The inspectors identified a non-cited violThe inspectors identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, because the licensee did not conduct required technical specification surveillance testing on equipment in an as-found condition. Specifically, the licensee performed corrective maintenance (preconditioning) on the system to achieve better results, prior to completing the surveillance. The licensee entered this issue into their corrective action program for resolution as CR-WF3-2011-1927. The immediate corrective action included the performance of the control room envelope tracer gas test. The finding is more than minor because it is associated with the barrier performance attribute of the barrier integrity cornerstone and affects the cornerstone objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. Specifically, the licensee did not properly perform testing on equipment to evaluate barrier performance. The inspectors evaluated this finding using IMC 0609 Attachment 4, Phase 1 Initial Screening and Characterization of Findings. The inspectors determined that the finding is of very low safety significance (Green) because the finding doesnt represent a degradation of the radiological barrier, or the smoke and toxic gas barrier functions provided for the control room. The finding has a cross-cutting aspect in the work control component of the human performance area because the licensee did not appropriately plan work activities by incorporating the need for planned contingencies, compensatory actions, and abort criteria (H.3.a of IMC 0310)ns, and abort criteria (H.3.a of IMC 0310)  +
23:59:59, 31 March 2011  +
05000382  +
23:59:59, 31 March 2011  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
19:06:48, 30 September 2017  +
23:59:59, 31 March 2011  +
Control Room Envelope Preconditioning  +