6.1-5 Revision 0 SUBJECT TO DOE COOPERATIVE AGREEMENT NO. DE-NE0009040 Copyright © 2025 Long Mott Energy, LLC All Rights Reserved Long Mott Generating Station Preliminary Safety Analysis Report When a non-safety-related SSC is required to protect the SR SSCs in their ability to perform their RSFs, such non-safety-related SSCs are not necessarily NSRST. The NSRST classifications are based on the Probabilistic Risk Assessment (PRA) Safety Functions (PSFs) these SSCs perform to prevent or mitigate event sequences and not functions that are focused on protecting the SR SSCs.
Table 6.1-3 provides the non-safety related SSCs that have design requirements to protect the SR SSCs performing their RSFs in response to DBHL.
References None Tables Table 6.1-1: Table of Design Basis Hazard Levels Design Basis Hazard Level Summary of Basis for Parameters Seismic PGA: Horizontal: 0.1853g Vertical: 0.1160g GMRS: see Figure 2.5.2-4856 See PSAR Section 2.5.2 High Winds (structural) 210 mph See PSAR Section 2.3.1 External Floods 10.47 ft above plant grade 36.38 ft (still water) NAVD 88 46.49 ft (with wave runup)
NAVD 88 See PSAR Section 2.4.5.6 Internal Fires Will be provided in the Operating License Application Pending detailed plant design information Internal Floods Will be provided in the Operating License Application Pending detailed plant design information High Energy Line Breaks Will be provided in the Operating License Application Pending detailed plant design information Other Will be provided in the Operating License Application Pending detailed plant design information