~ Southern Nuclear Cheryl A. Gayheart Regulatory Affairs Director 40 Inverness Center Park way Post Office Box 1295 Bimtingharn. AL Yi242 205 992 5316 tel 205 992 760 I fax MAY 1 4 2018 cagayhea@1;outhernco.com Docket Nos.: 50-321 50-348 50-424 NL-18-0539 50-366 50-364 50-425 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Ladies and Gentlemen:

Southern Nuclear Operating Company (SNC) is the licensed operator for the Edwin I. Hatch Nuclear Plant (Hatch) Units 1 & 2, the Joseph M. Farley Nuclear Plant (Farley) Units 1 and 2, and the Vogtle Electric Generating Plant (Vogtle), Units 1 and 2. The requirements of 10 CFR 50.46(a)(3)(ii) include an annual report by licensees of changes to or errors in acceptable emergency core cooling system (ECCS) models that affect the temperature calculation and the estimated effect of changes or errors on the limiting ECCS analysis. Accordingly, the reports required by 10 CFR 50.46(a)(3)(ii) for Hatch, Farley and Vogtle are provided in Enclosures 1, 2, and 3. The resulting peak cladding temperature (PCT) for Hatch, Farley and Vogtle continue to meet the criterion of 10 CFR 50.46(b)(1) (i.e., s 2200°F). HNP Unit 2 Cycle 25 is the first unit to load GNF3 lead use assemblies (LUAs). The cycle began in the first quarter of 2017.

This letter contains no NRC commitments. If you have any questions, please contact Jamie Coleman at 205.992.6611.

Respectfully submitted, Cheryl ~ a eart Regulatory Affairs Director CAG/PDB/CBG

U.S. Nuclear Regulatory Commission NL-18-0539 Page2

Enclosures:

1. Edwin I. Hatch Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017
2. Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017
3. Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 cc: Regional Administrator, Region II NRR Project Manager- Farley, Hatch, Vogtle 1 & 2 Senior Resident Inspector- Farley, Hatch, Vogtle 1 & 2 NRR Project Manager -Farley, Hatch, Vogtle 1 & 2 RType: Farley=CFA04.054 Hatch=CHA02.004, Vogtle=CVC7000

Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Enclosure 1 Edwin I. Hatch Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 to NL-18-0539 Edwin I. Hatch Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Edwin I. Hatch Nuclear Plant Unit 1 Table 1-1a- SAfERIGESTR-LOCA Summary of Changes I Errors (2017) (GE14)

Estimated Description Effect

(~ PCT)

None affecting PCT 0 Table 1-1b- SAfERIPRIME-LOCA Summary of Changes I Errors (2017) (GNf2)

Estimated Description Effect

(~ PCT)

None affecting PCT 0 Table 1-1c- Cumulative Impact of Changes /Errors GE14 GNf2 Description ~ IPCTI ~ IPCTI (Of) (Of)

  • Changes/Errors Previously Reported (Reference 1) 0 0
  • Summary of Changes/Errors (2017) (Reference 2) 0 0 Cumulative 0 0 Total E1-1 to NL-18-0539 Edwin I. Hatch Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Edwin I. Hatch Nuclear Plant Unit 2 Table 1-2a- SAFERIGESTR-LOCA Summary of Changes I Errors (2017) (GE14)

Estimated Effect Description (11 PCT)

None affecting PCT 0 Table 1-2b- SAFERIPRIME-LOCA Summary of Changes I Errors (2017) (GNF2)

Estimated Effect Description

{11 PCT)

None affecting PCT 0 Table 1-2c- SAFER/PRIME-LOCA Summary of Changes I Errors (2017) (GNF3- LUAs)

Estimated Description Effect

{11 PCT)

None affecting PCT 1 0 Table 1-2d- Cumulative Impact of Changes /Errors GNF3 GE14 GNF2 (LUAs)

Description 11IPCTI 11IPCTI (oF) (oF) 11IPCTI (oF)1

  • Changes/Errors Previously Reported (Reference 1) 0 0 0
  • Summary of Changes/Errors (2017) (Reference 3) 0 0 0 Cumulative 0 0 0 Total 1

GNF3 LUAs have a PCT 50 degrees greater than GNF2 assemblies.

