10 CFR 50.65(a)(4) requires the licensee t10 CFR 50.65(a)(4) requires the licensee to assess and manage risk that may result from proposed maintenance activities. Contrary to the above, on September 29, while performing engineered safety features actuation system (ESFAS) testing, the licensee identified that the boric acid injection tank inlet valves (1HV8803A/B) were closed which isolated a secondary boration flow path they had credited in their outage risk assessment. Without that credited boration flow path, the unit was in a Yellow risk condition, versus the Green risk condition that had been vetted and published. The licensee documented this event in their corrective action program as CR 526195. Using Checklist 4 of IMC 0609 Appendix G Attachment 1, the inspectors concluded that the violation was of very low safety significance.ation was of very low safety significance.  +
23:59:59, 30 September 2012  +
05000424  +  and 05000425  +
23:59:59, 30 September 2012  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:46:15, 21 February 2018  +
23:59:59, 30 September 2012  +
Failure to Assess Maintenance Activities for Risk Causes an Inadvertent Loss of a Boration Flow Path and a Unplanned Risk Change  +