ML25233A048

From kanterella
Jump to navigation Jump to search
TLR-RES/DE 2025-08 Addressing Expanded Materials Degradation Assessment (Emda) Knowledge Gaps for Continued Use of Electrical Cables in Long-term Operation
ML25233A048
Person / Time
Issue date: 09/12/2025
From: Elen M, Fifield L, Glass S, Ni Y, Mohammad Sadollah
NRC/RES/DE, Pacific Northwest National Laboratory
To:
Mo Sadollah
References
PNNL-37317 TLR-RES/DE 2025-08
Download: ML25233A048 (70)


Text

Choose an item.

Technical Letter Report TLR-RES/DE 2025-08 PNNL-37317 Addressing Expanded Materials Degradation Assessment (EMDA) Knowledge Gaps for Continued Use of Electrical Cables in Long-term Operation July 2025 Prepared by:

Leonard S. Fifield Pacific Northwest National Laboratory Yelin Ni Pacific Northwest National Laboratory Muthu Elen Pacific Northwest National Laboratory Samuel W. Glass Pacific Northwest National Laboratory Project Manager:

Mohammad Sadollah Nuclear Regulatory Commission Instrumentation, Controls, and Engineering Branch Division of Engineering Office of Nuclear Regulatory Research U.S. Nuclear Regulatory Commission Washington, DC 20555-001

Choose an item.

DISCLAIMER This report was prepared as an account of work sponsored by an agency of the U.S. Government.

Neither the U.S. Government nor any agency thereof, nor any employee, makes any warranty, expressed or implied, or assumes any legal liability or responsibility for any third party's use, or the results of such use, of any information, apparatus, product, or process disclosed in this publication, or represents that its use by such third party complies with applicable law.

This report does not contain or imply legally binding requirements. Nor does this report establish or modify any regulatory guidance or positions of the U.S. Nuclear Regulatory Commission and is not binding on the Commission.

Choose an item.

PNNL-37317 Addressing Expanded Materials Degradation Assessment (EMDA)

Knowledge Gaps for Continued Use of Electrical Cables in Long-term Operation July 2025 Leonard S. Fifield Yelin Ni Muthu Elen Samuel W. Glass Prepared for the U.S. Nuclear Regulatory Commission Office of Nuclear Regulatory Research Under Contract DE-AC05-76RL01830 Task Order Number: 31310024S0025

Choose an item.

DISCLAIMER This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor Battelle Memorial Institute, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof, or Battelle Memorial Institute. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.

PACIFIC NORTHWEST NATIONAL LABORATORY operated by BATTELLE for the UNITED STATES DEPARTMENT OF ENERGY under Contract DE-AC05-76RL01830

Addressing Expanded Materials Degradation Assessment (EMDA) Knowledge Gaps for Continued Use of Electrical Cables in Long-term Operation July 2025 Leonard S. Fifield Yelin Ni Muthu Elen Samuel W. Glass Prepared for the U.S. Nuclear Regulatory Commission Office of Nuclear Regulatory Research Under Contract DE-AC05-76RL01830 Task Order Number: 31310024S0025 Pacific Northwest National Laboratory Richland, Washington 99354

Summary ii Summary The Expanded Materials Degradation Assessment Volume 5: Aging of Cables and Cable Systems (EMDA) (NUREG/CR-7153, Vol.5) [1], published October 2014, was a collaboration between the U.S. Nuclear Regulatory Commission (NRC) and the U.S. Department of Energy (DOE) that utilized a panel of industry experts to consider the continued use of electrical cables in nuclear power plants (NPPs) beyond initial plant license renewal. Electrical cables that are important to safety in NPPs (10 CFR § 50.49) were commonly environmentally qualified for at least 40 years, corresponding to the initial reactor license period. Elements of conservatism in that process have been relied upon to justify continued use of cables up to 60 years in initial license renewals and up to 80 years in subsequent license renewals. The EMDA documents a focused consideration of the state of knowledge and risks for cable materials in extended operation. It identified several gaps in understanding related to the historical qualification process and to continued use of cables beyond their initial qualified life. Identified gaps include variable activation energy, diffusion limited oxidation (heterogeneous degradation), dose rate effects, effects of sequence of exposure or synergism in thermal and radiation aging, inverse temperature effects, moisture effects and submerged cables, actual versus conservatively estimated NPP environments, and monitoring of cable condition. Suggestions were made in the EMDA of potential courses of action to address these topics.

This document considers progress and approaches that have been reported in the decade following publication of the EMDA toward closing the identified knowledge gaps and increasing confidence in decisions regarding continued use of qualified cables beyond their original qualified life. The NRC, DOE national laboratories, the Electric Power Research Institute (EPRI),

and other entities both inside and outside of the U.S. have published research and developments related to the knowledge gaps. The inherent characteristics of the historic approach to time-based environmental qualification, which often relied heavily on margin and conservatism to overcome the uncertainties in qualified life, have been acknowledged.

Alternative methods have been proposed to incorporate information gained from subsequent research. Actual in-plant service conditions in operating boiling water and pressurized water reactors have been more accurately determined. Susceptibility of certain cables to moisture damage and practical methods to ensure reliable performance of potentially wetted cables have been proposed, such as dewatering of manholes and periodic tangent delta testing. Consensus-based standard development groups, including IEEE, have updated their guidance on cable qualification with regards to information presented in the EMDA since the initial 1970s versions of those documents [2], [3]. The NRC has updated regulatory guidance to support revised standards for qualification of cables considering the uncertainties documented in the EMDA, including NRC Regulatory Guide 1.211 Qualification of Safety-Related Cables and Field Splices for Nuclear Power Plants, issued April 2009 [4] and NRC Regulatory Guide 1.89, Revision 2 Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants, issued April 2023 [5]. The NRC Generic Aging Lessons Learned for Subsequent License Renewal (GALL-SLR) Report, Draft Report for Comment (NUREG-2191)

[6], [7] document and subsequent license renewal guidance have been updated to acknowledge potential aging mechanisms identified in the EMDA and to require cable aging management practices to mitigate potential risks not fully appreciated in historic license guidance.

Acronyms and Abbreviations iii Acronyms and Abbreviations AC alternating current AEIC Association of Edison Illuminating Companies ANSI American National Standards Institute BWR boiling water reactor CBQ condition-based qualification CFR Code of Federal Regulations CSPE chlorosulphonated polyethylene DBE design basis event DC direct current DED dose to equivalent damage DLO diffusion limited oxidation DOE U.S. Department of Energy DRE dose rate effect Ea activation energy EAB elongation at break EMDA Expanded Materials Degradation Assessment EPDM ethylene-propylene-diene type-M rubber EPR ethylene-propylene rubber EPRI Electric Power Research Institute EQ environmental qualification/environmentally qualified EVA ethylene vinyl acetate FTIR Fourier transform infrared spectroscopy GALL Generic Aging Lessons Learned GL Generic Letter Gy Gray (unit of absorbed radiation dose)

HELB high energy line break Hz Hertz (unit of frequency), per second IEC International Electrotechnical Commission IEEE Institute of Electrical and Electronics Engineers IN Information Notice IPCEA Insulated Power Cable Engineers Association (now ICEA)

ITE inverse temperature effect kV kiloVolt (1000 V) kGy/h kiloGray per hour LOCA loss of coolant accident mil 0.001 inch

Acronyms and Abbreviations iv Mrad Megarad (10^6 rad)

MV medium voltage (>2 kV and <45 kV)

NMR nuclear magnetic resonance NPP nuclear power plant NRC U.S. Nuclear Regulatory Commission OE operating experience OIT oxygen induction time OITp oxygen induction temperature PE polyethylene PIRT phenomena identification and ranking technique PNNL Pacific Northwest National Laboratory PWR pressurized water reactor R&T concurrent gamma radiation and elevated temperature exposure RT gamma radiation exposure followed by elevated temperature exposure RG Regulatory Guide SLR subsequent license renewal Std standard TR elevated temperature exposure followed by gamma radiation exposure tan tangent delta, tan delta, or dissipation factor TGA thermogravimetric analysis V

Volts VVER water-water energy reactor, a Russian pressurized water reactor XLPE crosslinked polyethylene XLPO crosslinked polyolefin

Contents v

Contents Summary....................................................................................................................................... ii Acronyms and Abbreviations........................................................................................................ iii Contents........................................................................................................................................ v 1.0 Introduction....................................................................................................................... 1 2.0 Knowledge Gaps Identified in the Expanded Materials Degradation Assessment............ 3 2.1 Summary of EMDA Knowledge Gaps................................................................... 3 2.2 Qualification Related Knowledge Gaps................................................................. 3 2.2.1 Actual Nuclear Power Plant Environments............................................. 4 2.2.2 Non-Arrhenius Behavior and Non-Constant Activation Energy.............. 4 2.2.3 Diffusion Limited Oxidation................................................................... 10 2.2.4 Dose Rate Effects................................................................................. 13 2.2.5 Sequential vs. Concurrent and Synergistic Aging Effects..................... 16 2.2.6 Inverse Temperature Effects................................................................ 18 2.2.7 Pre-Aging of Semi-Crystalline Materials............................................... 20 2.2.8 Impact of the Knowledge Gaps on Operation Status............................ 20 2.3 Moisture Effects Related Knowledge Gap........................................................... 23 2.3.1 Understanding of Moisture Effects at the Time of the Expanded Materials Degradation Assessment...................................................... 23 2.3.2 Research on Moisture Effects Reported Since the Expanded Materials Degradation Assessment...................................................... 24 3.0 Updates on Cable Qualification Standards and Regulatory Guides............................... 26 3.1 Knowledge Gaps Addressed in IEEE Standards and NRC Publications............ 27 3.2 Example Environmental Qualification Reports for Cables................................... 29 3.2.1 Recognition of Synergistic Effects and Dose Rate Effects................... 29 3.2.2 Recognition of Non-Constant Ea........................................................... 30 4.0 Discussion of Status and Potential Paths Forward......................................................... 32 4.1 What has Changed Since the Expanded Materials Degradation Assessment was Published?............................................................................... 32 4.2 How to Manage Cables Past their Qualified Life?............................................... 33 4.2.1 Use Conservatism................................................................................ 33 4.2.2 Type Test on Aged Samples from the Nuclear Power Plant................ 33 4.2.3 Perform Type Testing for Longer Qualified Life.................................... 33 4.2.4 Replace Components........................................................................... 33 4.2.5 Pursue Condition-based Qualification.................................................. 33 5.0 Conclusion...................................................................................................................... 35 6.0 References...................................................................................................................... 36 7.0 Appendix......................................................................................................................... 48

Contents vi Figures Figure 1.

Schematic demonstration of the mismatch between estimated time to endpoint (without Ea change) and the actual time to endpoint when the Ea (slope) changes at lower temperatures. Modified from Fig. 2 of [28].

Respectively, the blue, green and pink symbols represent the actual time to endpoint (with a lowering in Ea) being 80%, 50% and 90% of the estimated time to endpoint (assuming a constant Ea)........................................... 7 Figure 2.

(a) A change in Ea at 124°C observed for a crosslinked polyolefin (XLPO) material. (b) Constant Ea for a different XLPO material. Figures are modified from (a) Figure IV-40 and (b) Figure IV-32 of [31].................................. 8 Figure 3.

Ea values obtained from different temperature ranges (x-axis) based on different testing methods (legend) for (a) XLPE/XLPO and (b) EPR/EPDM materials. (Data sources may be found in the Appendix)...................................... 9 Figure 4.

Schematic demonstration of the effects of DLO on qualified life, including (a) the underestimation of time to endpoint when extrapolating the DLO-affected high-temperature data using the Ea calculated from the high temperatures (red crosses) (b) a longer pre-aging time needed to accommodate a lowering in Ea due to DLO, if the pre-aging time was calculated based on the Ea derived from low-temperature data (blue pluses)................................................................................................................. 12 Figure 5.

Schematic illustration of different types of dose rate effects (DRE) under inert (curve I) and aerobic (curves II and III) atmospheres. On the dose to equivalent damage (DED) vs. dose rate plot, the sloped portions (circled) indicate the presence of DRE. The figure was reproduced from Gillen and Clough, 1993 [48]................................................................................................ 14 Figure 6.

Demonstration of using DED curve to find the equivalent dose at two different dose rates for samples showing dose rate effects................................ 15 Figure 7.

Steps for determining if inverse temperature effects (ITE) are of concern.......... 19 Figure 8.

Cable degradation indicators towards functional failure. The length of the line segments between different stages of degradation was estimated and may not be proportional to the actual lifetime. EAB = Elongation at Break.

IR = Insulation Resistance................................................................................... 20 Figure 9.

Normalized elongation at break (EAB), insulation resistance (IR) and capacitance (C) with respect to the baseline values (unaged samples) of Anaconda and BIW insulations subjected to 81°C, 0% RH and 69 Gy/h aging up to 480 days. The data were taken from tables in Appendix A of Watson, et al. [24]............................................................................................... 21 Figure 10.

Normalized elongation at break (EAB) and insulation resistance (IR) of an EPDM insulation/EPDM jacket cable and an XLPE insulation/CSPE jacket cable, subjected to 120°C and 142°C aging. The data were taken from tables in Spaang et al. [87].................................................................................. 22 Figure 11.

Insulation resistance (IR) of XLPO-type cables before and after design basis event (DBE; e.g., LOCA) simulation. The plot was taken from reference [82]...................................................................................................... 22

Contents vii Figure 12.

Type testing to qualify for normal operation described in IEEE Std 383-1974. AC = alternating current, AEIC = Association of Edison Illuminating Companies, ANSI = American National Standards Institute, DC = direct current, IPCEA = Insulated Power Cable Engineers Association (now ICEA), mil = 0.001 inch,....................................................................................... 27 Figure 13.

Type testing for operation during DBE described in IEEE Std 383-1974............ 27 Figure 14.

EQ process of crosslinked polyethylene (XLPE) insulation in a report from 1986.................................................................................................................... 30 Figure 15.

A change in slope on the Arrhenius plot recognized in two EQ reports, one with no date (a), and one dated in 1991 (b).................................................. 31 Tables Table 1.

Ratio of the actual time to endpoint (with a lowering in Ea) and estimated time to endpoint (without considering the lowering in Ea) at different hypothetical situations when estimating the time to endpoint at 48°C................... 8 Table 2.

IEEE Std 323 and IEEE Std 383 releases and endorsements by the NRC........ 26 Table 3.

Activation energy (Ea), pre-aging time and temperature and the corresponding time to endpoint at the service condition from seven EQ documents........................................................................................................... 31 Table 4.

Activation energy (Ea) values reported in literature............................................. 48

Introduction 1

1.0 Introduction The fifth volume of the NUREG/CR 7153, the Expanded Materials Degradation Assessment, Aging of Cables and Cable Systems (EMDA) report [1] describes an expansion of the NUREG/CR-6923, Expert Panel Report on Proactive Materials Degradation Assessment, [8]

consideration of nuclear power plant (NPP) materials degradation to include electrical cable materials and cable use in service environments beyond current license periods. Electrical cables important to safety in NPPs [9] were environmentally qualified for at least 40 years corresponding to the initial reactor license period. Elements of conservatism in that process have been used to justify continued use of cables up to 60 years in license renewal and up to 80 years in subsequent license renewal. Consideration of continued use of cables beyond current license periods prompted an intentional and documented consideration of the state of knowledge and risks of continued cable material use. The EMDA used a phenomena identification and ranking technique (PIRT) approach to rank potential degradation scenarios according to the judgement of experts on material susceptibility and the state of knowledge at the time. The PIRT approach of the EMDA identified the current knowledge base of electrical cable and cable system materials, gaps in knowledge for cables in need of further research, potential new forms of degradation, and prioritized research needs.

In the EMDA PIRT process, expert panelists were in general agreement on levels of knowledge at the time and overall aging-related susceptibility of cable materials. Very few materials and aging condition combinations were identified for which a susceptibility ranking of high (on a scale of low-1, medium-2, high-3) was given. The susceptibility ranking of a material increased with increasing severity of environmental conditions including higher aging temperatures and higher gamma radiation dose rates. Knowledge of material aging ranked as medium-2 or high-3 for all materials and environments considered, reflecting the significant existing extent of generic polymer aging research findings apart from specific plant locations and conditions.

The EMDA report documents several gaps in knowledge related to the historical qualification process and the continued use of cables, originally qualified for 40 years of operation, in extended operation. The main area of uncertainty identified by the EMDA panelists relates to the pre-aging (accelerated aging) carried out during the environmental qualification process and the equivalence of that accelerated aging to the long-term service aging it was intended to simulate. Identified gaps include variable activation energy, diffusion limited oxidation (heterogeneous degradation), dose rate effects, effects of sequence of exposure or synergism in thermal and radiation aging, inverse temperature effects, moisture effects and submerged cables, actual NPP environments, and methods for condition monitoring. Concerns over the uncertainty raised by these identified phenomena relate to the ability of environmentally qualified (EQ) cables to survive heat, radiation, humidity, chemical spray, and other environmental factors associated with design basis events (DBE) during their qualified time of service. In addition to uncertainty regarding the ability of the historic pre-aging methods to simulate extended time in service, uncertainty was also identified in the actual temperatures and gamma radiation doses to which fielded cables are exposed to during their qualified life. That is, according to the EMDA, not only does uncertainty exist related to the process of replicating long term service conditions through accelerated aging in the laboratory, but there is also uncertainty regarding the current understanding of the long-term environmental service conditions to be replicated. Suggestions were made in the EMDA strategies for actions to address these topics.

Introduction 2

The Nuclear Regulatory Commission (NRC), U.S. Department of Energy (DOE) national laboratories, the Electric Power Research Institute (EPRI), and other entities both inside and outside of the U.S. have published research and developments related to the knowledge gaps.

Uncertainties in the time-based approach to EQ have been acknowledged, and improved methods to account for them have been proposed. Actual in-plant service conditions in operating boiling water and pressurized water reactors have been more accurately determined.

Susceptibility of cables to moisture damage and practical methods to ensure reliable performance of potentially wetted cables have been established and implemented.

