Technical Specification 3.3.7.1, MonitorinTechnical Specification 3.3.7.1, Monitoring Instrumentation Radiation Monitoring Instrumentation, requires one operable reactor enclosure cooling water (RECW) system radiation monitor channel at all times. Action 72 of Table 3.3.7.1-1 requires obtaining a grab sample every 24 hours with the required monitor inoperable. Contrary to TS 3.3.7.1, the required RECW Radiation Monitor was inoperable in Unit 2 from March 24, 2008 until April 15, 2008 without obtaining a grab sample every 24 hours. The event is documented in Exelons CAP as IR 763510. The finding was of very low safety significance because it does not represent an open pathway in the physical integrity of reactor containment physical integrity of reactor containment  +
23:59:59, 30 June 2008  +
05000352  +  and 05000353  +
23:59:59, 30 June 2008  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
2.777778e-4 d (0.00667 hours, 3.968254e-5 weeks, 9.132e-6 months)  +