The following violation of very low safetyThe following violation of very low safety significance (Green) was identified by the licensee and is a violation of NRC requirements which meets the criteria of the NRC Enforcement Policy, for being dispositioned as a Non-Cited Violation. Since June of 1999, the licensee cross-tied the two starting air receivers for a given EDG when performing maintenance on one of the air start compressors. TS 3.8.3 required that the starting air subsystem for each EDG be within limits when the associated EDG was required to be operable. TS 3.8.3 Condition D applied if one or more EDGs had one of two starting air receiver pressures < 210 psig. The cross-tied starting air receivers reduced the number of air receivers from two to one which placed the subsystem outside the licensing basis for TS 3.8.3 Condition D. If Condition D was not met, then Condition E required that the associated EDG be declared inoperable. TS 3.8.1 Condition B required that when an EDG was inoperable, it should be restored to operable status within 72 hours. If Condition B was not met, Condition G required that the unit be in Mode 3 in 6 hours and in Mode 5 in 36 hours. Contrary to the above, between June 29, 1999, and August 13, 2010, on multiple occasions the starting air receivers were cross-tied resulting in an EDG being inoperable for greater than 72 hours and the licensee not placing the unit in Mode 3 within 6 hours or Mode 5 within 36 hours. This violation is of very low safety significance (Green) because the cross-tied air receivers remained pressurized greater than or equal to 210 psig. This violation is in the licensees corrective action program as PIP M-10-5299.s corrective action program as PIP M-10-5299.  +
23:59:59, 31 December 2010  +
05000369  +  and 05000370  +
23:59:59, 31 December 2010  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
8.333333e-4 d (0.02 hours, 1.190476e-4 weeks, 2.7396e-5 months)  +, 6.944444e-5 d (0.00167 hours, 9.920635e-6 weeks, 2.283e-6 months)  +  and 4.166667e-4 d (0.01 hours, 5.952381e-5 weeks, 1.3698e-5 months)  +
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
15:40:38, 30 May 2018  +
Mcguire +  and McGuire +
23:59:59, 31 December 2010  +
TS-3.8.1 +  and TS-3.8.3 +