Consensus-based standard development groups, including IEEE, have updated their guidance on the cable qualification process considering information presented in the EMDA. The NRC has updated regulatory guidance to support revised standards for qualification of cables considering the uncertainties documented in the EMDA, per NRC Regulatory Guide 1.89, Revision 2 Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants, issued April 2023 [5]. The NRCs Generic Aging Lessons Learned for Subsequent License Renewal (GALL-SLR) Report, Draft Report for Comment (NUREG-2191)

[6], [7], and subsequent license renewal guidance have been updated to acknowledge potential aging mechanisms identified in the EMDA and to require cable aging management practices to mitigate potential risks not fully appreciated in previous historic license guidance.

This report considers progress and approaches that have been reported in the decade following publication of the EMDA to close the identified knowledge gaps and to increase confidence in decisions regarding continued use of qualified cables beyond their original qualified life. Each of the knowledge gaps will be discussed individually in Section 2.0, including the location of their mention in the EMDA document, published progress on the topic since the EMDA was released, and conclusions regarding the updated status of the identified topic of concern. A summary of the EMDA knowledge gaps is provided in Section 2.1, followed by topics related to cable qualification in Section 2.2, and consideration of moisture effects in Section 2.3. Section 3.0 reviews the evolution and status of technical standards and regulatory guidance relevant to cable environmental qualification. Section 4.0 contains a discussion of changes to cable qualification and aging management since the EMDA was published and updated guidance on reassessment of qualified cables for use beyond their original qualified life. Finally, Section 5.0 provides concluding remarks considering progress on EDMA knowledge gaps since the publication of the EMDA in 2014.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 3

2.0 Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 2.1 Summary of EMDA Knowledge Gaps The summary input of experts documented in the EMDA described several specific knowledge gaps or topics of uncertainty related to continued use of installed cables in reactors in extended operation. These topics included concerns with the methodology used to environmentally qualify safety-related cables, limited knowledge of actual in-plant service conditions for cables, and the unanticipated long-term degradation mechanisms of moisture exposure (such as insulation failures due to water-treeing) even for cables designed for submerged conditions. Each of the knowledge gaps will be discussed individually below, including the location of its mention in the EMDA document, published progress on the topic since the EMDA was released, and conclusions regarding the updated status of the knowledge gap.

2.2 Qualification Related Knowledge Gaps Several of the potential concerns raised in the EMDA relate to the methodology historically used to meet the EQ requirements for safety-related cables. The U.S. Atomic Energy Commission (the predecessor to the U.S. Nuclear Regulatory Commission [NRC]) first published the Qualification of Class 1E Equipment for Nuclear Power Plants Regulatory Guide 1.89 (Regulatory Guide [RG] 1.89) in 1974, which described a method acceptable to the Regulatory staff for complying with the Commission's regulations with regard to design verification of Class 1E equipment for service in light-water-cooled nuclear power plants[10]. That first RG 1.89 edition found the basic procedures for qualifying Class 1E equipment described in the IEEE Standard (Std) 323-1974, "IEEE Standard for Qualifying Class IE Equipment for Nuclear Power Generating Stations,[2] to be generally acceptable and to provide an adequate basis for complying with design verification requirements of such equipment outlined in the NRC Regulations Title 10 portion of the Code of Federal Regulations (CFR) (Criterion III of Appendix B to 10 CFR Part 50 [11]), Requirements binding on all persons and organizations who receive a license from NRC to use nuclear materials or operate nuclear facilities. Class 1E or safety-related electrical equipment, including cables, must conform to established industry performance standards to promote confidence in reliably safe function in the nuclear reactor environment. Generally, these standards require cable manufacturers to ensure products maintain performance requirements throughout their design life, even after DBEs [12]. This assurance has usually been met by accelerated aging of the components (e.g., applying the Arrhenius method or the equal dose-equal damage approach) using either thermal, radiation, or a combination of stressors, to simulate the accumulated stress of their qualified life (e.g., 40 years, 60 years, etc.) prior to subjecting the pre-aged components to a design basis (e.g., loss of coolant accident [LOCA], high energy line break [HELB]) exposure simulation. Components that successfully perform following this process are deemed environmentally qualified. Most installed EQ cables have been qualified for a lifetime of at least 40 years, corresponding to the initial license period of NPPs. The points of concern with the qualification process presented in the EMDA mostly involve the methods used in the pre-aging step, in which the equivalence of 40 years of service aging was meant to be imparted to a component prior to testing its capacity to pass a DBE simulation.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 4

2.2.1 Actual Nuclear Power Plant Environments To understand the effects of aging equivalent to 40 years on a component in the service environment (to provide reasonable assurance whether a 40-year-old component will pass the DBE simulation), the conditions of the service environment must be used as an input. At the beginning of the nuclear electric power industry, operating experience and knowledge of the effects of service environment conditions on cable system materials was limited. Conservative assumptions were made about the average service temperature, such as 50ºC or even 90ºC, and the average accumulated gamma dose, such as 50 megarad (Mrad [106 rad]) or 500 kGray (kGy), that a safety-related cable may be subject to over 40 years of operation. Knowing that they would be conservative, such values were used to robustly qualify cables for confidence in the ability of the cables to perform their safety function throughout the 40-year life of the reactor (corresponding to its initial license period). As the need and desire arose for continued use of existing reactors beyond 40 years, it became important to understand exactly how conservative those original service condition estimates were and consequently, to seek to better understand how much longer than the initial operating license a qualified component might be expected to reliably perform [13]. Chapter 5.9.5 of the EMDA mentions the knowledge gap relating to actual in-service conditions of nuclear power plant electrical components.

EPRI produced a report that addresses the knowledge gap of actual in-service conditions for NPP cables [14]. It describes and discusses measured thermal and radiation data for a representative boiling water reactor (BWR), a representative pressurized water reactor (PWR),

and a Russian PWR [the water-water energy reactor (VVER)]. This data can be extrapolated to estimate approximate actual conditions over 40, 60, or 80 years of reactor operation. Key findings from the report are that:

In the overwhelming majority of cases radiation levels were often two (2) or more orders of magnitude less than design values used for environmental qualification, and Thermal environments are typically less than design values (for Westinghouse PWR monitored, one location was 12ºF (7ºC) higher than design while the remaining 54 monitors were 5ºF to 50ºF (2.8ºC to 28ºC) less than design values).

2.2.2 Non-Arrhenius Behavior and Non-Constant Activation Energy 2.2.2.1 Understanding of Non-Arrhenius Behavior and Non-Constant Activation Energy at the Time of the Expanded Materials Degradation Assessment Chapter 5.1 of the EMDA document identifies activation energy values used for thermal aging as a potential concern in qualification methodology and hence a gap in knowledge for extension of qualification results to expected performance in long-term operation. The process for accelerated aging of cables to the equivalence of the license period (e.g., 40 years) prior to exposing the cable to a DBE simulation involved the assumption that exposure to a higher temperature for a shorter time produces aging equivalent to a longer period at a lower temperature. Specifically, that the rate of the aging reaction depends on the temperature according to the Arrhenius relationship. A material property that tracks aging is selected, such as tensile elongation at break (EAB) of the cable insulation polymer material, an endpoint is selected for the reaction, such as EAB = 50% of the original value, and the exposure time to endpoint at each temperature is determined for a series of temperatures. The activation energy (Ea) of the degradation reaction is derived from the slope of the Arrhenius plot (such as time to EAB endpoint versus the reciprocal absolute temperature). If the natural log of the rate of

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 5

change is linear with the reciprocal absolute temperature, and the slope of the line (the Ea) is constant over the range of temperatures considered, then the relationship is described as exhibiting Arrhenius behavior. Chapter 5 in the EMDA listed a few publications that reported observation of non-Arrhenius behavior in polymers, or a change in Ea of the polymers in different temperature ranges. Chapter 5.1 of the EMDA elaborated on the reduction in Ea as the temperature was lowered from the accelerated aging condition to the service condition. The potential concern is that if an Ea value calculated using greatly elevated temperatures is significantly higher than the Ea that would be calculated using temperatures near the actual service temperature, then the robustness (i.e., the ability to perform the intended safety function) of the cable at service temperatures may be overestimated.

In Chapter 5.1 of the EMDA, the authors concluded that some of the limitations of use of the Arrhenius equation as a basis for accelerated thermal aging needed to be [better] appreciated.

For example, the Arrhenius model is only applicable if the same balance of degradation reactions occurs at both the elevated accelerated aging temperatures and at service temperatures.

Chapter 5.9.1 in the EMDA on Activation Energies suggests that derivation of Arrhenius activation energies with reduced uncertainty at low temperatures (close to service temperatures) using sensitive measurement techniques (such as oxygen consumption rather than tensile EAB), and conditions that avoid other aging artifacts (such as use of thin samples to avoid diffusion limited oxidation [DLO]) would provide needed data for improved analytical simulation of thermal aging (see Section 2.2.3 below for additional discussion).

A key finding of the expert panel assembled in the EMDA process is reproduced here:

If, as expected, environmental information demonstrates that thermal aging is the dominant process for nearly all cables in U.S. NPPs, then it is important that the activation energy for the specific cable materials used, under [a] specific environment, be estimated with increased confidence level. This is because the actual value of activation energy plays a major role in behavior prediction [modelling] over time at a given environment. Experiments conducted to estimate activation-energy should be conducted at temperatures close to service temperatures using techniques such as oxygen consumption that have the ability to cover wide temperature ranges. This ability allows one to use the oxygen consumption results to confirm a correlation (same activation energy) with the mechanical properties (e.g., elongation) at the higher temperatures and to use low temperature oxygen consumption results to probe any changes in activation energy in the low temperature extrapolation region (EMDA Chapter 10.2) [1].

Thus, the EMDA authors bring attention to the fact that Ea values can vary with temperature and Ea values used in predicting cable material behavior over time in service should be determined for the temperature range of the service environment.

2.2.2.2 Research on Activation Energy Reported Since Publication of the Expanded Materials Degradation Assessment The Arrhenius methodology has been used in many fields to describe the temperature dependance of polymer degradation, but only as an empirical model, with limited predictive power. Using both EAB and oxygen consumption measurements, a reduction in Ea at lower temperatures was experimentally observed for many cable materials, including those used as cable insulation and jacket material [15], [16], [17]. Measuring Ea at a temperature as close to

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 6

the service temperature as possible is key to improving the accuracy of lifetime estimation. Near the service temperatures, where EAB does not change within months of aging in the laboratory environment, oxygen consumption was reported as one of the few tests sensitive enough to provide a reliable Ea value. Ea values at low temperatures (below 100°C) were reported when other degradative stressors (e.g., gamma or ultraviolet radiation) were present using markers of polymer aging including loss in elasticity, as determined by tensile EAB [18], [19], and rise in chemical oxidation, as tracked by absorbance in the carbonyl region of the infrared spectra observed using Fourier transform infrared spectroscopy (FTIR) [20], [21]. In addition to supporting the determination of Ea and DLO modeling, the accumulated oxygen consumption (or the oxidation level) was also used to represent the progress of degradation, essentially replacing a time-temperature superposition framework with an oxygen consumption-temperature superposition framework [22], [23].

The choice of endpoint and the aging indicator metric were reported to affect the value of Ea

[19], [24], [25]. There was also a desire to use thermogravimetric analysis (TGA) data at different ramp rates to calculate Ea [26], [27], [28]. As has been pointed out in a review of the subject [29], the Ea values calculated from TGA data were focused on the degradation chemistry pathways that for most polymers are too far removed from the mechanisms that are relevant for the usual application conditions. Similarly, attention should be paid to the relevance of the process used for Ea determination and the degradation process happening in the service condition of cables when using other techniques to calculate Ea.

A numerical method was proposed using two processes, each with its own Ea, to describe degradation of ethylene-propylene-diene type-M rubber (EPDM) characterized by EAB, oxygen consumption, compressive stress relaxation and decay in sealing force [30]. The idea was similar to using two competing processes to explain non-Arrhenius behavior [31] but used different approaches to deconvolute the two processes and arrive at different Ea values. In the model of Zaghdoudi, Ea was dependent on degradation rate, while in the model of Celina and Gillen, Ea was temperature controlled.

2.2.2.3 Impact of Non-Constant Activation Energy on Qualified Life The impact of non-constant Ea in cable qualification is that it changes the estimated time to endpoint in cable pre-aging (accelerated aging) to the qualification period prior to DBE simulation. If Ea was lower at the service temperature compared to the Ea obtained from accelerated aging studies at significantly higher temperatures, the Arrhenius model would overestimate the time at service temperature represented by the pre-aging. For example, heating cable over a few weeks at elevated temperature to induce degradation representing 40 years of aging at service temperature might represent less than the equivalent of 40 years of aging if the Ea of degradation at service temperature is lower than Ea at the accelerated aging temperature. The amount of overestimation scales with the amount of change in Ea ( ),

the measured time to endpoint at the accelerated conditions (1), and depends on the temperature at which the Ea value varies (3). Specifically, if the Ea was constant for the temperature range bracketing the accelerated temperature (1) and the service temperature (2), then the estimated time to endpoint at the service condition (2) would be 2 = 1 x exp 1

1 1

2

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 7

where 1 is the measured time to endpoint at the accelerated temperature (1). If the activation energy value decreased to at an intermediate temperature (3), then the new estimated time to endpoint (2

) would be 2

= 2 x exp

1 2

1 3

= 1 x exp

1 1

1 2x exp

1 2

1

3.

A comparison between the estimated time to endpoint (2) and the actual time to endpoint (2

)

considering the lowering of Ea was demonstrated in Figure 1, where the actual time to endpoint was 80%, 50% and 90% of the estimated time in the three hypothetical scenarios. Figure 1 is a modified version of Fig. 2 of Celina in [29] that illustrates non-linearity in response to accelerated aging.

Figure 1. Schematic demonstration of the mismatch between estimated time to endpoint (without Ea change) and the actual time to endpoint when the Ea (slope) changes at lower temperatures. Modified from Fig. 2 of [29]. Respectively, the blue, green and pink symbols represent the actual time to endpoint (with a lowering in Ea) being 80%,

50% and 90% of the estimated time to endpoint (assuming a constant Ea).

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 8

Figure 2. (a) A change in Ea at 124°C observed for a crosslinked polyolefin (XLPO) material. (b)

Constant Ea for a different XLPO material. Figures are modified from (a) Figure IV-40 and (b) Figure IV-32 of [32].

A lower Ea value at lower temperature has been reported for a variety of polymers. For example, Figure 2(a) showed the change in Ea for a crosslinked polyolefin (XLPO) material (labeled as green insulation XLPO-05 in the original report [32]) from 135 kJ/mol (124°C to 151°C) to 98 kJ/mol (48°C to 124°C) and the transition happened at 124°C. In this example, the ratio of the actual time to endpoint and the estimated time to endpoint at 48°C would be 2

2

= exp

1 2

1 3

= exp (13598)x1000 8.314

1 48+273.15 1

124+273.15= exp(2.65) = 0.07, which means the time to endpoint was only 7% of the time to endpoint for the higher Ea value. If the Ea or Ea were of a different value, or if the changeover happened at a different temperature, the ratio (2 2

) would be different as listed in Table 1. It should be noted that not all XLPO materials exhibited a decrease in Ea with temperature. For a different XLPO (labeled as XLPO-02B in the original document [32]), as shown in Figure 2(b), the Ea was constant over the temperature range of 48°C to 138°C, which would not lead to overestimation of time to endpoint if accelerated aging was performed at or below 138°C and if the service temperature was at 48°C or above.

Table 1. Ratio of the actual time to endpoint (with a lowering in Ea) and estimated time to endpoint (without considering the lowering in Ea) at different hypothetical situations when estimating the time to endpoint at 48°C.

High-temperature (kJ/mol)

Low-temperature

(kJ/mol)

Change-over temperature, (°C)

Ratio of times to endpoint,

(%)

135 98 124 7

120 98 124 21 135 98 64 52 120 98 64 68

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 9

Literature Ea values for crosslinked polyethylene (XLPE)/XLPO and EPR/EPDM types of materials are compiled in Figure 3, where the horizontal lines represent the Ea value calculated based on the isotherms obtained in the corresponding temperature range. Ea values for other polymers reported in literature are listed in the Appendix. As shown in Figure 3, Ea values vary with the test method and the temperature range when the base polymer is in the same material category. As the values were obtained from different references, the test specimens would have different formulations, which may also contribute to the variability of Ea values. A possible explanation for why the Ea values vary between different testing methods is that the different methods probe different stages of aging where the predominant aging mechanism could be associated with different Ea values. For example, OIT is correlated with loss of antioxidants, which occurs at an early stage of degradation. Color change (including yellowing due to the conjugated species produced during aging), and the absorption peaks A at 1720 cm-1 and 1714 cm-1 (in the carbonyl region), were related to the formation of new chemical structures (e.g., carbonyls). Chemical changes typically happen at much earlier stages than mechanical embrittlement as measured by a decrease in EAB.

Figure 3. Ea values obtained from different temperature ranges (x-axis) based on different testing methods (legend) for (a) XLPE/XLPO-based and (b) EPR/EPDM-based materials. (Data sources may be found in the Appendix).

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 10 2.2.3 Diffusion Limited Oxidation 2.2.3.1 Understanding of Diffusion Limited Oxidation at the Time of the Expanded Materials Degradation Assessment Diffusion limited oxidation (DLO) was discussed in detail in Chapter 5.2 of the EMDA. Under extreme accelerated aging conditions such as at highly elevated temperatures, oxygen permeating in the polymeric cable insulation material can be consumed in the oxidation reaction with the polymer faster than the oxygen can be replenished by diffusion into the polymer matrix from the surrounding atmosphere. This phenomenon can artificially protect the center of polymer sample from oxidative aging through rapid formation of an aged layer of the surface of the sample with significantly reduced oxygen permeability, such that oxygen is prevented from reaching and reacting with polymer at the center of the sample. DLO may be detected by through-thickness profiling techniques, such as modulus profiling, as demonstrated in Figure 5.5 of the EMDA, where the modulus of a 1.3 mm thick chlorosulphonated polyethylene (CSPE) sample was lower in the center of the sample thickness than the modulus was on the outside air-exposed surfaces. According to Chapter 5.2 of the EMDA, presence of DLO may overestimate cable insulation lifetimes. However, the discussion in Chapter 5.2.1 of EMDA for the CSPE sample showing DLO pointed out that the tensile elongation of the subject sample was not affected by DLO, as the local hardening on sample surface could quickly result in bulk failure from crack initiation, indicating that lifetime to the endpoint of a EAB reduction might not be affected by the presence of DLO.

