- 05000346/LER-1998-006, :on 980624,loss of Offsite Power Was Noted. Caused by Tornado Damage to Switchyard.Tested & Repaired Affected Electrical & Mechanical Equipment Necessary to Restore Two Offsite Power Sources +
- 05000285/LER-1988-027, :on 881020,steamfitter Disabled by Heat Exhaustion After Exiting Steam Generator.Caused by Contamination of Protective Clothing.First Aid Provided & Victim Taken to Hosp for Medical Treatment +
- 05000498/LER-1988-026, :on 880330,reactor Trip & Safety Injection Sequence Initiated Due to Partial Offsite Power Loss.Caused by Personnel Error & Design Inadequacy.Event Incorporated in Training Session & Protection Sys Evaluated +
- 05000413/LER-1988-010, :on 880211,unmonitored Release of Liquid Radwaste Into Environ Occurred.Caused by Personnel Error in Not Adequately Reviewing Info Before Starting Release. Incident Discussed W/Involved Personnel +
- 05000293/LER-1992-017, :on 921214,primary Containment Isolation Sys Groups 2 & 3 Actuations Occurred During RPS Power Supply Shift.Caused by B RPS Breaker Inadvertently Deenergizing. Operator Counseled +
- 05000334/LER-1996-008, :on 960531,reactor Trip Occurred.Caused by Test Circuit Applying More Test Current than Amount Required to Test Solenoid Coil.Performed Mod to Reduce Test Current for This Circuit to Lowest Practical Value +
- 05000440/LER-1996-004, :on 960502,maintenance Under Inadequate Tagout Resulted in Partial ESF Actuation.Caused by Personnel Errors.Personnel Responsible Will Be Retrained +
- 05000461/LER-1995-004, :on 950427,personnel Error During Plant Startup Resulted in Increased RP Above 150 Psig Prior to Rcics Being Operable.Shift Supervisor Discussed Event W/Lass & Emphasized Attention to Detail +