E1-2 to NL-18-0539 Edwin I. Hatch Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017

Reference:

1. Letter from J.J. Hutto to USNRC {NL-17-0463) ML17110A061, "Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2016," dated April 20, 2017
2. Global Nuclear Fuel 004N0711, "Supplemental Reload Licensing Report for Hatch 1 Reload 28 Cycle 29," dated November 2017
3. Global Nuclear Fuel 002N6847, "Supplemental Reload Licensing Report for Hatch 2 Reload 24 Cycle 25," dated November 2016 E1-3

Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Enclosure 2 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 to NL-18-0539 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Joseph M. Farley Nuclear Plant - Unit 1 ASTRUM Best Estimate Large Break LOCA Evaluation Table 1-1a- Summary of Changes/Errors (2017)

Estimated Description Effect

(~ PCT°F)

None affecting PCT 0 Table 1-1b- Cumulative Impact of Changes/Errors

~ IPCTI Description (Of)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Summary of Changes/Errors {2017) (Reference 2) 0 Cumulative Total 0 E2-1 to NL-18-0539 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Joseph M. Farley Nuclear Plant - Unit 1 NOTRUMP Appendix K Small Break LOCA Evaluation Table 1-1c- Summary of Changes/Errors (2017)

Estimated Description Effect

(.:1 PCT °F)

None affecting PCT 0 Table 1-1d- Cumulative Impact of Changes/Errors L1IPCTI Description (oF)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Summary of Changes/Errors (2017) (Reference 2) 0 Cumulative Total 0 E2-2 to NL-18-0539 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Joseph M. Farley Nuclear Plant - Unit 2 ASTRUM Best Estimate Large Break LOCA Evaluation Table 1-2a- Summary of Changes/Errors (2017)

Estimated Description Effect

(~ PCT °F)

None affecting PCT 0 Table 1-2b - Cumulative Impact of Changes/Errors

~ IPCTI Description (oF)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Summary of Changes/Errors (2017) (Reference 2) 0 Cumulative Total 0 E2-3 to NL-18-0539 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Joseph M. Farley Nuclear Plant - Unit 2 NOTRUMP Appendix K Small Break LOCA Evaluation Table 1-2c- Summary of Changes/Errors (2017)

Estimated Description Effect

(~ PCT °F)

None affecting PCT 0 Table 1-2d - Cumulative Impact of Changes/Errors

~ IPCTI Description (Of)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Summary of Changes/Errors (2017) (Reference 2) 0 Cumulative Total 0 E2-4 to NL-18-0539 Joseph M. Farley Nuclear Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017

References:

1. Letter from J.J. Hutto to USNRC (NL-17-0463) ML17110A061, "Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2016," dated April 20, 2017
2. Westinghouse Letter LTR-LIS-18-20, "J. M. Farley Units 1 and 2, 10 CFR 50.46 Annual Notification and Reporting for 2017," dated February 15, 2018 E2-5

Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Enclosure 3 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 to NL-18-0539 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Vogtle Electric Generating Plant- Unit 1 BASH Large Break LOCA Evaluation Table 1-1a- Summary of Changes/Errors (2017)

Estimated Effect Description

(~ PCT) (°F)

None affecting PCT 0 Table 1-1b- Cumulative Impact of Changes/Errors

~IPCTI Description (oF)

  • Changes/Errors Previously Reported (Reference 1) 29
  • Summary of Changes/Errors (2017) (Reference 2) 0 Cumulative Total 29 E3-1 to NL-18-0539 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Vogtle Electric Generating Plant- Unit 1 Appendix K Small Break LOCA Evaluation Table 1-1c- Summary of Changes/Errors (2017)

Estimated Effect Description

{.!l PCT)

None affecting PCT 0 Table 1-1d- Cumulative Impact of Changes/Errors iliPCTI Description (oF)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Changes/Errors 2017 Calendar Year (Reference 2) 0 Cumulative Total 0 E3-2 to NL-18-0539 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Vogtle Electric Generating Plant - Unit 2 BASH Large Break LOCA Evaluation Table 1-2a - Summary of Changes/Errors (2017)

Estimated Description Effect

(~ PCT)

None affecting PCT 0 Table 1-2b - Cumulative Impact of Changes/Errors

~IPCTI Description (oF)

  • Changes/Errors Previously Reported (Reference 1) 29
  • Summary of Changes/Errors (2017) (Reference 2) 0 Cumulative Total 29 E3-3 to NL-18-0539 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017 Vogtle Electric Generating Plant - Unit 2 Appendix K Small Break LOCA Evaluation Table 1-2c- Summary of Changes/Errors (2017)

Estimated Effect Description

(~ PCT)

None affecting PCT 0 Table 1-2d -Cumulative Impact of Changes/Errors

~IPCTI Description (Of)

  • Changes/Errors Previously Reported (Reference 1) 0
  • Changes/Errors 2017 Calendar Year (Reference 2) 0 Cumulative Total 0 E3-4 to NL-18-0539 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2017

References:

1. Letter from J.J. Hutto to USNRC (NL-17-0463) ML 1711 OA061, "Edwin I. Hatch Nuclear Plant Units 1 and 2 Joseph M. Farley Nuclear Plant Units 1 and 2 Vogtle Electric Generating Plant Units 1 and 2 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2016," dated April 20,2017
2. Westinghouse Letter LTR-LIS-18-37, II A. W. Vogtle Units 1 and 2, 10 CFR 50.46 Annual Notification and Reporting for 2017, II dated February 15, 2018 E3-5