Chapter 5.2.1 of EMDA gave the equation for the critical sample thickness below which DLO is insignificant as a function of oxygen partial pressure, oxygen permeation rate and oxygen consumption rate. Chapter 5.9.2 suggested measuring these parameters and developing 2-D finite element models for DLO on the cable cross-sections.

2.2.3.2 Research on DLO Reported Since Publication of the Expanded Materials Degradation Assessment Simulation of DLO through finite element modeling has been pursued [33], [34], [35], enabling the visualization of the effects of modeled parameters as a function of oxygen concentration and of sample thickness. The limiting thickness of a sample at which the oxidation rate at the center of the sample closely approximates the oxidation rate at the surface of the sample is a function of the oxygen pressure in the surrounding atmosphere, the oxygen permeability of the polymer, the solubility of oxygen in the polymer, and the oxidation rate of the reaction. These values are not only material dependent but are temperature dependent and evolve during the oxidation reaction. The gradient of transition of highest oxidation of the surface of cable polymers to the lowest extent of oxidation within the sample thickness for polymers exhibiting DLO in the above works seems to be on the order of 0.2 mm to 0.5 mm such that, when present, DLO might be expected to be a factor for samples around 0.5 mm or thicker for those exposed to air on one side only during oxidation and 1 mm or thicker for those exposed to air on both sides during oxidation.

In addition to modulus profiling mentioned in EMDA Chapter 5.2, other profiling methods have been performed to detect DLO including color change [36], FTIR-detected carbonyl bond generation [37], [38], [39], [40], [41], [42], nuclear magnetic resonance (NMR) T2 relaxation time

[41], oxidation induction time (OIT) [43], and tensile testing of dumbbell samples cut from different locations through the sample thickness [42]. Among these, the analytical characterizations, such as FTIR and NMR, were able to separate the different pathways leading

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 11 to the overall degradation of mechanical properties. Pourmand and collaborators reported three mechanisms giving rise to the increase in the indenter modulus of an EPDM after thermal aging.

The three mechanisms were oxidation-induced crosslinking, migration of low molar mass species, and anaerobic crosslinking [41], [44]. Others used FTIR profiling to study the concentration and distribution of antioxidant molecules [40] and oxidative products such as carboxylic acid and hydroperoxides through the polymer sample thickness [39], [45].

Another study by Wei et al. examined the fracture propagation of polyamide 6 with the observed DLO [46]. After thermal aging, the sample formed a skin-core structure, with the oxidation layer on the surface, and the crack could be arrested by the interface between the oxidized skin and the unoxidized core through plastic deformation. The arrested crack propagated through the unoxidized sample by necking, leading to a constant EAB of approximately 25% when the aging time varied from 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at 180°C. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and after 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, the EAB decreased with aging time [46].

2.2.3.3 Impact of DLO on Qualified Life Presence of DLO can lead to a decrease in overall degradation rate at extremely accelerated conditions (e.g., above 150°C) [15], [29]. If the Ea obtained from a DLO-present high-temperature scenario using an affected material property was used to estimate the time to endpoint, then the time to endpoint would be underestimated, as shown in Figure 4(a), which does not impair conservativeness. However, if the larger Ea obtained from the lower temperature range was used to back-calculate the aging time needed at the high temperature to achieve an extended time to endpoint, then a longer aging time would be required at the high temperature if DLO is present, as demonstrated in Figure 4(b). One method to quantify the effect of DLO on the time to endpoint is to use the equations listed in Section 2.2.2.3, those involving the two activation energies (Ea, Ea) and the crossover temperature (3), if a deviation from linear behavior (associated with Ea) was observed in the DLO-affected region (associated with Ea). It should be noted that the treatment of DLO effect as a change in Ea is only a simplified mathematical treatment and is not derived from reaction kinetics. The amount of change in Ea due to DLO depends on the material property or the degradation indicator used for Ea determination. For the common degradation indicators, EAB is insensitive to DLO since the crack initiated on the surface can rapidly propagate through the entire cross-section [15], [40].

Localized indicators such as carbonyl index (CI, measured by ATR-FTIR) and indentation modulus (IM) will show different values through the thickness, revealing the oxidation profile, while the CI and IM on the surface represent the most degraded condition. The dielectric permittivity ( and ) measures the polarizability of all molecules through the sample thickness collectively, and trends with the average carbonyl index, meaning it is affected by DLO but cannot be used to detect the oxidation profile through the thickness [47], [48].

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 12 Figure 4. Schematic demonstration of the effects of DLO on qualified life, including (a) the underestimation of time to endpoint when extrapolating the DLO-affected high-temperature data using the Ea calculated from the high temperatures (red crosses) (b) a longer pre-aging time needed to accommodate a lowering in Ea due to DLO, if the pre-aging time was calculated based on the Ea derived from low-temperature data (blue pluses).

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 13 2.2.4 Dose Rate Effects 2.2.4.1 Understanding of Dose Rate Effects at the Time of the Expanded Materials Degradation Assessment Dose rate effects (DRE), as discussed in Chapter 5.3 of the EMDA, represent exceptions to equal dose, equal damage behavior in the degradation of cable insulation polymers with exposure to gamma radiation. DRE are cases in which degradation depends not only on total dose, but on how quickly that dose is delivered. In the pre-aging step of cable qualification, the conservatively estimated gamma dose expected to be received by a cable over 40 years of service was applied all at once, within hours. The concern raised in the EMDA is that a significant difference may exist between the effects of a lifetime dose (e.g., 50 Mrad [500kGy])

applied slowly over 40 years to those of a lifetime dose applied over several hours. High dose rate exposure may lead to DLO or other artificial aging behavior that may result in overestimation of cable performance when translated to service conditions. As discussed in the EMDA, the risks associated with DRE include: (1) DRE being commonly found in most of the insulation and jacket materials; and (2) Degradation at low dose rates, such as those present under normal reactor operational conditions, is significantly higher than the degradation that occurs for the same total dose at a higher dose rate, such as in accelerated testing.

Two types of DRE were delineated in EMDA Chapter 5.3:

(1) In the low-dose-rate regime, the thermally induced degradation becomes more dominant (while the proportion of radiation-induced degradation decreases) as the dose rate is lowered; and (2) True chemical DRE, which includes (2-1) heterogeneous oxidation (or DLO as discussed in EMDA Chapter 2.2.2) the high-dose-rate regime, resulting from degradation being bounded by oxygen diffusion rate; and (2-2) other chemical DRE in the radiation-dominant regime.

EMDA Chapter 5.3 also noted that the DRE observed in the same dose rate value ranges can be of different types for different materials. For example, at the combined aging condition of 50°C and 0.1 to 0.5 Gy/h, Neoprene and CSPE jacket materials showed type (1) apparent DRE (Figures 5.8 and 5.9 in EMDA), whereas a crosslinked polyethylene (XLPE) insulation material, which falls in the radiation-dominant region at the same aging condition, showed type (2-2) chemical DRE (Figure 5.10 in EMDA).

DRE was mentioned in the summary Chapter 5.9.2 in EMDA together with DLO, perhaps because of the co-existence of DRE, which are phenomena, and DLO, which is the mechanism behind the type [2-1] DRE phenomena.

Data showing DRE for different polymers can be found in a review paper published in 1993 titled, Predictive Aging Results in Radiation Environments, by K. T. Gillen and R. L. Clough

[49], which was cited in the EMDA report (reference 89). The different types of DRE were illustrated in a figure of that work (recreated with labels as Figure 5 below), including the type (1) apparent DRE due to a shift towards thermal-dominant degradation and the type (2-1) chemical DRE because of DLO. The paper also discussed additional mechanisms for type (2-2) chemical DRE observed at intermediate dose rates, including the slow reaction of long-lived radicals such as those trapped in the crystalline regions of semi-crystalline polymers. Another mechanism is the rate-determining breakdown of intermediate hydroperoxide species.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 14 Figure 5. Schematic illustration of different types of dose rate effects (DRE) under inert (curve I) and aerobic (curves II and III) atmospheres. On the dose to equivalent damage (DED) vs. dose rate plot, the sloped portions (circled) indicate the presence of DRE. The figure was reproduced from Gillen and Clough, 1993 [49].

Based on the proposed mechanisms, it could be deduced that type (2-2) may be material-specific, while type (1) and (2-1) DRE are likely to be observed for all polymers but at material-specific dose rate ranges. Polymers that are more resistant to thermal aging might exhibit the type (1) apparent DRE at lower dose rates.

2.2.4.2 Research on Dose Rate Effects Reported Since the Expanded Materials Degradation Assessment was Published Most research on DRE of cable materials published after 2012 arrived at the same conclusions as mentioned in EMDA Chapter 5.3 [18], [22], [25], [37], [50], [51], [52], [53], [54], [55], [56], [57],

[58], [59], [60], [61]. The topics of these publications include direct observation of DRE in cable materials, the molecular-level evidence supporting proposed DRE mechanisms, and model development incorporating the proposed mechanisms into degradation kinetics. The datasets cited in EMDA Chapter 5.3 were mainly mechanical properties, especially tensile EAB.

Additional properties were measured to examine if DRE could be detected using other testing methods. DRE were observed using dielectric permittivity (, ) [47], [62], dissipation factor (tan

) [63], [64], resistivity [64], density [47], [64], swelling ratio [51], gel fraction [51], oxidation induction temperature (OITp) [51], gas analysis including O2 consumption, CO2 and H2 evolution

[65], [66], and FTIR signals in the carbonyl wavenumber range [67], [68]. Electron paramagnetic resonance results of irradiated XLPE and EPR revealed the presence of long-lived polyenyl, allyl and peroxyl radicals [52], which supports the proposed mechanisms for type (2-2) DRE.

The yields of these free radicals were found to be dose-rate dependent [52].

Exhibition of DRE was found to be dependent on material formulation [66]. For example, based on gas analysis data, an XLPE with a specific antioxidant did not show DRE when the specimens were irradiated at 5 and 40 Gy/h, while the other XLPE samples studied without that antioxidant did show DRE [66].

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 15 Models based on autoxidation kinetics were developed to describe the type (1) apparent DRE with the asymptotic behavior at low dose rates [23], [69], [70]. Fuses model also predicted another DRE at higher dose rates caused by antioxidant depletion [69].

2.2.4.3 Impact of Dose Rate Effects on Qualified Life Based on Figure 6, the same total dose level does not generate the same damage when DRE is present (i.e., DED was not constant). IEEE Std 383-1974 specified a total dose of 50 Mrad (500 kGy) at a dose rate below 1 Mrad/h (10 kGy/h) for radiation pre-aging before LOCA simulation testing. If DRE existed, the 50 Mrad dose delivered at the high dose rate used during qualification would be equivalent to a total dose smaller than 50 Mrad at a low dose rate in the service condition. It should be noted that this hypothetical non-conservative case due to the presence of DRE could be mitigated by the two-orders-of-magnitude overestimation in 50 Mrad compared to actual NPP conditions discussed in 2.2.1 [14]. It is possible that the equivalent total dose, considering a lowered value due to DRE, may still exceed the actual dose that most insulated cables receive during service. No cases have been identified that provide documented evidence of DRE in cables removed from service.

To quantify the impact of DRE, a hypothetical non-conservative case due to DRE is illustrated in in Figure 6, where the 50 Mrad at approximately 4200 Gy/h (accelerated condition) is equivalent to 8 Mrad at 1 Gy/h (service condition, entering temperature-dominant regime), following the DED curve II. In this case, if the target total dose at the service condition is 50 Mrad, then 50 ÷ 8 x 50 = 312.5 Mrad would be needed reach equivalent damage at 4200 Gy/h. Alternatively, the dose rate at the accelerated condition should be carefully chosen to avoid DRE (e.g., between 2 Gy/h and 1000 Gy/h where the curve II is flat). However, the equivalent total dose at the service dose rate needs to be determined from the DED curve for the specific material, which could be challenging due to lack of DED data for most materials, especially at low dose rates. Although models might help provide DED data at low dose rates, model predictions need to be compared to experimental data for validation. The DED curve data available in the literature are typically interpolated from EAB data, which could limit its relevance if the dose to equivalent reduction in dielectric properties is of interest.

Figure 6. Demonstration of using DED curve to find the equivalent dose at two different dose rates for samples showing dose rate effects.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 16 2.2.5 Sequential vs. Concurrent and Synergistic Aging Effects 2.2.5.1 Understanding of Exposure Order and Synergistic Effects in the Expanded Materials Degradation Assessment Synergistic effects, or non-additive aging behavior of cable materials exposed to both elevated temperature and gamma radiation at the same time, were discussed in Chapter 5.4 of the EMDA, while a discussion of sequential vs. concurrent aging was briefly provided in Chapter 5.5 of the EMDA. The concern associated with whether materials age differently based on order of exposure to heat and radiation involves recreating service aging behavior during the accelerated pre-aging of the qualification process. An in-service Class 1E cable located in the containment building of a reactor may be exposed to gamma radiation and to thermal stress during the years of its service, while a cable to be type-tested in the qualification process may be exposed to 40-years-service-temperature-equivalent heat exposure at one service provider before being transferred to another location to have 40-years-equivalent gamma dose applied. If the degradation mechanisms are additive, then the accelerated aging might well represent the service aging. If, however, different mechanisms of degradation occur when the material is exposed to elevated temperatures and to gamma radiation concurrently, then the accelerated aging of the material to be qualified may lead to overestimation of the longevity of the material when translated into the service environment. In Chapter 5.5 of the EMDA, its authors declare that degradation is most severe in concurrent aging and least severe in sequential aging where the thermal aging is carried out before radiation aging. It should be noted that although the basis for this statement was theoretically robust, the validity of the statement is highly dependent on material formulation, with instances of experimental data revealing exceptions, such as inverse temperature effects for certain cable materials.

Chapter 5.4 of the EMDA also called attention to variation in values of thermal-resistivity and radiation-resistivity in different polymers. This knowledge would be helpful in determining if the material under normal operational conditions (50°C and 0.5 Gy/h, as suggested in EMDA) would be subjected to thermal-dominant or radiation-dominant degradation.

The EMDA Chapter 5.4 also mentioned another type of synergistic effect arising from interactions between the different materials in a cable assembly, so that aging the complete assembly might give different results than observed from aging of components separately. In the case of bonded cable insulation, for example, when a second layer of insulation or jacketing material is strongly adhered to the insulation of a cable, the less stable of the two materials may reduce the stability of the other material through creation of additional stresses upon aging. In another example, reactive chemical species may volatilize from one material as it ages and induce aging in a nearby material. In cases where qualification was performed on intact cable assemblies, interactions between components could be considered as captured in the qualification process.

2.2.5.2 Research on Order of Aging and Synergistic Effects Reported Since the Expanded Materials Degradation Assessment As discussed in Chapter 5.5 of the EMDA, the concurrent aging scenario was believed to be the most degradative, as the slowest step in a high-temperature thermal degradation is the initiation of free radicals and radiation could largely accelerate radical generation rate. With the same reasoning, radiation followed by thermal aging is more degradative than the converse, since a large quantity of free radicals produced in the radiation aging step can react with other radical species or oxygen to cause degradation in the subsequent thermal aging step [55], [71]. This

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 17 trend was confirmed for a silicone rubber material aged at elevated thermal (205°C) and at radiation (1 kGy/h at 100°C) conditions simultaneously (concurrent gamma radiation and elevated temperature exposure [R&T]), sequentially (thermal followed by radiation, TR), and in the reverse order (radiation followed by thermal, RT) [72]. The reduction in EAB and tensile strength and increase in modulus, indicating embrittlement, was the most severe under the simultaneous aging condition [72]. The reversed condition (RT) was slightly more degradative than sequential condition (TR) but the difference was not significant [72]. The more pronounced degradation in the simultaneous condition was attributed to higher radical yield upon radiation at temperatures above 120°C [72].

Simultaneous aging has not always been observed to be more degradative than sequential or reversed aging (radiation than heat). In a study of EPR materials aged at 155°C and 1 kGy/h, the EAB performance was found to decrease most rapidly under the reversed (RT) condition and the least rapidly under the sequential condition (TR), while the reduction in EAB under the simultaneous condition (R&T) depended on the type of antioxidant in the material system

[73].

In another study, the relative severity of the simultaneous, sequential, and reversed conditions was found to be dependent on the material properties tested. Fifield et al. reported the EAB results of an EPDM insulation aged at 300 Gy/h and 150°C in which the samples degraded fastest under the reversed order (RT) and the slowest under the sequential condition (TR)

[74]. The same trend was observed for the indenter modulus behavior of the EPDM [74]. In contrast, the carbonyl index and density data for the same material showed that degradation after simultaneous (R&T) and reversed (RT) aging conditions were identical and were significantly faster than the sequential (TR) condition [74], which was consistent with the trend indicated in examples presented in the EMDA. Bortoletto et al. studied the degradation of a cable sheath made of a halogen-free flame-retardant compound irradiated at 100°C and under two dose rates, 0.87-1.31 kGy/h and 4.7-5.8 kGy/h [75]. The reduction in EAB after the sequential (TR) and combined (R&T) aging conditions were of the same level and were much more severe than under the reversed condition (RT) [75]. But the OIT of the same cable sheath reduced faster at the sequential (TR) and reversed (RT) conditions than the concurrent (R&T) aging condition.

One study of XLPE aged at 150°C and 300 Gy/h showed that the sequential (TR) condition was the most degradative, based on the EAB results, perhaps because inverse temperature effects (ITE) (see Chapter 2.2.6 below) were present in the second radiation step [74]. EAB reduced the least in the reversed (RT) condition [74]. The carbonyl index of XLPE showed a different trend wherein the simultaneous aging (R&T) degraded faster than the other two aging conditions.

