The licensee reported in LER 2008-005-00 tThe licensee reported in LER 2008-005-00 that the train B, Class 1E electrical equipment room cooler was miswired during replacement such that it might not be operable following a control room fire. This represented a violation of License Condition 2.C.(5), Fire Protection. A bounding Phase 3 evaluation concluded that this issue had very low safety significance (Green) since only 4 of the 103 control room cabinets could lead to a loss of the train B, Class 1E electrical equipment room cooler. This issue was entered into the licensees corrective action program as performance improvement request 2008-001896.rformance improvement request 2008-001896.  +
23:59:59, 30 September 2011  +
05000482  +
23:59:59, 30 September 2011  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
15:43:07, 30 May 2018  +
23:59:59, 30 September 2011  +
Licensee-Identified Violation  +