GNii=
Global Nuclear Fuel M250338 October 20th, 2025 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C. 20555-0001 Global Nuclear Fuel Chandi Davidson Facility Licensing 3901 Castle Hayne Road P.O. Box780 Wilmington, NC 28402 USA T (910) 547-0391 Chandi.davidson@gevernova.us
Subject:
GNF-A Written Follow-up Report - Sprinkler System Impairment
References:
- 1) NRC License SNM-1097, Docket 70-1113
- 2) GNF-A Event Notification EN 57884, 08/22/2025
Dear Sir or Madam:
In accordance with 10 CFR 70.74(b), Global Nuclear Fuel-Americas, LLC (GNF-A) hereby submits a written follow-up report for Event Notification 57884 that was provided to NRC on August 22nd, 2025 (Reference 2).
Event 57884 As discussed in the initial event report, GNF-A reported an unplanned fire suppression system impairment to the New Hanover County (NHC) Deputy Fire Marshal. Consistent with 10 CFR 70, Appendix A(c), a concurrent report was provided to NRC and is included as Attachment 1 to this letter.
Additional information is provided as follows:
Event Details and Safety Significance At approximately 1035 (EDT) on August 22nd, 2025, the New Hanover County Deputy Fire Marshal was notified per North Carolina Fire Code requirements that a fire suppression system riser, which provides sprinkler protection to a portion of the fuel manufacturing operation (FMO),
was impaired due to missing ceiling tiles. A fire watch for the affected area was initiated.
Immediate Corrective Actions Taken A fire watch was initiated and repairs begun.
USNRC M250338 October 20, 2025 Page2 Probable Cause of Event An investigation determined the probable cause to be a water leak from an overhead HVAC unit which damaged some ceiling tiles and caused them to fall to the floor.
Short Term Corrective Actions A fire watch was immediately initiated for the affected area and identified missing ceiling tiles were replaced. The leak in the overhead was addressed by shutting off the chilled water valve to the HVAC unit and removing the unit from active service. Completed 10/20/2025.
Longer Term Corrective Action None.
If you have any questions regarding this matter, please contact me at (910) 547-0391.
Sincerely, Chandi Davidson Facility Licensing Attachments: 1) EN 57884 Description cc: NRC Region II Administrator, Atlanta, GA C. Ubben, NRC RII, Atlanta, GA J. Rowley, NRC NMSS, Washington, DC CBD 25-004
USNRC M250338 October 20, 2025 Page3 EN 57884 Description At approximately 1035 (EDT) on August 22nd, 2025, the New Hanover County Deputy Fire Marshal was notified per NC Fire Code requirements that a fire suppression system Riser, which provides sprinkler protection to a portion of the Fuel Manufacturing Operation (FMO), was impaired due to missing ceiling tiles. A Fire Watch for the affected area has been initiated.
Because the New Hanover County Deputy Fire Marshal was notified, a concurrent notification to the NRC Operations Center is being made per 10 CFR 70, Appendix A(c).
Phillip Ollis, Facility Licensing Manager 1421 08/22/2025