2.2.5.3 Impact of Order of Aging and Synergistic Effects on Qualified Life For materials exhibiting synergistic effects, meaning degradation induced by heat and radiation was not simply additive, the estimated qualified life would be inaccurate because the time to endpoint estimation assumes that thermal and radiation aging effects are independent. From reported data, the answer of which scenario among the three (R&T, TR, RT) is the most severe depends on the polymer type and formulation. The aging procedure in IEEE Std 383-1974 was TR, which is the most conservative when the material exhibits inverse temperature effects (ITE) but not necessarily the most conservative for all polymers. In a later version, IEEE Std 383-2003, endorsed by NRC in RG 1.211, removed proscription of the order of aging by specifying age conditioning pertains to temperature and radiation, applied either simultaneously

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 18 or sequentially, in an accelerated manner. Revised language in the 2003 edition is quoted below.

Where substantial service-related synergistic effects of pertinent insulating and jacketing material types have been identified, and where methods to reproduce them in accelerated testing are known, such methods shall be used with due consideration to cost, time, and complexity. Thermal and radiation aging synergistic effects may be addressed by simultaneous exposure to radiation and thermal environments or an appropriate choice of sequential exposure order, level, or duration. As a minimum, if no evidence of a synergistic effect exists, a clear statement, noting that this is the case, shall be included with the qualification report. [76]

2.2.6 Inverse Temperature Effects 2.2.6.1 Understanding of Inverse Temperature Effects in Cable Materials at the Time of the Expanded Materials Degradation Assessment Inverse temperature effects (ITE) are mentioned in EMDA Chapter 5.5.1, as a subsection of the sequential vs concurrent aging topic. ITE have been observed in the combined thermal and radiation scenario, where the degradation rate was counterintuitively observed to be faster at lower temperatures (50°C to 60°C) than at elevated aging temperatures with common concurrent radiation dose rate. ITE had been observed for many, but not all, insulation materials including XLPE, XLPO, EPR, and EPDM. The accelerated aging conditions of the qualification process inherently utilize higher temperatures than those experienced by cables in long-term service. The concern associated with ITE is that the predicted time to endpoint for materials that exhibit ITE, using existing aging models, might overestimate the actual time to endpoint at the service conditions. That is, if degradation from gamma exposure proceeds more rapidly at the lower temperatures associated with service conditions, then prediction of cable longevity from results of gamma exposure under accelerated, higher temperature conditions will overestimate cable long-term performance. The ITE phenomenon has been explained to result from the localized chain scission of tie molecules in the amorphous region in semi-crystalline polymers, which is less severe at higher temperatures when the chain mobility and oxygen diffusion rate in the crystalline region are higher. In Chapter 5.9.3 of the EMDA, it was suggested that cable materials susceptible to ITE should be identified and suitable accelerated aging should be developed for them.

2.2.6.2 Research on ITE Reported Since the Expanded Materials Degradation Assessment was Published Similar ITE mechanisms to those discussed in the EMDA Chapter 5.5.1 have been reported in multiple publications [54], [61], [77]. Emphasis has been placed on the observation of ITE below 60°C (the onset of melting of ethylene crystals), detected by EAB, and accompanied by chain scission as evidenced by a decrease in gel content and an increase in density. Two published reviews point out the correlation between chain scission in the amorphous region and lowered EAB based on the re-crystallization of the broken chain ends that causes embrittlement [22],

[55]. How the re-crystallization might affect dielectric properties is not clear. The proposed re-crystallization mechanism is consistent with the observation in the same study that ITE was found in mechanical data but not in other material properties. For example, Liu et al. observed ITE of EPDM below 50 °C from EAB and tensile strength data, but not from gas yield or solvent swelling data [78]. Similarly, Fifield et al. reported ITE for an XLPE material below 50 °C as evidenced by EAB but not by yellowing or FTIR carbonyl index [79]. On the contrary, Verardi

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 19 reported ITE of an ethylene vinyl acetate (EVA) material (a semicrystalline polymer consisting of ethylene segments) detected by OITp, dielectric permittivity, and gel fraction, although their EAB data did not show ITE [80, p. 201], [81].

With experimental confirmation of ITE reported by many research groups, screening of ITE-susceptible materials was suggested to be performed before accelerated aging [60], [82].

Specifically, for the ethylene-based semi-crystalline insulation materials of interest, it was suggested to perform irradiation at room temperature to check if ITE exists, granted that the timeframe to reach an EAB endpoint would be attainable due to ITE. If radiation aging during the qualification process is conducted at ambient temperature, screening of ITE-susceptible materials might be implemented following radiation aging at ambient temperature.

2.2.6.3 Impact of ITE on Qualified Life The non-conservative case is that the material showing ITE was qualified for 40 years based on the high-temperature test data, but it embrittled shortly after exposure to radiation at mild temperature. This situation may have been mitigated in IEEE Std 383-2003 by involving both aged and unaged samples in radiation exposure during DBE, if the radiation exposure during DBE was sufficient to distinguish the ITE-susceptible material. Otherwise, documenting the threshold dose for ITE-susceptible material might be needed to know the dose limit when using the material. The threshold dose could be obtained by exposing the sample to radiation-only aging at mild temperature and no subsequent thermal aging until the EAB reached the endpoint. For cables already installed, the following checklist (Figure 7) can be used to check if there is an ITE-related concern.

Figure 7. Steps for determining if inverse temperature effects (ITE) are of concern.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 20 2.2.7 Pre-Aging of Semi-Crystalline Materials 2.2.7.1 Description in Expanded Materials Degradation Assessment Chapter 5.6 of EMDA specifically discussed semi-crystalline cable insulation polymers, especially XLPE, because their melting temperatures lie between their accelerated aging temperatures and their service temperatures. Associated concerns include the change in Ea, the susceptibility to ITE, and the presence of DLO, which have been discussed in Sections 2.2.2, 2.2.6, and 2.2.3 respectively. The EMDA discussion of pre-aging attempted to use a power law dependence between the dose to equivalent damage (DED) and the dose rate (D),,

for time to endpoint estimation for materials subjected to ITE from DED obtained at high dose rates. However, the power law approach may underestimate the time to endpoint of an XLPE insulation at 20°C without radiation aging, since the transitional dose rate below which thermal aging became dominant was not known.

2.2.8 Impact of the Knowledge Gaps on Operation Status As discussed, the identified knowledge gaps listed in Section 2.2 are situations where the model assumptions for lifetime estimation do not hold. Their local effects on the estimated qualified life at the service condition depend on how much the model assumptions deviate from the actual conditions, as discussed in Sections 2.2.2.3, 2.2.3.3, 2.2.4.3, 2.2.5.3, 2.2.6.3 for each corresponding knowledge gaps. The global impact of the knowledge gaps is illustrated in Figure 8, where there might still be enough conservativeness beyond the qualified life and the built-in safety margin until reaching cable operational capacity (e.g., failing LOCA). The margin and the extra conservatism (as illustrated by the blue shaded segment in Figure 8) can mitigate uncertainty in the service condition qualified life associated with identified knowledge gaps.

Figure 8. Cable degradation indicators progress toward functional failure. The length of the line segments between different stages of degradation is for illustration and is not to scale.

Margin and conservatism mitigate significant uncertainty of the service conditions and the effects of accelerated aging.

A method to estimate additional conservatism is to consider the times required to reach earlier stages of degradation than loss of cable qualified condition. For example, in Figure 8, reduction in tensile EAB and dielectric strength are set as Stage 1 and Stage 2 and occur before functional failure of the cable. The sequence of the two stages considers the case where embrittlement of the insulation leads to cracking and subsequent conductor contact or moisture intrusion resulting in electrical shorting. The time to reach the first stage, significant EAB reduction, may be measurable at the accelerated condition. However, a low EAB does not directly indicate functional failure since many cables with a low EAB still pass LOCA testing [83],

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 21

[84]. Therefore, additional conservatism may still exist beyond the Stage 1 in Figure 8.

Dielectric properties are more directly related to the functional performance of cable insulation and its safety function, but the time to reach a Stage 2 of severely degraded dielectric strength would likely take a long time even at the accelerated aging condition, potentially making it a lagging indicator that passes a threshold of concern at much longer aging times than EAB [85],

[86], [87]. Data has been reported in which both EAB and dielectric performance were measured for the same materials aged at the same conditions. As plotted in Figure 9, the measured dielectric performance (IR, capacitance) did not change during the considered aging period for the two EPR-type insulation materials subjected to combined thermal and radiation condition at 81°C, 0% RH and 69 Gy/h [25]. For both materials, EAB results showed a monotonically decreasing trend, while IR and capacitance (C) fluctuated with aging time [25].

Data for EPDM and XLPE materials are plotted in Figure 10, where the IR did not change except for the EPMD cable aged at 142°C which showed a decreasing trend [88]. To be able to see orders-of-magnitude decrease in IR, the samples would typically be subjected to LOCA testing especially heat and steam exposure [84]. It was also possible that the IR did not decrease after LOCA, or even recovered, as shown in Figure 11.

Figure 9. Normalized elongation at break (EAB), insulation resistance (IR) and capacitance (C) with respect to the baseline values (unaged samples) of Anaconda and BIW insulations subjected to 81°C, 0% RH and 69 Gy/h aging up to 480 days. The data were taken from tables in Appendix A of Watson, et al. [25].

0 0.2 0.4 0.6 0.8 1

1.2 1.4 1.6 1.8 0

60 120 180 240 300 360 420 480 Normalized EAB, IR, C Aging Time (days)

Anaconda, EAB/EAB0 Anaconda, IR/IR0 Anaconda, C/C0 BIW, EAB/EAB0 BIW, IR/IR0 BIW, C/C0

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 22 Figure 10. Normalized elongation at break (EAB) and insulation resistance (IR) of an EPDM insulation/EPDM jacket cable and an XLPE insulation/CSPE jacket cable, subjected to 120°C and 142°C aging. The data were taken from tables in Spaang et al. [88].

Figure 11. Insulation resistance (IR) of XLPO-type cables before and after design basis event (DBE; e.g., LOCA) simulation. The plot was taken from reference [83].

Difficulty in estimating the time to reach Stage 2 in Figure 8 leads to uncertainty in the operation status of the cable beyond the qualified life (e.g., whether the cable is still within the additional conservatism region). Efforts have been made to improve the accuracy of time-based qualified life calculation, for example, by measuring the Ea at low temperatures from oxygen consumption experiments. Even in an ideal case where the time to endpoint can be 0

0.2 0.4 0.6 0.8 1

1.2 0

50 100 150 200 Normalized EAB, IR Aging Time (days)

EPDM, EAB/EAB0, 120°C EPDM, EAB/EAB0, 142°C EPDM, IR/IR0, 120°C EPDM, IR/IR0, 142°C XLPE/CSPE, EAB/EAB0, 120°C XLPE/CSPE, EAB/EAB0, 142°C XLPE/CSPE, IR/IR0, 120°C XLPE/CSPE, IR/IR0, 142°C

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 23 estimated with total accuracy, entering the period of unknown status is inevitable when the time of operation exceeds the target endpoint. To understand the operational status evolution of a cable over its entire degradation curve, the cable needs to be aged and tested periodically until it fails a LOCA simulation. Since LOCA failures typically initiate from localized defects and can differ from one cable to another subjected to the same aging condition [89], the full-lifecycle test would require many replicates to establish statistical reliability, which could be an expensive enterprise. Alternatively, a more cost-effective approach may be to correlate the unknown status (the ability of passing LOCA) to a measurable material property (i.e., a condition indicator or condition monitor in EMDA Vol. 5) and monitor that material property during operation to determine whether the status corresponds to that of a cable able to pass. This approach may still require full testing (including the condition indicator and LOCA with replicates) to establish correlation information.

2.3 Moisture Effects Related Knowledge Gap 2.3.1 Understanding of Moisture Effects at the Time of the Expanded Materials Degradation Assessment As relayed in Chapter 7 of the EMDA, industry responses to generic letter (GL) summary report, Generic Letter 2007-01: Inaccessible or Underground Power Cable Failures That Disable Accident Mitigation Systems or Cause Plant Transients, [90] indicated that water intrusion and/or water treeing in the presence of electrical stress is the most significant failure mechanism in the medium-voltage (MV) cable category (rated 5,000 V) [90] [1]. The GL responses revealed that for low-voltage cables (rated < 2,000 V), general or age-related degradation is the most significant failure mechanism followed by physical/mechanical damage and water/moisture intrusion [1]. It was noted in the GL that, overall, the presence of water or moisture appears to be the predominant factor contributing to MV cable failures.

Chapter 8 of the EMDA mentions that wet or submerged conditions are an aging concern for energized medium voltage cables, especially for early cable designs. Operating experience had shown that certain XLPE-type insulation materials from the early 1970s were more prone to developing water trees and degradation from flaws or inclusions in the material. Water treeing may lead to partial discharge or reduced dielectric strength and potential dielectric breakdown at operating voltages. This behavior was observed after decades of aging but was not uniform and many older cables continued to perform successfully. XLPE quality has improved and tree-retardant XLPE has been developed, but pink EPR has generally been employed as a replacement for moisture-susceptible XLPE cable [91].

In 2008, participants in an NRC - DOE Workshop on Nuclear Power Plant Life Extension Research and Development [92] recommended that future research be considered to investigate the aging effects of very long term wetting for both low-and medium-voltage safety-related cables, with the goal of developing an accurate aging model. In 2010, the NRC published Information Notice (IN) 2010-26, Submerged Electrical Cables [93], as a follow-up to IN 2002-12, Submerged Safety-Related Electrical Cables [94], to inform licensees of updated operating experience on submerged cables. IN 2010-26 stated that the NRC expects licensees to identify conditions which could potentially affect the quality of cables exposed to long-term submergence in water. Upon discovery of a submerged condition, the licensee should take prompt corrective actions to restore the local cable environmental conditions to those within the cable design specifications, immediately determine the operability of the cable to perform its intended function and determine the impact of the adverse environment on the design life of the

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 24 cable. Measures such as design changes to manholes and periodic inspection ensure that cables are not subjected to wetting or submergence.

The effects of long-term wetting of low-voltage cables were not well understood at the time of the EMDA. Results were available from a large volume of wet-aging research on medium-voltage XLPE cable, which is the most common distribution industry cable insulation. Less information on wet aging was available for MV EPR cables used in NPPs. EPRI performed failure mechanism research on EPR cables removed from NPPs after failure or recognition of aging through testing. EPRI technical documents 1015070 [95], 1018777 [96], 1021069 [97],

1022965 [98], 1024894 [99], 3002000554 [100], 3002002993 [101], 3003005323 [102], and 3003007991 [103] describe those results.

2.3.2 Research on Moisture Effects Reported Since the Expanded Materials Degradation Assessment While thermal and radiation aging mainly affect mechanical properties, moisture is more relevant to dielectric function, which is a concern for the higher electrical stress of MV, especially underground and/or submerged cable [22]. Loss of dielectric function is often initiated by charge generation near impurities, such as particulate inclusions in the formulation, degradation products, voids, defects, and moisture. Moisture degradation is of particular concern for submerged and/or underground MV cables. Charge accumulation can be identified by changes in dielectric properties, such as an increase in dissipation factor (tan ) or decrease in insulation resistance. The tan measurement is particularly sensitive to early-stage moisture-related aging. Unlike thermal and radiation aging that follows a free radical degradation mechanism and can be approximately described by phenomenological models, the effect of moisture has not been captured by a widely accepted model with sufficient predictive power. In SAND-2015-1794 [91], a thorough literature review was performed on the mechanisms of moisture-related aging of MV cables and on relevant condition monitoring techniques. The review concluded that there is no uniformly accepted methodology, mechanistic model, or empirical model that can predict lifetimes or performance changes as a function of time [for submerged cable degradation] and that there is no simple path forward to obtain a more comprehensive model due to the complexity [of a variety of environmental stressors involving]

water, ions, voltage, temperature and other factors [91].

A Nuclear Energy University Program project led by University of Minnesota Duluth focused on a mechanistic, predictive understanding of aqueous impact on ageing of MV and LV cables

[104]. Several topics related to a mechanistic understanding were separately studied with the following conclusions:

  • The water vapor permeability of polyethylene (PE) films increased with oxidation.
  • PE films doped with gold nanoparticles were synthesized with the assumption that the nanoparticles would occupy voids during dielectric breakdown and help visualize pore structures.
  • Polypropylene and PE samples aged at dry, submerged, and cyclic dry-rewetting conditions in water and ionic salt solutions, all at 90°C, showed no significant differences in terms of carbonyl index, elastic modulus, or yield strength.
  • Capacitance increased with water tree length gradually, while resistance decreased rapidly as the water tree tip approached the conductor.

Knowledge Gaps Identified in the Expanded Materials Degradation Assessment 25

  • No increase in partial discharge was detected during the two-year aging of harvested MV power cables at 60 Hertz (Hz), 90°C, and elevated voltages (30 kilovolt [kV] for XLPE and 12 kV for EPR cables).

Research conducted by EPRI concluded that water trees are one of the leading degradation mechanisms that contribute to the loss of dielectric insulation strength in MV cable materials in wet or submerged environments. The electrochemical reactions are caused by the combined effect of the presence of water and high electrical stress. The relative importance of these causal stressors can vary among cable installations and are not specifically measured in most cases. Records of cable failures provided by nuclear plant operators confirm the reliability concern for MV cables in wet or submerged environments and serve as a basis for developing the EPRI test program. Practical management of this kind of damage is based on performance tests. EPRI dissipation factor or Tan Delta (tan ) testing guidelines and acceptance criteria have been adopted by most NPP operators as the primary tool for evaluation of MV cables.

