Browse wiki
Jump to navigation
Jump to search
A licensee-identified violation of 10 CFR … A licensee-identified violation of 10 CFR 50, Appendix B, Criterion III, was discovered in March 2014, during a planned visual inspection of the upper internals in SG-2A and SG-2B. The licensee identified damage to the feedring in both steam generators as a result of a thermal-hydraulic transient. The transient caused an increase in feedring pressure, damage to the feedring supports, and increased stresses on the feedring piping and feedwater nozzle. The transient was attributed to leakage from the feedring bolted inspection covers, which were modified in 2011 through the engineering change process. 10 CFR 50, Appendix B, Criterion III, Design Control, states that design control measures shall provide for verifying or checking the adequacy of design, such as by the performance of design reviews, by the use of alternate or simplified calculational methods, or by the performance of a suitable testing program. Contrary to the above, on January 18, 2011, the licensee failed to establish design control measures that provided for verifying or checking the adequacy of the modified feedring inspection cover design to maintain the safety related function of the steam generators. The modification replaced the feedring inspection covers, the gaskets, and the bolts lock washers in SG-2A and SG-2B. However, in March 2014, the modification was determined to be inadequate, resulting in leakage through the bolted inspection covers and consequently in a thermal hydraulic transient that affected the safety-related portion of the steam generators. This violation was determined to be of very low safety significance (Green) because SG-2A and SG-2B maintained their operability and functionality, and therefore resulted in no loss of safety function. The licensee entered this violation in the corrective action program as AR 01951667. corrective action program as AR 01951667. +
23:59:59, 30 June 2014 +
23:59:59, 30 June 2014 +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 +, 05000389/FIN-2014008-02 + and 05000389/FIN-2014008-02 +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
15:51:02, 30 May 2018 +
23:59:59, 30 June 2014 +
Steam Generator + and Feedwater +