A non-cited violation of 10CFR50.59 was idA non-cited violation of 10CFR50.59 was identified by the inspectors for changing the design of the auxiliary feedwater system as described in the Updated Final Safety Analysis Report without performing a safety evaluation or obtaining a Technical Specification change. The change reduced the required number of trains of auxiliary feedwater from three independent trains to two independent trains to safely shutdown the reactor.</br>This failure to perform a safety evaluation and submit a Technical Specification change is more than minor because it would require an NRC review prior to implementation. Because there was no evidence to indicate that the licensee had used the change the safety significance was determined to be very low. Consequently, the regulatory significance was categorized as a Severity Level IV violation.egorized as a Severity Level IV violation.  +
23:59:59, 30 September 2004  +
05000369  +  and 05000370  +
23:59:59, 30 September 2004  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:31:30, 21 February 2018  +
Mcguire +  and McGuire +
23:59:59, 30 September 2004  +
Failure to Obtain a License Amendment Prior to Implementing a Design Change to the Facility Associated with the Auxiliary Feedwater System  +