EPRI collected member data from 2009 to 2012 to analyze and validate the EPRI-developed acceptance criteria guidelines [105], [106], [107], [108] and to support forensic research on causes of insulation degradation and failure. The guidelines advise tan testing every six years if test result values are in the good or green range and every two years if test result values fall into the further study or yellow range. Guideline values are insulation material specific and may not be available for all cable insulation materials. Pacific Northwest National Laboratory (PNNL) performed a statistical review of the EPRI reports and the associated data with specific plant information redacted. The PNNL analysis found the EPRI guideline thresholds appropriate, as documented in the PNNL-28542-1 report [109]. The NRC review of this data agreed with the conclusions but did not endorse the shortened test interval due to the limited data/test results for some categories of cable types and material, as well as reported cases of multiple test results for the same cables. These data do not support consistent and reliable interpretation of trend results [110]. Available test data from which to make confident conclusions regarding the appropriateness of the EPRI criteria were particularly lacking for XLPE and for brown EPR cable types.

There is no single or simple test to accurately predict remaining useful cable life following submergence or water exposure for nuclear cables. Support for detailed studies of moisture damage is waning in favor of simply adopting a testing-based reliability program that involves periodic or even online testing. EPRI has established tan test criteria that are used to manage cable reliability and to guide decisions such increasing test frequency when cable test data indicates degradation and repair, mitigation, or replacement when test data indicates action required according to the EPRI acceptance criteria [107]. As part of license renewal, utilities agree to establish a cable aging management program that includes regular testing of some or all safety critical cables [111]. Cable testing intervals are typically six to ten years for undamaged insulation, and as low as two years for cables that are degraded. Ongoing testing is performed to ensure continued acceptability and to establish trending data of degradation progression.

Updates on Cable Qualification Standards and Regulatory Guides 26 3.0 Updates on Cable Qualification Standards and Regulatory Guides NPP electrical cables are commonly qualified following procedures in IEEE Std 383 [3], [76],

[112]. Type testing, demonstrating that representative samples of cables can meet performance requirements under service conditions including normal and DBE environments [2], has been the preferred method for qualification. The IEEE Std 383supplements IEEE Std 323, which describes general guidelines and basic requirements for environmental qualification. Nuclear plants have been operating for more than 55 years in the United States with no systematic problems. Initial qualifications of cables may be been done prior to aging being required, but this was quickly corrected, and IEEE standards have been updated periodically. IEEE 383 was initially issued in 1974 [3] and reaffirmed in 1992, and then updated in 2003 [76], 2015 [112],

and 2023 [119]. Versions of the applicable standards are shown below in Table 2, where the four-digit number after dash - represents the release year. Selected versions of IEEE Std 323 and IEEE Std 383 have been endorsed by NRC in regulatory guides (RG), including:

  • RG 1.89, Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants [5], [10], [113].
  • RG 1.131, Qualification Tests of Electric Cables, Field Splices, and Connections for Light-Water-Cooled Nuclear Power Plants (for Comment) (withdrawn) [114].
  • RG 1.211, Qualification of Safety-Related Cables and Field Splices for Nuclear Power Plants [4].

Table 2. IEEE Std 323 and IEEE Std 383 releases and endorsements by the NRC.

Standards Endorsement IEEE 323-1971, trial-use [115]

Applies to NPPs with construction permit prior to July 1, 1974, per NUREG-0588 IEEE 323-1974 [2]

Endorsed in RG 1.89, Rev. 0, November 1974, and in RG 1.89, Rev. 1, June 1984 IEEE 323-1983 [116]

Endorsed in RG 1.209 for mild environment qualification of computer-based instrumentation IEEE 323-2003 [117]

Not endorsed IEEE / International Electrotechnical Commission (IEC) 60780-323-2016 [118]

Endorsed in RG 1.89, Rev. 2, April 2023 IEEE 383-1974 [3]

Endorsed in RG 1.131, Rev. 0, August 1977, for comment (RG 1.131 is withdrawn in April 2009)

IEEE 383-2003 [76]

Endorsed in RG 1.211, Rev. 0, April 2009 IEEE 383-2015 [112]

Not endorsed IEEE 383-2023 [119]

Not endorsed Considering the construction permit issue year for NPPs currently in need of SLR, the IEEE standards relevant to the historical qualification of those NPPs are listed below:

  • IEEE Std 323-1971, IEEE Trial-Use Standard: General Guide for Qualifying Class 1 Electric Equipment for Nuclear Power Generating Stations [115]. Note that aging was not listed as a part of type test procedure.
  • IEEE Std 323-1974, IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations [2]. Section 6.3.2 in the standard lists aging as a step in the type test procedure to simulate the expected end-of-qualified-life condition. Appendix A2 suggested the

Updates on Cable Qualification Standards and Regulatory Guides 27 following aging sequence: (i) aging, including but not limited to accelerated thermal aging, (ii) radiation, and (iii) vibration. Aged equipment should be operated while exposed to DBE and safety functions monitored.

  • IEEE Std 383-1974, IEEE Standard for Type Test of Class 1E Electric Cables, Field Splices, and Connections for Nuclear Power Generating Stations [3]. The standard was more specific to type testing of cables. Aging was involved in two examples of type tests: (i) testing to qualify for normal operation and (ii) testing for operation during DBE. Procedures of these two examples are depicted in Figure 12 and Figure 13, respectively.

Figure 12.

Type testing to qualify for normal operation described in IEEE Std 383-1974. AC

alternating current, AEIC = Association of Edison Illuminating Companies, ANSI

American National Standards Institute, DC = direct current, IPCEA = Insulated Power Cable Engineers Association (now ICEA), mil = 0.001 inch, Figure 13.

Type testing for operation during DBE described in IEEE Std 383-1974.

3.1 Knowledge Gaps Addressed in IEEE Standards and NRC Publications Later versions of the qualification standards released in the early 1970s mentioned the knowledge gaps discussed in EMDA Vol. 5, including but not limited to the following statements.

Where substantial service-related synergistic, dose rate, and diffusion-limited oxidation or acceleration related dose rate effects of pertinent insulating and jacketing material types have been identified, and where methods to reproduce them in accelerated testing are known, such methods shall be used with due consideration to cost, time, and complexity. Thermal and radiation aging synergistic effects may be addressed by simultaneous exposure to radiation and thermal environments or an appropriate choice of sequential exposure order, level, or duration. Dose rate and diffusion-limited oxidation effects are often minimized by reducing the acceleration level and extending

Updates on Cable Qualification Standards and Regulatory Guides 28 the exposure duration. As a minimum, if no evidence of a synergistic effect exists, a clear statement, noting that this is the case, shall be included with the qualification report. (emphasis added)

As Chapter 4.4 of the EMDA mentions, the 2003 release of the IEEE 383 standard addresses many of the shortcomings of the 1974 version that form the basis of the EMDA Knowledge Gaps as quoted in the preceding and following paragraphs.

Reference [in the updated version] is made to IEEE standards on Arrhenius behavior that have also been updated over the years ((76], [120], [121], [122)). Those standards provide guidance on variables such as sample shape, thickness, maximum extrapolation, minimum time for one point to be 5,000 h, and the number of air exchanges in the oven. Mastics for splices, when credited for qualification, must also be addressed for qualified life. Because there may be multiple activation energies in a construction, some guidance is given on how to handle this.

  • IEEE/IEC 60780-323-2016, section 7.4.1.9.3: This process involves applying simulated in-service stresses, typically thermal, moisture, radiation, wear and vibration at magnitudes or rates that are more severe than expected in-service levels, but less severe than levels that cause ageing mechanisms not present in normal service The sequence of age conditioning should consider sequential, simultaneous, and synergistic effects in order to achieve the worst state of degradation expected The risk of overestimation of qualified life or qualified condition due to diffusion limited oxidation effects of application of excessive temperatures or dose rates depends on the materials involved. (emphasis added)

Therefore, the uncertainties in qualified life or status due to the knowledge gaps might be considered less of a concern for NPPs which followed IEEE Std 383-2003 or later versions for the initial cable qualifications.

In addition to the IEEE standards, the following documents published by NRC have also recognized concerns highlighted in the EMDA, including synergistic and dose rate effects.

  • NUREG-0588, Rev. 1 (July 1981), Interim Staff Position on Environmental Qualification of Safety-Related Electrical Equipment, Including Staff Responses to Public Comments: The staff is aware that some equipment important to safety may contain materials whose aging effects from combined environments (applied either concurrently or sequentially) are more severe than the sum of the effects of each environmental parameter applied separately.

Identifying the most limiting combination of environmental parameters in order to establish a qualified life through research programs, however, may be a long-term, on-going process.

Therefore, in lieu of research programs, the qualification program should: (1) Identify potentially significant synergistic effects through a literature search and account for those effects through testing or analysis when establishing a qualified life, or (2) Establish through a literature search or operating experience the basis for omitting synergistic considerations. For equipment where, for example, significant radiation and temperature environments may be present (and in lieu of contrary information determined through items 1 or 2), the synergistic effects to these parameters should be considered during the simulated aging portion of the overall test sequence. The testing sequence used to age the equipment (or material) should be justified and the basis documented in the qualification report. For equipment where thermal aging evaluation has been conducted prior to issuance of this document on non-irradiated equipment or materials, the adequacy of the assumptions made and the conclusions reached will be evaluated on a case-by-case basis. Other methods designed to address synergisms (such as ongoing surveillance with additional qualification testing) may also be found acceptable and will be evaluated on a case-by-case basis. (emphasis added)

Updates on Cable Qualification Standards and Regulatory Guides 29

  • RG 1.89, Rev. 1 (June 1984): 5. Section 6.3.3, "Aging," of IEEE Std 323-1974 and paragraph 50.49(e)(5) should be supplemented with the following: a. If synergistic effects have been identified prior to the initiation of qualification, they should be accounted for in the qualification program. Synergistic effects known at this time are dose rate effects and effects resulting from the different sequence of applying radiation and (elevated) temperature. Periodic surveillance and testing programs are acceptable to account for uncertainties regarding age-related degradation that could affect the functional capability of equipment. Results of such programs will be acceptable as ongoing qualification to modify designated life (or qualified life) of equipment and should be incorporated into the maintenance and refurbishment/replacement schedules. (emphasis added) 3.2 Example Environmental Qualification Reports for Cables To better understand whether and how the knowledge gaps were addressed in the EQ process, seven EQ documents of Class 1E cables used in NPPs were reviewed. Since the purpose of this section is not to comment on the specific EQ processes, the tradenames and manufacturers of the cables are withheld. The conclusion in this section was drawn from only seven reports and should not be generalized to all EQ efforts.

3.2.1 Recognition of Synergistic Effects and Dose Rate Effects Among the seven available documents, one was dated in 1986, four in 1991, one in 2005 and one was undated. Three document packages dated in 1991 included a comprehensive questionnaire and a list of documents including the original EQ reports dated in 1976, 1981 and 1984. The questionnaire seems to have been added when the document package was collected and bound together in 1991. One section of the questionnaire asked if there were any known synergistic effects that could affect the equipment performance and if the report had addressed the synergistic effects, and the answers to these questions were no. A paragraph was included to further discuss both dose rate effects and sequential vs. concurrent aging effects since both were considered as synergistic effects in RG 1.89 Rev. 1. Similarly, in the fourth document dated in 1991, a section titled known synergistic effects also discussed these two knowledge gaps and concluded no need to address them during EQ.

The document dated in 2005 selected the most degradative sequence to be 50 Mrad radiation thermal 150 Mrad radiation aging (DBE dose), by comparing the retention in mechanical properties after thermal and radiation aging in different orders.

The document dated in 1986 did not directly discuss the need of addressing the two knowledge gaps but mentioned the most severe postulated conditions being constructional extreme for possible synergistic effects upon the electrical, chemical and mechanical performance. Their EQ process (Figure 14) involved IR measurement for unaged samples, for samples after 150°C followed by 200 Mrad aging (DBE dose), and before and after LOCA, which could be compared to additional IR data obtained from a separate research program on synergistic effects and dose rate effects.

Updates on Cable Qualification Standards and Regulatory Guides 30 Figure 14.

EQ process of crosslinked polyethylene (XLPE) insulation in a report from 1986.

3.2.2 Recognition of Non-Constant Ea Although the non-Arrhenius behavior and non-constant Ea had not been raised as a concern in the reviewed reports, the phenomenon was recognized, as shown in Figure 15, where the slope changed at 121°C and 150°C. In the EQ report dated in 1991, the slope change was correctly attributed to two different rate controlling mechanisms. The other EQ report also correctly pointed out that the Arrhenius technique is valid if only one chemical reaction is controlling the insulation aging process. In both EQ reports, the slope obtained from the two lowest temperatures (i.e., 113°C and 121°C in Figure 15(a), 127°C and 150°C in Figure 15(b)), was used for Ea calculation.

Updates on Cable Qualification Standards and Regulatory Guides 31 Figure 15.

A change in slope on the Arrhenius plot recognized in two EQ reports, one with no date (a), and one dated in 1991 (b).

As shown in Table 3, all seven representative EQ reports have been checked for the Ea values obtained, the criteria to pick the endpoint and the temperatures for Ea determination. One report showed different Ea values for three formulations, and therefore a total of nine Ea values are listed in Table 3. In addition to the commonly recognized EAB, the voltage withstand capability was also used as a failure criterion for two XLPE cables. The service temperature was 90°C in some reports and 49°C in others. The difference in the assumed service temperature and Ea values led to the large variation in pre-aging time and temperature conditions.

Table 3. Activation energy (Ea), pre-aging time and temperature and the corresponding time to endpoint at the service condition from seven EQ documents.

Polymer Ea (eV)

Ea endpoint Temperature for Ea determination (°C)

Pre-aging time and temperature XLPE 1.35 60% retention of elongation 121, 136, 150 909.5 h @ 150°C XLPE 2.11*

crack after 8x mandrel bend, or fail within 5 min to withstand 4 kV-AC immersed in 1% NaCl (aq.) solution 113, 121 168 h @ 136°C EPR 1.14 50% retention of elongation 121, 150 1440 h @ 155°C EPR 1.15 40% retention of elongation 121, 136, 150, 165, 180 504 h @ 150°C; 336 h @ 165°C EPR 1.13 50% retention of elongation 136, 150, 165, 175 EPR 1.32 50% retention of elongation 136, 150, 165, 175 EPDM 1.31 N/A N/A 168 h @ 121°C EPR 1.69 50% retention of elongation 121, 135, 150 168 h @ 150°C XLPE 1.36 voltage withstand test at 3.0 kV for 1 min 127, 150 168 h @ 150°C

  • The Ea value was not listed in the original EQ report but calculated using the data provided in the EQ report.

The Ea value listed in the original EQ report was 1.32 eV, but it was found to be 1.23 eV when re-calculated using the data provided in the EQ report.

Using the data provided in the EQ report, the Ea was re-calculated to be 1.51 eV from three temperatures or 1.84 eV from the two lowest temperatures.

Discussion of Status and Potential Paths Forward 32 4.0 Discussion of Status and Potential Paths Forward 4.1 What has Changed Since the Expanded Materials Degradation Assessment was Published?

The EMDA highlighted several points of uncertainty and potential concern regarding continued use of qualified cables in long-term operation, beyond their original 40-year qualified life.

Several of these points relate to assumptions that were made in the methodology of the original time-based qualification process and its accuracy in predicting cable performance over many decades of service. Accelerated aging of a representative cable under elevated conditions was used in qualification to represent the aging expected to occur on similar cables installed in an operating plant over the 40-year operating license period. The equivalency of short term accelerated aging effects and long-term service aging effects in the aged cable was noted in the EMDA to be challenged by several aspects of the accelerated aging process. The uncertainty of actual plant conditions was also identified in the EMDA. Finally, concerns regarding performance of cables not originally qualified for wet service, but located in a long-term wetted NPP environment, were also raised. These EMDA gaps surround the question of whether the controls and administrative limitations for use of cables important to safety in long-term operation are sufficiently conservative to provide reasonable assurance of reliable performance.

Prior to publication of the EMDA and the communication of the concerns raised therein, the nuclear cable community has taken action to address the EMDA-identified issues in revisions of the IEEE 323-1974 [2] and 383-1974 [3], notably in the 2003 revisions [76], [117] and the 2015 /

2016 revisions [112], [118]. As discussed in Section 2.0 of this report, the NRC, EPRI, and DOE researchers, as well as industry and academic entities, have performed further aging and testing research on cable materials to investigate issues such as calculation of Ea, diffusion limited oxidation, synergistic effects of combined thermal and radiation aging, inverse temperature effects, and aging due to moisture. These entities have also developed new technologies and methods for condition monitoring of aging cables and further determined correlations between test results and cable status. EPRI has worked with its members to demonstrate testing options in operating NPPs and to obtain measured in-plant conditions for cable locations in PWRs and BWRs.

International consensus-based standards organizations that develop cable qualification guidance have updated standards to include improved guidance regarding the limitations of accelerated aging (i.e., time period extrapolation, synergy between effects of temperature and radiation, dose rate effects, etc.) [118]. EPRI continues to update its cable aging management guidance based on new research results and operating experience (OE) [123]. The NRC has acknowledged and endorsed updated qualification standards [5]. The potential for moisture damage to cables has also been acknowledged [6], [7] and methods to verify cable integrity have been or are being established [110].

Updated NRC guidance in RG 1.89 [5] endorses the international standard IEC/IEEE 60780-323-2016 [118] for qualification of electrical equipment important for safety in nuclear facilities.

This standard is an update of earlier IEEE-323 standards and directly reflects an appreciation of the concerns raised in the EMDA.

Discussion of Status and Potential Paths Forward 33 4.2 How to Manage Cables Past their Qualified Life?

The concerns raised in the EMDA largely relate to the question of confidence for continued use of qualified cables beyond their qualified life. The updated and endorsed IEC/IEEE 60780-323-2016 document [118] directly answers this question with a section entitled Reassessing qualified life, which addresses achieving qualified status for cables with anticipated service life beyond their EQ-yielded qualified life. This may refer to cables beyond their original qualified life or cables for which, due to limitations of accelerated aging and material or environment knowledge (such as those raised in the EMDA), have significant uncertainty in relation to their appropriate qualified life. Options available for reassessing qualified life for cables that fit this description as delineated in the standard [118] are listed below. Qualified cable reassessment is a natural part of a cable aging management program and, following current guidance, appreciates the potential concerns raised in the EMDA.

