Browse wiki

Jump to navigation Jump to search
The inspectors identified a non-cited violThe inspectors identified a non-cited violation of 10CFR50.59 for failure to obtain a license amendment prior to implementing a change to plant procedures that involved an unreviewed safety question. The unreviewed safety question dealt with extending the availability of non- seismic condenser circulating water piping to perform a safety-related function following a seismic event. This issue is more than minor because it would require NRC review prior to implementation. A subsequent engineering evaluation determined that the non-seismic piping would not collapse or kink, and although it may leak, it will provide the necessary minimal service water flow function. Since the technical issue was determined to be of very low safety significance, the regulatory significance was categorized as a Severity Level IV violation.egorized as a Severity Level IV violation.  +
23:59:59, 30 September 2004  +
05000369  +  and 05000370  +
23:59:59, 30 September 2004  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
00:31:30, 21 February 2018  +
23:59:59, 30 September 2004  +
Failure to Obtain a License Amendment Prior to Implementing an Unreviewed Safety Question Associated with the Nuclear Service Water System  +