- 05000271/LER-1980-015, Forwards LER 80-015/03L-0 + (ML19309G348)
- ML19309G349 + (ML19309G349)
- 05000312/LER-1980-023, Forwards LER 80-023/01T-0 + (ML19309G350)
- 05000271/LER-1980-015-03, /03L-0:on 800401,during pre-startup Testing of Recirculation Pump Discharge Valve V-2-53B,valve Would Not Open Fully.Caused by Loose Pinion Gear on Limitorque-type Smb Motor Operator.Pinion Gear Was Replaced + (ML19309G352)
- ML19309G353 + (ML19309G353)
- ML19309G354 + (ML19309G354)
- 05000271/LER-1980-014, Forwards LER 80-014/03L-0 + (ML19309G355)
- ML19309G356 + (ML19309G356)
- 05000312/LER-1980-023-01, /01T-0:on 800414,vendor Notified Util That Representation for Specific Valves Will Not Be Provided Re Reliability & Operation for Other than Saturated Steam Svc. Cause Not Stated.Test Program Will Be Conducted + (ML19309G357)
- ML19309G358 + (ML19309G358)
- 05000313/LER-1980-011, Forwards LER 80-011/03L-0 + (ML19309G359)
- ML19309G360 + (ML19309G360)
- 05000271/LER-1980-014-03, /03L-0:on 800402,during Routine Reactor Startup, Operators Observed Frequency Drifting on Uninterrupted Ac Electrical Power sys-A.Caused by Setpoint Drift of Adjustable Frequency Potentiometer.Setpoint Readjusted + (ML19309G361)
- 05000348/LER-1980-025, Forwards LER 80-025/03L-0 + (ML19309G362)
- ML19309G363 + (ML19309G363)
- ML19309G364 + (ML19309G364)
- ML19309G365 + (ML19309G365)
- ML19309G366 + (ML19309G366)
- 05000313/LER-1980-011-03, /03L-0:on 800401,based on Sys Review Per IE Bulletin 79-14,certain Hangers Declared Inoperable.Cause Not Stated.Hangers Repaired or Modified within Required Time Limit on Affected Svc Water & Main Steam Sys + (ML19309G368)
- 05000409/LER-1980-002-01, /01T-0:on 800415,during Type C Leakage Testing, Containment Isolation Did Not Meet Test Criteria.Seat Ring on Upstream Containment Ventilation Isolation Exhaust Damper 73-25-005 Replaced & Leakage Rate Retested + (ML19309G369)
- 05000313/LER-1980-009, Forwards LER 80-009/03L-0 + (ML19309G370)
- ML19309G371 + (ML19309G371)
- ML19309G372 + (ML19309G372)
- 05000348/LER-1980-025-03, /03L-0:on 800331,0407 & 22,diesel Generator 1C Started & Reached Rated Speeds in Excess of Tech Spec Requirement.Lube Oil Sump Temp Below 120-130 F Range Was Only Abnormal Condition Found.Cause Under Investigation + (ML19309G373)
- 05000313/LER-1980-009-03, /03L-0:on 800328,while Performing Surveillance Test,Lead Hydrogen Purge Supply fan,VSF-30A Tripped on Overload.Caused by Check Valve HPA-5 Being Stuck,Due to Corrosion from Seal Water Leaking Onto Valve + (ML19309G374)
- ML19309G375 + (ML19309G375)
- 05000313/LER-1980-012, Forwards LER 80-012/03L-0 + (ML19309G377)
- ML19309G378 + (ML19309G378)
- 05000409/LER-1980-003-01, /01T-0:on 800417,during Type C Leakage Testing, Containment Isolation Did Not Meet Test Criteria.Seal Rings Which Exhibited Aging Due to Normal Wear replaced.Post-maint Leakage Rate Test on 800425 Exhibited Zero Leakage + (ML19309G379)
- 05000155/LER-1980-006-03, /03L-0:on 800403,following Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Was Removed from Svc to Correct Problem. Caused by Setpoint Drift.Unit Was Readjusted + (ML19309G380)
- 05000334/LER-1980-020, Forwards LER 80-020/03L-0 + (ML19309G381)
- ML19309G382 + (ML19309G382)
- 05000346/LER-1980-030, Forwards LER 80-030/01T-0 + (ML19309G383)
- ML19309G384 + (ML19309G384)
- 05000155/LER-1980-008-03, /03L-0:on 800411,following Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Was Removed from Svc to Correct Problem. Caused by Drift.Unit Was Readjusted + (ML19309G385)
- 05000334/LER-1980-020-03, /03L-0:on 800329,during Operations to Increase Level in RCS Loops,Vol Control Tank Outlet MOV-CH-115C Found Closed.Vol Control Tank Level Indicated Normally.Caused by Bad Fuse Holder for Level Bistable.Fuse Holder Replaced + (ML19309G386)
- ML19309G387 + (ML19309G387)
- 05000346/LER-1980-030-01, /01T-0:on 800418,contrary to Tech Spec 3.4.1,decay Heat Pump 1-2 Stopped When RCS Water Level Decreased to 37 Inches Above Hot Leg Piping Centerline.Caused by Valve Operator Component Failure.Work Order Issued for Adjustment + (ML19309G388)
- ML19309G389 + (ML19309G389)
- ML19309G390 + (ML19309G390)
- ML19309G391 + (ML19309G391)
- 05000312/LER-1980-022, Forwards LER 80-022/03L-0 + (ML19309G392)
- 05000313/LER-1980-012-03, /03L:on 800406,while Performing Monthly Inservice Valve Stroke Test,Emergency Feedwater Supply valves,CV2667 & CV2617,failed to Fully Open.Caused by Binding Due to Loose Bolts Securing Actuator + (ML19309G394)
- ML19309G395 + (ML19309G395)
- ML19309G396 + (ML19309G396)
- 05000312/LER-1980-022-03, /03L-0:on 800406,refueling Test Revealed Valve Sfv 53603 Returned to Open Position After Signal Reset.Caused by Sticking Blpb Open Contacts.Blpb Replaced & Valve Successfully Tested + (ML19309G397)
- 05000266/LER-1980-004, Forwards LER 80-004/03L-0 + (ML19309G398)
- ML19309G399 + (ML19309G399)
- ML19309G400 + (ML19309G400)
- 05000282/LER-1980-012, Forwards LER 80-012/03L-0 + (ML19309G402)
- ML19309G403 + (ML19309G403)