4.2.1 Use Conservatism The EMDA knowledge gaps represent sources of uncertainty in cable qualified life that may contribute to a reduction in the conservatism of the historic qualification process. Re-analysis of original EQ methodologies to utilize built-in conservatism and safety margin has been the primary method used by industry to extend qualified life beyond original periods. Understanding the assumptions of the original EQ methodology and limitations of the accelerated aging factors used may result in an opportunity to account for those limitations and aging artifacts to arrive, with proper verification, at aging models that can provide a sufficiently conservative qualified life.

4.2.2 Type Test on Aged Samples from the Nuclear Power Plant Extension of the qualified life of a cable may also be achieved through removal from service of a qualified cable prior to the end of its qualified life, further aging of the sample using accelerated means, and demonstration of the ability of the cable to perform during a simulated DBE. Similar cables in identical service conditions might then be apportioned the extended qualified life, representing service life plus the added period.

4.2.3 Perform Type Testing for Longer Qualified Life Qualified life may be extended (e.g., from 40 years) by re-qualifying an existing or new cable artificially aged to a longer period representing the desired qualified life (e.g., to 80 years) prior to demonstrating performance or the cable following a DBE simulation.

4.2.4 Replace Components Aging components may be replaced with new components to extend the qualified life of the system if the component is accessible to replace, and if the replacement process does not adversely affect the ability of the system to perform its safety-related function.

4.2.5 Pursue Condition-based Qualification An alternative option to the time-based approach for qualifying cables that has historically been used by the nuclear industry in the U.S., in which the desired qualification life is imparted to a material before it is demonstrated to pass a DBE simulation, is to verify through testing that the condition of the cable is consistent with a condition in which it can conservatively be expected to perform its safety-related function during a DBE [83], [124]. Condition-based qualification (CBQ)

Discussion of Status and Potential Paths Forward 34 justifies continued use of a qualified cable based on test results that establish the cable condition along a degradation profile that has been matched to a qualification program, where a representative sample cable continues to perform its safety function following a DBE. The key to performing CBQ is to find a suitable condition indicator (or a group of complementary indicators) that monotonically tracks with aging and can be measured nondestructively. A list of test methods probing the chemical, thermal, mechanical, and dielectric properties of cable insulations have been surveyed for their applicability as condition monitoring techniques, where no single condition monitoring method was found to be suitable for CBQ for all cable types [25],

[32], [83], [84], [125]. The well-established EAB trends with aging [25], [84], but it is a destructive method. IM and OIT have been shown to trend with certain jackets and insulation materials [25],

[83], [84]. Non-destructive techniques that could potentially be used for condition monitoring include reflectometry, dielectric spectroscopy, dielectric loss (tan ), polarization/depolarization current, monitored withstand, interdigital capacitance, or other methods that provide a value that monotonically changes as the cable insulation sample degrades in response to normal operating stresses or elevated temperature and radiation exposure for accelerated aging.

Conclusion 35 5.0 Conclusion While re-analysis of the original 40-year cable qualification data was largely successful in supporting extension of plant operating licenses to 60 years, when it became apparent that there was a need and desire to continue to operate NPPs in the U.S. beyond their first license renewal, it was prudent to consider material aging issues that may arise during operation beyond the original 60 years and up to the 80 years of a second license renewal. The EMDA process convened nuclear cable experts to consider the state of knowledge of cable materials and aging concerns in the context of such extended operation. That effort resulted in the highlighting of several knowledge gaps and topics of potential concern related to the methodology historically used for cable qualification, the environmental conditions of cables in the service environment, and the long-term effects of moisture on cables not originally anticipated to be wetted in service. The earliest standards for cable qualification did not adequately address these concerns, and the phenomena identified contributed to uncertainty in the expected safety-related performance of qualified cables in DBE conditions, particularly as the cables continued to age past their original qualified life.

Following publication of the EMDA in 2014 [1] and communication of the EMDA topics within the nuclear cable community, much research has been done to consider and address the identified knowledge gaps. Technical standards, industry practice, and regulatory guidance have all been updated since the initial version to account for the issues summarized in the EMDA. Following these accomplishments, new cables are qualified according to a process that minimizes aging artifacts and considers the limitations of artificial aging in recreating NPP service aging. Several options have been developed to reassess the qualified life of installed cables with either anticipated service lives that will exceed their qualified life or for which uncertainty exists regarding their qualified life. These methods may be used to establish a technical basis for extending the qualified life of existing, aged cables.

Condition monitoring of cables has advanced, especially for cables in wet environments using tan testing. Research continues by EPRI and others to develop more advanced non-destructive testing methodologies that can be used for cables in dry environments [126]. An additional option for providing confidence in the reliability of cables that are important to safety is CBQ. This option requires development of correlation between cable test results and the ability of a cable to perform its safety function during and after a DBE. CBQ could provide a technical and conservative basis for continued use of a cable in verifiable good condition indefinitely, while not being limited to the original qualified life or hampered by potential uncertainties and inadequate conservatism associated with a time-based qualification method.

The EMDA has served an important role in bringing cable material aging concerns relevant to long-term operations to light for the broader nuclear cable community. Since the initial days of qualification, the community has responded to concerns such as those raised in the EMDA by taking action to improve methods for developing technical bases for reliable safety-related cable use, as reflected in updated and endorsed qualification standards. Operating experience has demonstrated that service environments of most plant cables are much less severe in terms of dose rate and temperature than the conservative conditions used as boundaries in initial qualification methodologies. With advancements in understanding of the points identified in the EMDA, the industry has the tools it needs to confidently use new and existing nuclear cables in new construction and in existing reactors.

References 36 6.0 References

[1]

NRC. 2014. Expanded Materials Degradation Assessment (EMDA): Aging of Cables and Cable Systems. Nuclear Regulatory Commission NUREG/CR-7153 Vol. 5 ORNL/TM-2013/532. Washington, D.C. https://www.nrc.gov/docs/ML1427/ML14279A461.pdf.

[2]

IEEE 323-1974. 1974. IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations. IEEE Standards Association.

https://ieeexplore.ieee.org/document/6568022.

[3]

IEEE 383-1974. 1974. IEEE Standard for Type Test of Class 1E Electric Cables, Field Splices, and Connections for Nuclear Power Generating Stations. IEEE Standards Association. https://doi.org/10.1109/IEEESTD.1974.120627.

[4]

NRC. 2009. Qualification of Safety-Related Cables and Field Splices for Nuclear Power Plants. Nuclear Regulatory Commission RG-1.211. Washington, D.C.

https://www.nrc.gov/reading-rm/doc-collections/reg-guides/power-reactors/rg/division-1/division-1-201.html.

[5]

NRC. 2023. Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants. Nuclear Regulatory Commission RG 1.89 R2. Washington, D.C.

https://www.nrc.gov/reading-rm/doc-collections/reg-guides/power-reactors/rg/division-1/division-1-81.html.

[6]

NRC. 2017. Generic Aging Lessons Learned for Subsequent License Renewal (GALL-SLR), Revision 1 Final Report, Vol. 1. Nuclear Regulatory Commission NUREG-2191 Vol.

1 R1. Washington, D.C. https://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr2191/r0/index.htm.

[7]

NRC. 2023. Generic Aging Lessons Learned for Subsequent License Renewal (GALL-SLR), Revision 1, Final Report, Vol. 2, Nuclear Regulatory Commission NUREG-2191 Vol.

2 R1. Washington, D.C.

https://www.nrc.gov/reactors/operating/licensing/renewal/slr/guidance.html.

[8]

NRC NUREG/CR-6923. 2007. Expert Panel Report on Proactive Materials Degradation Assessment. Nuclear Regulatory Commission. https://www.nrc.gov/reading-rm/doc-collections/nuregs/contract/cr6923.

[9]

10 CFR 50.49. 2025. Environmental Qualification of Electric Equipment Important to Safety for Nuclear Power Plants. Code of Federal Regulations. https://www.ecfr.gov/current/title-10/chapter-I/part-50/subject-group-ECFRdf2af20f8a72d91/section-50.49.

[10] AEC RG 1.89. 1974. Qualification of Class 1E Equipment for Nuclear Power Plants.

Atomic Energy Commission. https://www.nrc.gov/docs/ML0128/ML012880422.pdf.

[11] Appendix B to Part 50, Title 10. Appendix B to Part 50Quality Assurance Criteria for Nuclear Power Plants and Fuel Reprocessing Plan, Code of Federal Regulations.

https://www.ecfr.gov/current/title-10/part-50/appendix-Appendix B to Part 50.

[12] Hosticka, C., E. R. Kingsbury, and A. C. Bruhin. 1980. Qualification of Cables to IEEE Standards 323-1974 and 383-1974. IEEE Transactions on Nuclear Science 27(1): 885-889. https://doi.org/10.1109/TNS.1980.4330945.

[13] EPRI. 2013. Long-Term Operations: Normal Temperature and Radiation Dose to Installed Cable for U.S. Nuclear Power Plants in Containment. Electric Power Research Institute 3002000816. Palo Alto, CA.

https://www.epri.com/research/products/000000003002000816.

[14] EPRI. 2017. Results of Radiation and Temperature Monitors Research for Installed Cables at U.S. Nuclear Power Plants in Support of Long-Term Operations. Electric Power Research Institute 3002010404. Palo Alto, CA.

https://www.epri.com/research/products/000000003002010404.

References 37

[15] Celina, M. C., K. T. Gillen, and R. Bernstein. 2015. Review of Some Important Issues and Resolutions when Lifetime Predictions of Elastomers are Made Using Accelerated Aging Techniques. SAND2015-0917C. https://www.osti.gov/servlets/purl/1504343.

[16] Gillen, K. T., R. Bernstein, and M. Celina. 2015. The Challenges of Accelerated Aging Techniques for Elastomer Lifetime Predictions. Rubber Chemistry and Technology 88(1):

1-27. SAND2017-0624J. https://www.osti.gov/servlets/purl/1361646.

[17] Gillen, K. T. 2020. Importance of Synergism for Degradation of Elastomers in Combined Radiation Plus Temperature Environments. Rubber Chemistry and Technology 93(1):

121-141. https://doi.org/10.5254/rct.19.80457.

[18] -arac, T., N. Quiévy, A. Gusarov, and M. J. Konstantinovi. 2016. Influence of -

Irradiation and Temperature on the Mechanical Properties of EPDM Cable Insulation.

Radiation Physics and Chemistry 125: 151-155.

https://doi.org/10.1016/j.radphyschem.2016.03.024.

[19] Moon, B., N. Jun, S. Park, C.-S. Seok, and U. S. Hong. 2019. A Study on the Modified Arrhenius Equation Using the Oxygen Permeation Block Model of Crosslink Structure.

Polymers 11(1): 136. https://doi.org/10.3390/polym11010136.

[20] Blivet, C., J.-F. Larché, Y. Israli, and P.-O. Bussire. 2022. Non-Arrhenius Behavior:

Influence of the Crystallinity on Lifetime Predictions of Polymer Materials Used in the Cable and Wire Industries. Polymer Degradation and Stability 199: 109890.

https://doi.org/10.1016/j.polymdegradstab.2022.109890.

[21] Tocháek, J. and Z. Vrátníková. 2014. Polymer life-time prediction: The Role of Temperature in UV Accelerated Ageing of Polypropylene and Its Copolymers, Polymer Testing 36: 82-87. https://doi.org/10.1016/j.polymertesting.2014.03.019.

[22] Fifield, L.S., Y. Ni, and M. P. Spencer. 2024. Status of Cable Aging Knowledge Gaps Identified in the Expanded Materials Degradation Assessment (EMDA). Pacific Northwest National Laboratory PNNL-34863. Richland, WA.

https://lwrs.inl.gov/content/uploads/11/2024/07/EMDA_CableGaps.pdf.

[23] Celina, M., E. Linde, D. Brunson, A. Quintana, and N. Giron. 2019. Overview of Accelerated Aging and Polymer Degradation Kinetics for Combined Radiation-Thermal Environments. Polymer Degradation and Stability 166: 353-378.

https://doi.org/10.1016/j.polymdegradstab.2019.06.007.

[24] Fifield, L. S., W. Fuchs, Y. Ni, D. Li, M. R. Pallaka, A. L. Arteaga, M. P. Spencer, and A.

Zwoster. 2021. Inhomogeneous Aging of Nuclear Power Plant Electrical Cable Insulation.

Pacific Northwest National Laboratory PNNL-31443. Richland, WA.

https://lwrs.inl.gov/content/uploads/11/2024/03/InhomogeneousAgingNPP_ElectricalCableI nsulation.pdf.

[25] Watson, S. 2021. Assessment of Condition Monitoring Methods of Electrical Cables.

National Institute of Standards and Technology NISTIR 8391. Gaithersburg, MD.

https://www.nrc.gov/docs/ML2229/ML22298A160.pdf.

[26] Qin, S., R. Liu, Q. Wang, X. Chen, Z. Shen, Z. Hou, and Z. Ju. 2022. Study on the Molecular Structure Evolution of Long-Term-Operation XLPE Cable Insulation Materials.

Energy Reports 8:1249-1256. https://doi.org/10.1016/j.egyr.2021.11.212.

[27] de Medeiros, P. R., P. L. B. Araujo, K. A. S. Aquino, and E. S. Araujo. 2022. Green Polyethylene in Harsh Environments: Gamma-irradiation Effects. Materials Research 25:

e20220186. https://doi.org/10.1590/1980-5373-MR-2022-0186.

[28] Bene, M., V. Plaek, G. Matuschek, A. A. Kettrup, K. Gyryová, W. D. Emmerich & V.

Balek. 2005. Lifetime Simulation and Thermal Characterization of PVC Cable Insulation Materials. Journal of Thermal Analysis and Calorimetry 82: 761-768.

https://doi.org/10.1007/s10973-005-0961-6.

References 38

[29] Celina, M. C. 2013. Review of Polymer Oxidation and Its Relationship with Materials Performance and Lifetime Prediction. Polymer Degradation and Stability 98(12): 2419-2429. https://doi.org/10.1016/j.polymdegradstab.2013.06.024.

[30] Zaghdoudi, M., A. Kmmling, M. Jaunich, and D. Wolff. 2020. Erroneous or Arrhenius: a Degradation Rate-Based Model for EPDM during Homogeneous Ageing, Polymers 12(9):

2152. https://doi.org/10.3390/polym12092152.

[31] Celina, M., K. T. Gillen, and R. A. Assink. 2005. Accelerated Aging and Lifetime Prediction: Review of Non-Arrhenius Behaviour Due to Two Competing Processes.

Polymer Degradation and Stability 90(3): 395-404.

https://doi.org/10.1016/j.polymdegradstab.2005.05.004.

[32] Assink, R.A., K. T. Gillen, and R. Bernstein. 2005. Nuclear Energy Plant Optimization (NEPO) Final Report on Aging and Condition Monitoring of Low-Voltage Cable Materials.

Sandia National Laboratories SAND2005-7331. Albuquerque, NM.

https://doi.org/10.2172/875986.

[33] Linde, E., F. Nilsson, M. Barrett, M. S. Hedenqvist, and M. C. Celina. 2021. Time-and Feedback-Dependent DLO Phenomena in Oxidative Polymer Aging. Polymer Degradation and Stability 189: 109598. https://doi.org/10.1016/j.polymdegradstab.2021.109598.

[34] Quintana, A. and M. C. Celina. 2018. Overview of DLO Modeling and Approaches to Predict Heterogeneous Oxidative Polymer Degradation. Polymer Degradation and Stability 149: 173-191. https://doi.org/10.1016/j.polymdegradstab.2017.11.014.

[35] Dinari, A. F. Zairi, M. Chaabane, J. Ismail, and T. Benameur. 2021. Thermo-Oxidative Stress Relaxation in Carbon-Filled SBR. Plastics, Rubber and Composites 50(9): 425-440. https://doi.org/10.1080/14658011.2021.1913385.

[36] Spencer, M., W. Fuchs, Y. Ni, D. Li, M.R. Pallaka, A. Arteaga, and L.S. Fifield. 2023.

Color as a Tool for Quantitative Analysis of Heterogeneous Polymer Degradation.

Materials Today Chemistry 29: 101417. https://doi.org/10.1016/j.mtchem.2023.101417.

[37] Gong, Y., S.-M. Hu, X.-L. Yang, J.-L. Fei, Z.-G. Yang, X.-Q. Shi, Y.-C. Xie, A.-H. Guo, J.-F.

Xu. 2017. Comparative Study on Degradation of Ethylene-Propylene Rubber for Nuclear Cables from Gamma and Beta Irradiation, Polymer Testing 60: 102-109.

https://doi.org/10.1016/j.polymertesting.2017.03.017.

[38] Celina, M. C., E. Linde, and E. Martinez. 2021. Carbonyl Identification and Quantification Uncertainties for Oxidative Polymer Degradation. Polymer Degradation and Stability 188:

109550. https://doi.org/10.1016/j.polymdegradstab.2021.109550.

[39] Sugimoto, M., A. Shimada, H. Kudoh, K. Tamura, and T. Seguchi. 2013. Product Analysis for Polyethylene Degradation by Radiation and Thermal Ageing. Radiation Physics and Chemistry 82: 69-73. https://doi.org/10.1016/j.radphyschem.2012.08.009.

[40] Shimada, A., M. Sugimoto, H. Kudoh, K. Tamura, and T. Seguchi. 2013 Degradation Distribution in Insulation Materials of Cables by Accelerated Thermal and Radiation Ageing, IEEE Transactions on Dielectrics and Electrical Insulation. 20(6): 2107-2116.

https://doi.org/10.1109/TDEI.2013.6678859.

[41] Pourmand, P., E. Linde, M. S. Hedenqvist, I. Furó, S. V. Dvinskikh, and U. W. Gedde.

2016. Profiling of Thermally Aged EPDM Seals Using Portable NMR, Indenter Measurements and IR Spectroscopy Facilitating Separation of Different Deterioration Mechanisms. Polymer Testing 53: 77-84.

https://doi.org/10.1016/j.polymertesting.2016.05.015.

