RBG-41155, Monthly Operating Rept for Dec 1994 for River Bend Station
| ML20077S118 | |
| Person / Time | |
|---|---|
| Site: | River Bend |
| Issue date: | 12/31/1994 |
| From: | James Fisicaro, Glueck D ENTERGY OPERATIONS, INC. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| RBF1-95-0013, RBF1-95-13, RBG-41155, NUDOCS 9501230295 | |
| Download: ML20077S118 (6) | |
Text
-
q Ent:rgy Operations,Inc.
Arver Bend Station 5485 U.S Highway 61
' = ENTERGY l r*e" ""
u w5 Tel 504 336 6225 Fax 504 635 5(E8 James J. Fisicaro Director Nuclear Safety January 13,1995 l
U.S. Nuclear Regulatory Commission Document Control Desk M/S PI-37 Washington, DC 20555
Subject:
River Bend Station - Unit 1 Docket No. 50-458 i
Monthly Operating Report File No.:
G9.5, G4.25 REG-41155 RBF1-95-0013 Gentlemen:
In accordance with River Bend Station (RBS) Technical Specification 6.9.1.6, enclosed is the December 1994 Monthly Operating Report for RBS - Unit 1.
Sincerely, dg-6 Af KDG/jr i
enclosure 210hbb 9501230295 941231
~
DR ADOCK 050 g
./
I v
~
e 4
/
Decer$1ber 1994 Monthly Operating Report January 13,1995 RBG-41155 RBF1-95-0013 Page 2 of 2 cc:
U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011 NRC Senior Resident Inspector P.O. Box 1051 l
St. Francisville, LA 70775 l
INPO Records Center 1100 Circle 75 Parkway Atlanta, GA 30339 l
Chester R. Oberg l
PUCT j
7800 Shoal Creek Blvd., Suite 400N Austin, TX 78757 Dottie Sherman American Nuclear Insurers 29 South Main Street West Hartford, CN 06107 Cajun Electric Power Co-op, Inc.
I u
=s
4 s
DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO.
R-94-12 DATE January 10.1995 COMPLETED BY D. R. Glueck TITLE Senior Ennineer TELEPilONE 504-381-4317 MONTII December.1994 DAY AVERAGE DAILY DAY AVERAGE DAILY POWER LEVEL POWER LEVEL (MWe-Net)
(MWe-Net) 1.
940.7 17.
924.4 2.
935.4 18.
942.0 3.
932.4 19.
940.5 4.
777.I 20.
937.8 5.
0 21.
936.8 6.
0 22.
938.9 7.
0 23, 936.5 8.
0 24, 940.9 9.
0 25.
941.0 10.
0 26.
940.8 11.
0 27.
939.5 12, 293.7 28.
936.5 x
13.
888.4 29, 936.0 14.
939.8 30.
929.3 I 5.
937.2 31.
913.6 16.
928.0
f M
i DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 i
REPORT NO.
R-94-12 DATE January 10.1995 COMPLETED BY D. R. Glueck TITLE Senior Ennineer TELEPHONE-504-381-4317 L
PAGE 1
OF 2 OPERATING STATUS
- 1. REPORTING PERIOD: December 1994 GROSS IlOURS IN REPORTING PERIOD:
744
- 2. CURRENTLY AUTilORIZED POWER LEVEL (Mwt): 2894 MAX. DEPEND CAPACITY (MWe-Net): 926 DESIGN ELECTRICAL RATING (MWe-Net): 936 t
- 3. POWER LEVEL TO WillCli RESTRICTED (l!r ANY)(MWe-Net): N/A
- 4. REASONS FOR RESTRICTION (IF ANY): N/A i
THIS YR TO CUMU-MONTli DATE LATIVE
- 5. NUMBER OF 110URS REACTOR WAS CRITICAL 594.9 5684.3 56496.2
- 6. REACTOR RESERVE SIIUTDOWN IIOURS 0
0 0
- 7. IIOURS GENERATOR ON LINE 566.4 5457.7 53439.1 l
- 8. UNIT RESERVE SilUTDOWN llOURS 0
0 0
a
- 9. GROSS T11ERMAL ENERGY GENERATED (MWil) 1.605.590 15.373.344 143.073.013
- 10. GROSS ELECTRICAL ENERGY GENERATED (MWil) 553.365 5.218.447 48.382.055
- 11. NET ELECTRICAL ENERGY GENERATED (MWil) 518.572 4.886.231 45.275.732 i
DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO.
R-94-12 DATE January 10.1995 COMPLETED BY D. R. Glueck TITLE Senior Eneineer TELEPHONE 504-381-4317 PAGE 2
OF 2
OPERATING STATUS tills YR TO CUMU-MONTII DATE LATIVE
- 12. REACTOR SERVICE FACTOR 80.0 64.9 70.7 13 REACTOR AVAILABILITY FACTOR 80.0 64.9 70.7
- 14. UNIT SERVICE FACTOR 76.1 62.3 68.4
- 15. UNIT AVAILABILITY FACTOR 76.1 62.3 68.4
- 16. UNIT CAPACITY FACTOR (USING MDC) 74.5 59.6 63.2
- 17. UNIT CAPACITY FACTOR (USING DESIGN MWe) 74.5 59.6 63.2
- 18. UNIT FORCED OUTAGE RATE 23.9 19.7 14.1
- 19. SIIUTDOWNS SCIIEDULED OVER NEXT SIX MONTIIS (TYPE, DATE, AND DURATION OF EACH):
NO SIIUTDOWNS SCIIEDULED OVER NEXT SIX MONTIIS
- 20. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
N/A
UNIT SHUTDOWNS AND POWER REDUCTIONS TIME TLME START RECOVER OF FROM DURATION TYPE REASON METHOD CORRECTIVE ACTION /
NO.
DATE OCCURR',NCE OCCURRENCE (HOURS)
NOTE (1) NOTE (2) NOTE (3)
COMMENTS FO 94-03 12-4-94 1958 12-12-94 0535 177.62 F
H 3
An automatic shutdown occurred when the isolation logic was satisfied and a full MSIV isolation occurred during the performance of STP 058-4501, Containment and Drywll ManualIsolation A tuation ChannelFuncuonalTest.
SUMMARY
NODI (1)
TYPE OF OCCURRENCE:
ENITIR CODE DOCKETNO. 50/458 F:
FORCED RIVER BEND STATION UNIT 1 S:
SCHEDULED NOTE (2)
PEASON FOR OCCURRENCE: ENTER CODE REPORT NO.
R-94-12 A:
EQUIPMENT FAILURE (EXPLAIN IN CORRECTIVE ACTIONS / COMMENTS)
B:
MALNTENANCE ORTEST REPORTMONTH December.1994 C:
REFUELING D:
REGULATORY RESTRICTION E:
OPERATORTRAINING AND LICENSE EXAMINATION DATE January 10.1995 F:
ADMINISTRATIVE G:
OPERATIONAL ERROR (EXPLAIN IN CORRECTIVE ACTIONC/ COMMENTS)
D. R. Glucck H:
OTHER (EXPLAIN IN CORRECTIVE ACTIONS / COMMENTS)
COMPLETED BY NOTE (3)
METHOD OF SHIJITING DOWN REACTOR OR REDUCING POWER:
ENTER ONE
'SIDNATURE 1.
MANUAL 2.
MANUAL SCRAM Senior Mech. Engineer 3.
AUTOMATIC SCRAM TTILE 4.
OTHER (EXPLAIN IN CORRECTIVE ACTION / COMMENTS)
(
TELEPHONE: 504-381-4317
~..
-