NRC-89-0257, Ro:On 891115,second Start Failure of Emergency Diesel Generator 14 Occurred.Caused by Test Personnel Incorrectly Determining ECCS Signal Voltage & Frequency.Surveillances Completed,Indicating That Problem self-corrected | 15 December 1989 | Ro:On 891115,second Start Failure of Emergency Diesel Generator 14 Occurred.Caused by Test Personnel Incorrectly Determining ECCS Signal Voltage & Frequency.Surveillances Completed,Indicating That Problem self-corrected | |
NRC-89-0253, Ro:On 891110,emergency Diesel Generator Start Failure Occurred.Caused by Human Error During Test Start.Wire at Terminal B2803 Determinated & Correctly Reterminated W/No Stray Strands.Engine Restarted & Surveillance Completed | 11 December 1989 | Ro:On 891110,emergency Diesel Generator Start Failure Occurred.Caused by Human Error During Test Start.Wire at Terminal B2803 Determinated & Correctly Reterminated W/No Stray Strands.Engine Restarted & Surveillance Completed |