[42] Zhang, Y., Z. Hou, K. Wu, S. Wang, J. Li, and S. Li. 2020. Influence of Oxygen Diffusion on Thermal Ageing of Cross-Linked Polyethylene Cable Insulation. Materials 13(9): 2056.

https://doi.org/10.3390/ma13092056.

[43] Lungulescu, E.-M., R. Setnescu, S. Ilie, and M. Taborelli. 2022. On the Use of Oxidation Induction Time as a Kinetic Parameter for Condition Monitoring and Lifetime Evaluation

References 39 under Ionizing Radiation Environments. Polymers 14(12) 2357.

https://doi.org/10.3390/polym14122357.

[44] Pourmand, P., M. S. Hedenqvist, I. Furó, and U. W. Gedde. 2017. Radiochemical Ageing of Highly Filled EPDM Seals as Revealed by Accelerated Ageing and Ageing In-Service for 21 Years. Polymer Degradation and Stability 144: 473-484.

https://doi.org/10.1016/j.polymdegradstab.2017.09.008.

[45] Min, D., S. Li, N. Hirai, and Y. Ohki. 2016. Modeling of Oxidation Process and Property Changes of Ethylene-Propylene-Diene Copolymer, IEEE Transactions on Dielectrics and Electrical Insulation 23(1): 537-546. https://doi.org/10.1109/TDEI.2015.005400.

[46] Wei, X.-F., K. J. Kallio, S. Bruder, M. Bellander, H.-H. Kausch, U. W. Gedde, M. S.

Hedenqvist. 2018. Diffusion-limited Oxidation of Polyamide: Three Stages of Fracture Behavior. Polymer Degradation and Stability 154: 73-83.

https://doi.org/10.1016/j.polymdegradstab.2018.05.024.

[47] E. Linde, L. Verardi, D. Fabiani, and U. W. Gedde. 2015. Dielectric Spectroscopy as a Condition Monitoring Technique for Cable Insulation Based on Crosslinked Polyethylene.

Polymer Testing 44: 135-142. https://doi.org/10.1016/j.polymertesting.2015.04.004.

[48] Ji, M., X. Colin, W. Liu, X. Chi, S. Chatenet, and W. Wei. 2024. Comparison of the Performances and Aging Mechanisms of XLPE and EVA Insulation During Their Thermal Oxidative Aging. Polymer Degradation and Stability 222: 110699.

https://doi.org/10.1016/j.polymdegradstab.2024.110699.

[49] Gillen, K. T., and R. L. Clough. 1993. Predictive Aging Results in Radiation Environments, Radiation Physics and Chemistry. 41(6) 803-815.

https://doi.org/10.1016/0969-806X(93)90026-Q.

[50] Ferry, M., G. Roma, F. Cochin, S. Esnouf, V. Dauvois, F. Nizeyimana, B. Gervais, Y.

Ngono-Ravache. 2020. Polymers in the Nuclear Power Industry. In Comprehensive Nuclear Materials (Second Edition), edited by R. J. M. Konings and R. E. Stoller, 545-580.

Oxford: Elsevier. https://doi.org/10.1016/B978-0-12-803581-8.11616-9.

[51] Boguski, J., and G. Przybytniak. 2016. Benefits and Drawbacks of Selected Condition Monitoring Methods Applied to Accelerated Radiation Aged Cable. Polymer Testing 53:

197-203. https://doi.org/10.1016/j.polymertesting.2016.05.023.

[52] Gharazi, S., K. R. Mecadon, L. Gonzalez-Lopez, and M. Al-Sheikhly. 2023. On the Mechanism of Radiation and Thermal-Induced Degradation of the Insulation Cables in Nuclear Power Plants-the Presence of Long-Lived Polyenyl C-Centered Radicals.

Radiation Physics and Chemistry 203(A): 110603.

https://doi.org/10.1016/j.radphyschem.2022.110603.

[53] White, II, G. V., R. Tandon, L. M. Serna, M. C. Celina, and R. Bernstein. 2013. An Overview of Basic Radiation Effects on Polymers and Glasses. Sandia National Laboratories SAND2013-8003P. Albuquerque, NM. https://www.osti.gov/biblio/1671997.

[54] Giuliano, D., R. Duckworth, and L. Cunningham. 2021. Literature Review for Conducting Accelerated Aging and Simulated Loss-of-Coolant Accident (LOCA) Exposures for Nuclear-Grade Wires and Cable. Oak Ridge National Laboratory ORNL/TM-2021/2166.

Oak Ridge, TN.

[55] Mustafa, E., R. S. A. Afia, and Z.. Tamus. 2019. Condition Monitoring Uncertainties and Thermal - Radiation Multistress Accelerated Aging Tests for Nuclear Power Plant Cables:

A Review. Periodica Polytechnica Electrical Engineering and Computer Science 64(1):

20-32. https://doi.org/10.3311/PPee.14038.

[56] -arac, T., N. Quiévy, A. Gusarov, and M. J. Konstantinovi. 2016. The Study of Temperature and Radiation Induced Degradation of Cable Polymers: A Comparison Between the Mechanical Properties of Industrial and Neat EPDM. Procedia Structural Integrity 2: 2405-2414. https://doi.org/10.1016/j.prostr.2016.06.301.

References 40

[57] -arac, T., J. Devaux, N. Quiévy, A. Gusarov, and M. J. Konstantinovi. 2017. The Correlation Between Elongation at Break and Thermal Decomposition of Aged EPDM Cable Polymer. Radiation Physics and Chemistry 132: 8-12.

https://doi.org/10.1016/j.radphyschem.2016.10.017.

[58] Celina, M. C., and K. T. Gillen. 2016. Predicting Polymer Degradation and Mechanical Property Changes for Combined Aging Environments. Sandia National Laboratories SAND2016-8618C. Albuquerque, NM. https://www.osti.gov/servlets/purl/1380191.

[59] White, II, G. V., J. L. Schroeder, P. S. Sawyer, D. Wichhart, G. A. Mata, J. Zorrilla and R.

Bernstein. Radiation Testing of a Low Voltage Silicone Nuclear Power Plant Cable. Sandia National Laboratories SAND2014-17756. Albuquerque, NM.

https://doi.org/10.2172/1158570.

[60] Gillen, K. T., and M. C. Celina. 2022. Issues with Approaches for Simulating Aging of Nuclear Power Plant Cable Materials. Rubber Chemistry and Technology 95(2): 322-341.

https://doi.org/10.5254/rct.21.78976.

[61] Celina, M. C., K. T. Gillen, and E. R. Lindgren. 2013. Nuclear Power Plant Cable Materials-Review of Qualification and Currently Available Aging Data for Margin Assessments in Cable Performance. Sandia National Laboratories SAND2013-2388. Albuquerque, NM.

https://doi.org/10.2172/1096518.

[62] Verardi, L., D. Fabiani, and G. C. Montanari. 2014. The Influence of Accelerated Aging Procedures on The Correlation of Electrical and Mechanical Properties of LV Nuclear Power Plant Cables. IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Des Moines, IA, October 19-22, 2014.

https://doi.org/10.1109/CEIDP.2014.6995898.

[63] Suraci, S. V. 2020. Aging Assessment of Polyethylene-Based Insulated Low-Voltage Cables for Nuclear Applications. Dissertation thesis, Alma Mater Studiorum Universit di Bologna. Dottorato di ricerca in Ingegneria biomedica, elettrica e dei sistemi, 33 Ciclo.

https://doi.org/10.48676/unibo/amsdottorato/9551.

[64] Kuriyama, I., N. Hayakawa, Y. Nakase, J. Ogura, H. Yagyu, and K. Kasai. 1979. Effect of Dose Rate on Degradation Behavior of Insulating Polymer Miaterials (sic). IEEE Transactions on Electrical Insulation EI-14(5): 272-277.

https://doi.org/10.1109/TEI.1979.298231.

[65] Fifield, L. S., Y. Ni, A. Sriraman, W. K. Fuchs, D. Li, M. R. Pallaka, M. P. Spencer, K.

Grubel, J. D. Egbert, A. Zwoster. 2021. Evaluation of Oxygen Consumption as a Sensitive Measure of Electrical Cable Polymer Insulation Degradation. Pacific Northwest National Laboratory PNNL-31954. Richland, WA. https://doi.org/10.2172/2280700.

[66] Ferry, M., F. Carpentier, and M. Cornaton. 2021. Radio-Oxidation Ageing of XLPE Containing Different Additives and Filler: Effect on the Gases Emission and Consumption.

Polymers 13(17): 2845. https://doi.org/10.3390/polym13172845.

[67] Suraci, S. V., S. Amat, L. Hippolyte, A. Malechaux, D. Fabiani, C. Le Gall, O. Juan, and N.

Dupuy. 2022. Ageing Evaluation of Cable Insulations Subjected to Radiation Ageing:

Application of Principal Component Analyses to Fourier Transform Infra-Red and Dielectric Spectroscopy. High Voltage 7(4): 652-665. https://doi.org/10.1049/hve2.12239.

[68] Liu, Q., W. Huang, B. Liu, P. Wang, and H. Chen. 2022. Experimental and Theoretical Study of Gamma Radiolysis and Dose Rate Effect of o-Cresol Formaldehyde Epoxy Composites. ACS Applied Materials & Interfaces 14(4): 5959-5972.

https://doi.org/10.1021/acsami.1c19609.

[69] Fuse, N., H. Homma, and T. Okamoto. 2012. A New Degradation Model with Critical Antioxidant Concentration Concept for Safety Cables. 2012 IEEE International Conference on Condition Monitoring and Diagnosis, Bali, Indonesia, September 23-27, 2012. https://doi.org/10.1109/CMD.2012.6416398.

References 41

[70] Chen, T., T.-Y. Chang, B. A. Konstanczer, M. A. Mostaan, and C. J. Palmer. 2023.

Review of Qualification and Modeling for Radiation-Induced Polymer Degradation.

Frontiers in Nuclear Engineering 2. https://doi.org/10.3389/fnuen.2023.1287370.

[71] IAEA. 2012. Assessing and Managing Cable Ageing in Nuclear Power Plants. International Atomic Energy Agency NP-T-3.6. Vienna, Austria.

https://www.iaea.org/publications/8753/assessing-and-managing-cable-ageing-in-nuclear-power-plants.

[72] Shimada, A. M. Sugimoto, H. Kudoh, K. Tamura, and T. Seguchi. 2014. Degradation Mechanisms of Silicone Rubber (Sir) by Accelerated Ageing for Cables of Nuclear Power Plant. IEEE Transactions on Dielectrics and Electrical Insulation 21(1): 16-23.

https://doi.org/10.1109/TDEI.2013.004177.

[73] Seguchi, T., K. Tamura, H. Kudoh, A. Shimada, and M. Sugimoto. 2015. Degradation of cable insulation material by accelerated thermal radiation combined ageing. IEEE Transactions on Dielectrics and Electrical Insulation 22(6): 3197-3206.

https://doi.org/10.1109/TDEI.2015.004880.

[74] Fifield, L. S., M. P. Spencer, Y. Ni, D. Li, M. R. Pallaka, T. T. Bisel, A. Zwoster, and M. K.

Murphy. 2020. Sequential Versus Simultaneous Aging of XLPE and EPDM Nuclear Cable Insulation Subjected to Elevated Temperature and Gamma Radiation (Final Results).

Pacific Northwest National Laboratory PNNL-30041 Rev. 1. Richland, WA.

https://lwrs.inl.gov/content/uploads/11/2024/03/Seq_vs_Sim_Aging_XLPE_EPDM_Nuclear

_Cable.pdf.

[75] F. Bortoletto, J. Gascon, M. Kranjcevic, B. Ruiz-Palenzuela, and A. Danyliuk, Mechanical and Chemical Degradation Assessment of Polymeric Cable Components Subjected to Different Accelerated Ageing Methods, in 11th International Conference on Insulated Power Cables (Jicable23), Lyon, France, June 18-22, 2023.

https://www.jicable.org/TOUT_JICABLE_FIRST_PAGE/2023/2023-B2-4_page1.pdf.

[76] IEEE 383-2003 (Revision of IEEE Std 383-1974). 2004. IEEE Standard for Qualifying Class 1E Electric Cables and Field Splices for Nuclear Power Generating Stations. IEEE Standards Association. https://doi.org/10.1109/IEEESTD.2004.94567.

[77] Fuse, N., H. Homma, and T. Okamoto. 2014. Remaining Issues of the Degradation Models of Polymeric Insulation Used in Nuclear Power Plant Safety Cables, IEEE Transactions on Dielectrics and Electrical Insulation 21(2): 571-581.

https://doi.org/10.1109/TDEI.2013.004086.

[78] Liu, Q., R. Dou, Y. Zhang, W. Huang, X. Meng, and H. Chen. 2024. Experimental and Simulation Studies of Degraded EPDM Composite in the Coupled Gamma Radiation-Thermal Environments. Polymer Degradation and Stability 227:110899.

https://doi.org/10.1016/j.polymdegradstab.2024.110899.

[79] Fifield, L. S., Y. Ni, D. Li, A. Sriraman, A. Guzman, A. Ortiz, M. P. Spencer, M. K. Murphy, and A. J. Zwoster. 2022. Inverse Temperature Effects in Nuclear Power Plant Electrical Cable Insulation. Pacific Northwest National Laboratory PNNL-33296. Richland, WA.

https://lwrs.inl.gov/content/uploads/11/2024/03/InverseTemperatureEffectsInNPP.pdf.

[80] Przybytniak, G., J. Boguski, V. Placek, L. Verardi, D. Fabiani, E. Linde, and U. W. Gedde.

2015. Inverse Effect in Simultaneous Thermal and Radiation Aging of EVA insulation.

Express Polymer Letters 9(4): 384-393. https://doi.org/10.3144/expresspolymlett.2015.36.

[81] Verardi, L., 2014. Aging of nuclear power plant cables: in search of non-destructive diagnostic quantities. Dissertation thesis, Alma Mater Studiorum Universit di Bologna.

Dottorato di ricerca in Ingegneria elettrotecnica, 26 Ciclo. Universit di Bologna.

https://doi.org/10.6092/unibo/amsdottorato/6246.

[82] Gillen, K. T. and R. Bernstein, Review of Nuclear Power Plant Safety Cable Aging Studies with Recommendations for Improved Approaches and for Future Work. Sandia National Laboratories SAND 2010-7266. Albuquerque, NM. https://doi.org/10.2172/1002106.

References 42

[83] EPRI. 2023. Condition-Based Qualification of Class 1E Cables. Electric Power Research Institute 3002026361. Palo Alto, CA.

https://www.epri.com/research/programs/065756/results/3002026361.

[84] Burany, S., D. Rouison, R. Burany, and J. Owens. 2023. Radiation Accident Dose and Simulated Loss-of-Coolant Accident Test of Low Voltage Cables. Nuclear Regulatory Commission NUREG/CR-7300. Washington, D.C.

https://www.nrc.gov/docs/ML2323/ML23237B247.pdf.

[85] Jacobus, M. J. 1992. Aging, Condition Monitoring, and Loss-Of-Coolant Accident (LOCA)

Tests of Class 1E Electrical Cables. Volume 1, Crosslinked Polyolefin Cables. Nuclear Regulatory Commission NUREG/CR-5772-Vol.1. SAND-91-1766/1. Washington, D. C.

https://www.osti.gov/biblio/10177143.

[86] Jacobus, M. J. 1992. Aging, Condition Monitoring, and Loss-Of-Coolant Accident (LOCA)

Tests of Class 1E Electrical Cables. Volume 2, Ethylene Propylene Rubber Cables.

Nuclear Regulatory Commission NUREG/CR-5772-Vol.2. SAND-91-1766/2. Washington, D.C. https://www.osti.gov/biblio/10114126.

[87] Jacobus, M. J. 1992. Aging, Condition Monitoring, and Loss-Of-Coolant Accident (LOCA)

Tests of Class 1E Electrical Cables. Volume 3, Miscellaneous Cable Types. Nuclear Regulatory Commission NUREG/CR-5772-Vol.3. SAND-91-1766/3. Washington, D.C.

https://www.osti.gov/biblio/10114105.

[88] Spaang, K. 1997. Aging of Electrical Components in Nuclear Power Plants. Relationships Between Mechanical and Chemical Degradation After Artificial Aging and Dielectric Behaviour During LOCA. Swedish Nuclear Power Inspectorate SKI-R-97-40. Stockholm, Sweden.

https://www.stralsakerhetsmyndigheten.se/contentassets/454789e354b24f95a75ffa6126b0 6377/199740-aging-of-electrical-components-in-nuclear-power-plants.

[89] Lofaro, R., E. Grove, M. Villaran, P. Soo, and F. Hsu. 2001. Assessment of Environmental Qualification Practices and Condition Monitoring Techniques for Low-Voltage Electric Cables: LOCA Test Results. Nuclear Regulatory Commission NUREG/CR-6704 (Vol.1)

BNL-NUREG-52610. Washington, D.C. https://doi.org/10.2172/1329393.

[90] NRC. 2007. Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients. Nuclear Regulatory Commission GL-07-01.

Washington, D.C. https://www.nrc.gov/reading-rm/doc-collections/gen-comm/gen-letters/2007/index.html.

[91] Brown, J., R. Bernstein, G. V. White, II, S. F, Glover, J. C. Neely, G. Pena, K. M.

Williamson, F. J. Zutavern, F. Gelbard. 2015. Submerged Medium Voltage Cable Systems at Nuclear Power Plants: A Review of Research Efforts Relevant to Aging Mechanisms and Condition Monitoring. Sandia National Laboratories SAND-2015-1794. Albuquerque, NM. https://doi.org/10.2172/1177756.

[92] Energetics Incorporated. 2008. Life Beyond 60 Workshop Summary Report. NRC/DOE Workshop U.S. Nuclear Power Plant Life Extension Research and Development.

Bethesda, MD. February 19-21, 2008.

https://lwrs.inl.gov/content/uploads/11/2024/04/Life_Beyond60_Report.pdf.

[93] NRC. 2010. Submerged Electrical Cables. Nuclear Regulatory Commission Information Notice IN 2010-26. Washington, D.C.

https://www.nrc.gov/docs/ML1028/ML102800456.pdf.

