- 05000325/LER-1982-142, Forwards LER 82-142/03L-0 +
- 05000311/LER-1982-142, Forwards LER 82-142/03L-0.Detailed Event Analysis Encl +
- 05000373/LER-1982-142, Forwards LER 82-142/03L-0 +
- 05000327/LER-1981-142, Forwards LER 81-142/03L-0 +
- 05000328/LER-1982-142, Forwards LER 82-142/03L-0 +
- 05000416/LER-1982-142, Forwards LER 82-142/99X-0 +
- 05000328/LER-1982-142-03, /03L-0:on 821229,while Running Surveillance Instruction 166.1 for Containment Isolation Valves,Valves 2-FCV-68-305 Failed to Open.Caused by Faulty Diaphragm. Diaphragm Replaced +
- 05000327/LER-1983-142-03, /03L-0:on 831007,w/unit in Mode 1,plant Procedure Listing safety-related Snubbers SI-162.1 Discovered Not in Agreement in Number W/Table 4.7.9a of Limiting Condition for Operation 3.7.9.Caused by Misinterpretation +
- 05000366/LER-1983-142-03, /03L-0:on 831208,during Performance of MSIV Leakage Control Sys Operability Procedure,Msiv B Leakage Control Sys Isolation Valve Failed to Complete Full Operating Cycle.Caused by Short in Motor +
- 05000373/LER-1983-142-03, /03L-0:on 831104,RHR Shutdown Cooling Suction Inboard Isolation Valve 2E12-F009 Failed to Open by Motor Operator or Manually.Caused by Closing of Valve When Hot, Resulting in Thermal Stress +
- 05000387/LER-1983-142-03, /03L-0:on 830929,jumper Caused Short Circuit in Relay Logic Board Resulting in Loss of Radiation Monitor & Ventilation Sys Isolation.Caused by Alligator Clips Falling Off Jumper.Logic Board Repaired +
- 05000395/LER-1983-142-03, /03L-0:on 831216,identified Leakage from RCS Determined to Be 10.4 Gpm,Exceeding Tech Spec Limit.Caused by Excessive Leakage from Seal 2 on Reactor Coolant Pump C & Packing Leaks +
- 05000416/LER-1982-142-99, /99X-0:on 821118,during Shutdown,Fire Barriers Broken in Control Room to Allow Cable Rerouting Per Approved Maint Work Order.Fire Watch Established.Fire Barriers Resealed Following Completion of Work +
- 05000361/LER-1982-142-01, /01T-0:on 821128,emergency Chiller E-335 Declared Inoperable,Rendering Creacus Train B Inoperable.Caused by Failure of Resistance Temp Detector in Motor Winding High Temp Trip Circuit.Spare Resistance Temp Detector Installed +
- 05000311/LER-1982-142-03, /03L-0:on 821123,steam Generator 21 Level Channel IV Indication Read 4% Higher than Other Channels & Declared Inoperable.Caused by Failure of Channel Level Transmitter. Transmitter Replaced +
- 05000325/LER-1982-142-03, /03L-0:on 821121,standby Gas Treatment Train 1B Stopped Running.Caused by Moisture Intrusion in Train Local Control Panel.Train 1B Dried & Cleaned & Control Logic Relays Replaced +
- 05000327/LER-1981-142-03, /03L-0:on 811118,auxiliary Feedwater Pressure Control Valve 1-PCV-3-122 Would Not Operate During Stroke Time Test.Caused by Inoperative Servo Valve in Hydraulic Sys Due to Clogged Passages from Containment Hydraulic Fluid +
- 05000373/LER-1982-142-03, /03L-0:on 821102,radwaste Valve OWL067 Did Not Fully Close When Tripped W/Simulated Radwaste Discharge hi-hi Trip Signal.Caused by Fouling of Valve Internals W/ Foreign Matls.Valve Cleaned +
- 05000324/LER-1981-142, Forwards LER 81-142/03L-0 +
- 05000324/LER-1981-142-03, /03L-0:on 811228,low Level Switch 2-B21-LIS-NO31D-B Actuated at Simulated Reactor Level of 104.53 Inches.Caused by Instrument Setpoint Drift.Switch Adjusted +
- 05000321/LER-1981-142, Forwards LER 81-142/03L-0 +
- 05000321/LER-1981-142-03, /03L-0:on 811225,reactor Water Conductivity Increased Above Tech Spec Limit.Caused by Tube Leaks of Waterbox C in Condenser B Due to Turbine Bucket & Diaphragm Metal Impingement.Turbines Repaired & Tubes Plugged +
- 05000324/LER-1982-142, Forwards LER 82-142/03L-0 +
- 05000324/LER-1982-142-03, /03L-0:on 821218,PCIV B32-F058B,located at RIP X-241B,found Closed.Caused by Const Personnel Accidently Bumping Valve &/Or Associated Instrument Piping.Valve Opened & Personnel Counseled +
- 05000369/LER-1981-142, Forwards LER 81-142/03L-0.Detailed Event Analysis Encl +
- 05000369/LER-1981-142-03, /03L-0:on 810819,both Channels of post-accident Containment Sump Level Instrumentation Indicated Water Levels W/No Water in Sump.Caused by Transmitters Shifting Out of Calibr Due to High Temp Conditions +
- 05000366/LER-1980-142, Forwards LER 80-142/03L-0 +
- 05000366/LER-1980-142-03, /03L-0:on 801014,while Operating at Steady State 2,138 Mwt Power Level,Break in 3-h Fire Rated Wall Identified.Caused by Personnel Oversight in Followup of Sealing New Penetrations.Fire Watch Posted +
- 05000327/LER-1980-142-03, /03L-0:on 800718,during Testing W/Unit in Mode 3, Ice Bed Temp Exceeded Tech Spec Limit of 27 F.Caused by Insufficient Recovery Time Between Personnel Entries & Exits.Work Halted & Temp Reduced to 27 F,19.5-h Later +
- 05000327/LER-1980-142, Forwards LER 80-142/03L-0 +
- 05000295/LER-1978-142, Cancelled +
- 05000338/LER-1979-142-01, /01T-0:on 791015,channel IV Steam Line Pressure Protection for Loop C Was Discovered to Be Swapped W/ Protection for Loop A.Caused by Incorrectly Connected Sensing Lines from Root Valves to Transmitters +
- 05000338/LER-1979-142, Forwards LER 79-142/01T-0 +