monitor 0-RM-90-102.Change Notice Issued +
- 05000440/LER-1986-055, :on 860902,reactor Scram Occurred.Caused by Sudden Increase in Sensed Pressure for Steam Bypass Valves Controller.Pressure Regulators & Instrumentation Valve Lineups Recalibr,Procedures Revised & Mgt Directive Issued +
- 05000498/LER-1988-055, :on 880930,automatic Actuation of Control Room Ventilation to Recirculation Mode Occurred.Caused by High Level Trip of Hydrochloric Acid Channel on One of Two Toxic Gas Analyzers.Analyzer Will Be Replaced +
- 05000352/LER-1985-055, :on 850529,isolation of RWCU Sys Occurred. Caused by Deficient Differential Temp Switch.Rwcu Sys Logic Reset,Panel 10C609 Inspected & TDTS-44-1N602AA Tested Four Times.No Defects Found +
- 05000341/LER-1987-055, :on 871210,isolation of RCIC Sys Steam Line Occurred.Caused by Inadequacy in Sys Operating Procedure.Rev Made to Operating Procedure Which Directs Operator to Throttle Inboard & Outboard Isolation Valves +
- 05000325/LER-1985-055, :on 851009,Units 1 & 2 Emergency Ac Electrical Diesel Generators auto-started & Diesel Generator 1 Tied on to Reenergize Units Common Emergency Ac Bus E-1.Caused by Ongoing Plant Mod.Procedure Revised +
- 05000259/LER-1985-055, :on 851122,during Maint Activities,Spare Sleeve Penetration in Fire Barrier Found Unsealed.Caused by Concealed Location Above Suspended Ceiling.Penetration Sealed +
- 05000413/LER-1985-055, :on 850919,backup Fire Hose for Auxiliary Bldg Hose Station Removed While Permanent Hose Station Still Inoperable.Caused by Procedural Deficiency.Wye Connection & Backup Hose Reinstalled +
- 05000361/LER-1985-055, :on 851029,fuel Handling Isolation Sys Train a Actuated by Signal from Fuel Handling Bldg Vent Airborne Process Radiation Monitor 2RE-7822B.Train B Manually Actuated.Caused by High Voltage Power Failure +
- 05000373/LER-1985-055-01, :on 850722,hydraulic Surge Resulted When Manual Stop Valve for Standby Liquid Control Opened to Relieve Pressure After Hydrostatic Test.Caused by Defective Procedure.Procedure Will Be Revised +
- 05000315/LER-1985-055, :on 851025,lower Containment Airborne Monitor Particulate Channel Train a High Alarmed,Resulting in ESF Actuation Signal.High Alarm & Alert Alarm Setpoint Readjusted +
- 05000458/LER-1985-055, :on 851210,following Loss of Reactor Protection Sys Bus D Power,Rwcu Sys Isolation & RHR Isolation Occurred During Baseline Performance of Surveillance Test Procedure. Caused by Personnel Error +
- 05000322/LER-1985-055, :on 851130,all Electrical Equipment Not Environmentally Qualified Removed from Plant.Two High Radiation Detectors Returned to Vendor.High Radiation Monitor Cable Assembly Checked Out +