Browse wiki

Jump to navigation Jump to search
Comanche Peak Unit 1, Operating License NPComanche Peak Unit 1, Operating License NPF-87, Condition 2.G, Fire Protection, requires, in part, that the licensee implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report through Amendment 78 and as approved in the Safety Evaluation Report and its supplements through Supplement 24. Comanche Peak Unit 2, Operating License NPF-89, Condition 2.G, Fire Protection, requires, in part, that the licensee implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report through Amendment 87 and as approved in the Safety Evaluation Report and its supplements through Supplement 27. The stations approved fire protection program includes Fire Protection Report, Revision 29, Section 5.3.8, Fire Area EO Control Room, includes Deviation 3c-1, Control Room Missile Door, which requires, in part, that since the control room missile door in the west wall is not a three hour rated fire door, the area of the turbine deck within 100 feet of the door is to be void of combustibles. Contrary to the above, on May 5, 2016, the licensee stored combustible materials within 100 feet of the control room missile door in the west wall. Specifically, licensee personnel identified that contractors had stored combustibles within the combustible free zone, and that no compensatory measures had been implemented for the deviation from the Fire Protection Report. The licensee implemented a periodic roving fire watch to compensate for the reduction in fire protection. The violation is more than minor because if left uncorrected, it could lead to a more significant safety concern. Using Inspection Manual Chapter 0609, Attachment 04, Initial Characterization of Findings, and Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, the inspector determined that the violation is of very low safety significance (Green) because the finding did not affect the ability of either unit to achieve safe shutdown. The violation was entered into the licensees corrective action program as CR-2016-004167.rrective action program as CR-2016-004167.  
23:59:59, 30 June 2016  +
05000445  +
23:59:59, 30 June 2016  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
15:54:28, 30 May 2018  +
23:59:59, 30 June 2016  +
Licensee-Identified Violation  +