[94] NRC. 2002. Submerged Safety-Related Electrical Cables. Nuclear Regulatory Commission Information Notice IN 2002-12. Washington, D.C.

https://www.nrc.gov/docs/ML0207/ML020790238.pdf.

[95] EPRI. 2007. Plant Support Engineering: Failure Mechanism Assessment of Medium Voltage Ethylene Propylene Rubber Cables. Electric Power Research Institute 1015070.

Palo Alto, CA. https://www.epri.com/research/products/1015070.

References 43

[96] EPRI. 2009. Plant Support Engineering: Failure Mechanism Assessment of Medium-Voltage Ethylene Propylene Rubber Cables - Revision 1. Electric Power Research Institute 1018777. Palo Alto, CA. https://www.epri.com/research/products/1018777.

[97] EPRI. 2011. Plant Support Engineering: Medium-Voltage Cable Failure Mechanism, Update 2. Electric Power Research Institute 1021069. Palo Alto, CA.

https://www.epri.com/research/products/1021069.

[98] EPRI. 2011. Plant Engineering: Medium Voltage Cable Failure Mechanism Update 3.

Electric Power Research Institute 1022965. Palo Alto, CA.

https://www.epri.com/research/products/1022965.

[99] EPRI. 2012. Plant Engineering: Medium-Voltage Cable Failure Mechanism Research, Update 4. Electric Power Research Institute 1024894. Palo Alto, CA.

https://www.epri.com/research/products/1024894.

[100] EPRI. 2013. Plant Engineering: Medium-Voltage Cable Failure Mechanism Research, Update 5. Electric Power Research Institute 3002000554. Palo Alto, CA.

https://www.epri.com/research/products/3002000554.

[101] EPRI. 2014. Plant Engineering: Medium-Voltage Cable Failure Mechanism Research, Update 6. Electric Power Research Institute 3002002993. Palo Alto, CA.

https://www.epri.com/research/products/3002002993.

[102] EPRI. 2015. Plant Engineering: Medium-Voltage Cable Failure Mechanism, Update 7:

Evaluation of Main Factors Causing Formation of Large Water Trees in Service-Aged, Pink and Brown Ethylene Propylene Rubber-Insulated Medium-Voltage Cables. Electric Power Research Institute 3002005323. Palo Alto, CA.

https://www.epri.com/research/products/3002005323.

[103] EPRI. 2016. Plant Engineering: Low-Voltage Cable Susceptibility to Wet Aging. Electric Power Research Institute 3002007991. Palo Alto, CA.

https://www.epri.com/research/products/3002007991.

[104] Hinderliter, B., M. Maurer-Jones, and R. Duckworth. 2021 Quantifying Properties for a Mechanistic, Predictive Understanding of Aqueous Impact on Aging of Medium and Low Voltage AC and DC Cabling in Nuclear Power Plants. University of Minnesota - Duluth, Oak Ridge National Laboratory DOE-UMDORNL-NE0008540.

https://www.osti.gov/biblio/1774077.

[105] EPRI. 2010. Medium Voltage Cable Aging Management Guide, Revision 1. Electric Power Research Institute 1021070. Palo Alto, CA.

https://www.epri.com/research/products/1021070.

[106] EPRI. 2012. Plant Engineering: Evaluation and Insights from Nuclear Power Plant Tan Delta Testing and Data Analysis. Electric Power Research Institute 1025262. Palo Alto, CA. https://www.epri.com/research/products/1025262.

[107] EPRI. 2015. Plant Engineering: Evaluation and Insights from Nuclear Power Plant Tan Delta Testing and Data Analysis - Update. Electrical Power Research Institute 3002005321. Palo Alto, CA. https://www.epri.com/research/products/3002005321.

[108] EPRI. 2013. Plant Engineering: Aging Management Program Guidance for Medium-Voltage Cable Systems for Nuclear Power Plants, Revision 1. Electrical Power Research Institute 3002000557. Palo Alto, CA. https://www.epri.com/research/products/3002000557.

[109] Glass, S. W., L. Fifield, A. Holmes, and K. Anderson. 2020. Assessment of EPRIs Tan Delta Approach to Manage Cables in Submerged Environments: Statistical Review of EPRI Data. Pacific Northwest National Laboratory PNNL-28542 Rev.1. Richland, WA.

https://doi.org/10.2172/1713064.

[110] NRC. 2022. Assessment of EPRIs Tan Delta Approach to Manage Cables in Submerged Environments: Statistical Review of EPRI Data. Nuclear Regulatory Commission RIL 2021-11. Washington, D.C. https://www.nrc.gov/docs/ML2201/ML22019A007.pdf.

References 44

[111] 10 CFR Part 54. 2025. Part 54Requirements for Renewal of Operating Licenses for Nuclear Power Plants. Code of Federal Regulations. https://www.ecfr.gov/current/title-10/part-54.

[112] IEEE 383-2015. 2015. IEEE Standard for Qualifying Electric Cables and Splices for Nuclear Facilities. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.2015.7287711.

[113] NRC. 1984. Environmental Qualification of Certain Electric Equipment Important to Safety for Nuclear Power Plants. Nuclear Regulatory Commission RG-1.89 R1. Washington, D.C.

https://www.nrc.gov/docs/ML0313/ML031320126.pdf.

[114] NRC.1977. Qualification Tests of Electric Cables, Field Splices, and Connections for Light-Water-Cooled Nuclear Power Plants. Nuclear Regulatory Commission RG-1.131.

Washington, D.C. https://www.nrc.gov/docs/ml0037/ML003740128.pdf.

[115] IEEE 323-1971. 1971. IEEE Trial-Use Standard: General Guide for Qualifying Class I Electric Equipment for Nuclear Power Generating Stations. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.1971.6529090.

[116] IEEE 323-1983. 1983. IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.1983.82408.

[117] IEEE 323-2003. 2004. IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.2004.94415.

[118] IEC/IEEE 60780-323-2016. 2016. IEC/IEEE International Standard - Nuclear facilities -

Electrical equipment important to safety - Qualification. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.2016.7425113.

[119] IEEE 383-2023. 2023. IEEE Standard for Qualifying Electric Cables and Splices for Nuclear Facilities. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.2023.10371251.

[120] IEEE 98-2002. 2002. IEEE Standard for the Preparation of Test Procedures for the Thermal Evaluation of Solid Electrical Insulating Materials. IEEE Standards Association.

https://doi.org/10.1109/IEEESTD.2002.93617.

[121] IEEE 1-2000. 2001. IEEE Recommended Practice - General Principles for Temperature Limits in the Rating of Electrical Equipment and for the Evaluation of Electrical Insulation.

IEEE Standards Association. https://doi.org/10.1109/IEEESTD.2001.92768.

[122] IEEE 101-1987 (R2010). 1988. IEEE Guide for the Statistical Analysis of Thermal Life Test Data. IEEE Standards Association. https://doi.org/10.1109/IEEESTD.1988.7473795.

[123] EPRI. 2017. Low-Voltage and Instrumentation and Control Cable Aging Management Guide, Revision 1. Electric Power Research Institute 3002010641. Palo Alto, CA.

https://www.epri.com/research/products/3002010641.

[124] Spencer, M. P., Y. Ni, and L. S. Fifield. 2024. First Phase Consensus Roadmap for Development of Condition-Based Cable Reliability Assurance. Pacific Northwest National Laboratory PNNL-36630. Richland, WA. https://doi.org/10.2172/2478702.

[125] Hashemian, H., A. Deatherage, and C. Sexton. 2023. Breakthrough Development in Aging Management of I&C Cables. NuclearNews. July 2023. 34-39.

https://www.ans.org/pubs/magazines/nn/year-2023/month-7/.

[126] EPRI. 2017. Long-Term Operations: Initial Findings on Use of Dielectric Spectroscopy for Condition Monitoring of Low Voltage Nuclear Power Plant Cables. Electric Power Research Institute 3002010403. Palo Alto, CA.

https://www.epri.com/research/products/3002010403.

[127] Clough, R. L. and K. T. Gillen. 1989. Radiation-Oxidation of Polymers. Sandia National Laboratories SAND-89-1756C. Albuquerque, NM. https://www.osti.gov/biblio/6050016.

References 45

[128] Gillen, K. T. and R. L. Clough. 1989. Time-Temperature-Dose Rate Superposition: a Methodology for Extrapolating Accelerated Radiation Aging Data to Low Dose Rate Conditions. Polymer Degradation and Stability 24(2): 137-168.

https://doi.org/10.1016/0141-3910(89)90108-0.

[129] Shaw, M.T. 1997. Natural versus Artificial Aging of Electrical Components: Interim Report 1991-1995, Electric Power Research Institute TR-106845. Palo Alto, CA.

[130] Spng, K. 1993. Methodology for Artificial Aging of Electrical Components in Nuclear Power Plants: Results of Experimental Studies. Swedish Nuclear Power Inspectorate SKI TR 93:39. Stockholm, Sweden.

[131] Gillen, K.T., J. Wise, and R. L. Clough. 1993. Novel Techniques Applied to Polymer Lifetime Predictions. Sandia National Laboratories SAND-93-1457C. Albuquerque, NM.

https://www.osti.gov/biblio/10113498.

[132] Celina, M. and G. A. George. 1995. Heterogeneous and Homogeneous Kinetic Analyses of the Thermal Oxidation of polypropylene. Polymer Degradation and Stability 50(1): 89-99, 1995. https://doi.org/10.1016/0141-3910(95)00136-A.

[133] Wise, J. K. T. Gillen, and R. L. Clough. 1995. An Ultrasensitive Technique for Testing the Arrhenius Extrapolation Assumption for Thermally Aged Elastomers. Polymer Degradation and Stability 49(3): 403-418. https://doi.org/10.1016/0141-3910(95)00137-B.

[134] Gazdzinski, R. F., W. M. Denny, G. J. Toman, and R. T. Butwin. 1996. Aging Management Guideline for Commercial Nuclear Power Plants - Electrical Cable and Terminations.

Sandia National Laboratories SAND96-0344. Albuquerque, NM.

https://www.nrc.gov/docs/ML0311/ML031140264.pdf.

[135] Villaran, M., B. Lee, and R. Lofaro. 1996. Environmental Qualification of Electric Equipment Used in Commercial Nuclear Power Plants. Preaging and LOCA Test Plan for Low-Voltage Electric Cables. Brookhaven National Laboratory TR-6168/69-04-95. Upton, NY. https://www.nrc.gov/docs/ML2009/ML20097F189.pdf.

[136] Subudhi, M. 1996. Literature Review of Environmental Qualification of Safety-Related Electric Cables. Summary of Past Work. Brookhaven National Laboratory NUREG/CR-6384 BNL-NUREG-52480 Vol.1. Upton, NY.

https://www.nrc.gov/docs/ML2010/ML20108E669.pdf.

[137] Gillen, K. T., M. Celina, R. L. Clough, and J. Wise. 1997. Extrapolation of Accelerated Aging Data-Arrhenius or Erroneous? Trends in Polymer Science 8(5): 250-257.

[138] Doyle, T. E., L. R. Mason, and B. A. Reynolds. 1997. Oxidation Induction Time (OIT) technology for electric cable condition monitoring and life assessment. Final report.

Pacific-Sierra Research Corporation DOE/ER/82249-2. Arlington, VA.

https://www.osti.gov/biblio/808456.

[139] Gillen, K. T. and R. L. Clough. 1997. Prediction of Elastomer Lifetimes from Accelerated Thermal-Aging Experiments. Elastomer-Service Life Prediction Symposium, Akron, OH, August 14-15, 1997. https://www.osti.gov/biblio/522769.

[140] Gillen, K. T., J. Wise, M. Celina, and R. L. Clough. 1997. Evidence That Arrhenius High-Temperature Aging Behavior for an EPDM O-Ring Does Not Extrapolate to Lower Temperatures. Sandia National Laboratories SAND-97-2181C. Albuquerque, NM.

https://www.osti.gov/servlets/purl/634046.

[141] Celina, M., J. Wise, D. K. Ottesen, K. T. Gillen, and R. L. Clough. 1998. Oxidation Profiles of Thermally Aged Nitrile Rubber. Polymer Degradation and Stability 60(2): 493-504.

https://doi.org/10.1016/S0141-3910(97)00113-4.

[142] Gillen, K. T., M. Celina, and R. L. Clough. 1998. Limitations of the Arrhenius methodology.

Sandia National Laboratories SAND98-1726C. Albuquerque, NM.

https://www.osti.gov/servlets/purl/1535.

[143] Gillen, K.T., M. R. Keenan, and J. Wise. 1998. New Method for Predicting Lifetime of Seals from CompressionStress Relaxation Experiments. Die Angewandte

References 46 Makromolekulare Chemie 261-262(1): 83-92. https://doi.org/10.1002/(SICI)1522-9505(19981201)261-262:1%3C83::AID-APMC83%3E3.0.CO;2-%23.

[144] IAEA. 2000. Assessment and Management of Ageing of Major Nuclear Power Plant Components Important to Safety: In-Containment Instrumentation and Control Cables, Volume II, International Atomic Energy Agency IAEA-TECDOC-1188 Vol 2. Vienna, Austria. https://www-pub.iaea.org/MTCD/Publications/PDF/te_1188v2_prn.pdf.

[145] Gillen, K. T., M. Celina, and R. Bernstein. 2004. Review of the Ultrasensitive Oxygen Consumption Method for Making More Reliable Extrapolated Predictions of Polymer Lifetimes. Society of Plastics Engineers Annual Technical Conference, Chicago, IL, May 16-20, 2004. https://www.4spe.org/i4a/doclibrary/getfile.cfm?doc_id=9250.

[146] Celina, M., and K. T. Gillen. 2005. Oxygen Permeability Measurements on Elastomers at Temperatures up to 225 °C. Macromolecules 38(7): 2754-2763.

https://doi.org/10.1021/ma0487913.

[147] Colin, X., A. Mavel, C. Marais, and J. Verdu. 2005. Interaction between Cracking and Oxidation in Organic Matrix Composites. Journal of Composite Materials 39(15) 1371-1389. https://doi.org/10.1177/0021998305050430.

[148] Kim, J.-S. 2005. Evaluation of Cable Aging Degradation Based on Plant Operating Condition. Journal of Nuclear Science and Technology 42(8): 745-753.

https://doi.org/10.1080/18811248.2004.9726444.

[149] Buslik, A. J., T. L. Chu, J. R. Lehner, and M. Subudhi. 2005. A Reliability Physics Model for Aging of Cable Insulation Materials. Brookhaven National Lab NUREG/CR-6869, BNL-NUREG-73676-2005. Upton, NY. https://www.nrc.gov/docs/ML0509/ML050940065.pdf.

[150] V. Plaek. 2005. Assessment of Parameters for Simulation of Thermal Ageing of Materials in Nuclear Power Plants Using DSC, Journal of Thermal Analysis and Calorimetry 80(2) 525-528. https://doi.org/10.1007/s10973-005-0688-4.

[151] Lim, B.-J., C.-D. Park, and C.-S. Song. 2006. Aging Assessment of Cable for NPP. In Proceedings of the International Conference Nuclear Energy for New Europe 2006.

Nuclear Society of Slovenia, Portoroz, Slovenia, September 18-21, 2006.

https://arhiv.djs.si/proc/port2006/pdf/0204.pdf.

[152] Rogovin, D. and R. Lofaro. 2006. Evaluation of the Broadband Impedance Spectroscopy Prognostic/Diagnostic Technique for Electric Cables Used in Nuclear Power Plants. The Boeing Company and Brookhaven National Laboratory NUREG/CR-6904, BNL-NUREG-75208-2005. Upton, NY. http://www.nrc.gov/reading-rm/doc-collections/nuregs/contract/cr6904/cr6904.pdf.

[153] Anandakumaran, K. 2007. Aging and Condition Monitoring Studies of Composite Insulation Cables Used in Nuclear Power Plants. IEEE Transactions on Dielectrics and Electrical Insulation 14(1): 227-237. https://doi.org/10.1109/TDEI.2007.302891.

[154] Bánhegyi, G., V. Vargha, P. Müller, and E. Zelenyánszki. 2009. Estimation of Thermal Acceleration Factors of Ageing Epoxy Insulation Using Thermogravimetry and Intuitive Kinetic Model, IEEE Transactions on Dielectrics and Electrical Insulation 16(5): 1420-1429. https://doi.org/10.1109/TDEI.2009.5293956.

[155] Coats, D., J. Wang, and Y.-J. Shin. 2011. Joint Time-Frequency Domain Reflectometry for Diagnostics/Prognostics of Aging Electric Cables in Nuclear Power Plants. University of South Carolina, ML120260654. Columbia, SC.

https://www.nrc.gov/docs/ml1202/ml120260654.pdf.

[156] Seguchi, T., K. Tamura, T. Ohshima, A. Shimada, and H. Kudoh. 2011. Degradation Mechanisms of Cable Insulation Materials During Radiation-Thermal Ageing in Radiation Environment, Radiation Physics and Chemistry 80(2): 268-273.

https://doi.org/10.1016/j.radphyschem.2010.07.045.

[157] Ohki, Y., N. Hirai, T. Yamamoto, T. Minakawa, and T. Okamoto. 2012. Improvement of Inspection and Maintenance Procedures of Polymeric Cable Insulation Used in Nuclear

References 47 Power Plants in Japan. In 44th International Conference on Large High Voltage Electric Systems 2012, Paris, France, August 26 - 31, 2012.

https://waseda.elsevierpure.com/en/publications/improvement-of-inspection-and-maintenance-procedures-of-polymeric.

[158] EPRI. 2015. Methodology and Installation of Radiation and Temperature Monitors:

Research for Installed Cables at U.S. Nuclear Power Plants in Support of Long-Term Operations. Electric Power Research Institute 3002005517. Palo Alto, CA.

https://www.epri.com/research/products/3002005517.

[159] IAEA. 2017. Benchmark Analysis for Condition Monitoring Test Techniques of Aged Low Voltage Cables in Nuclear Power Plants. International Atomic Energy Agency IAEA-TECDOC-1825. Vienna, Austria. https://www.iaea.org/publications/11164/benchmark-analysis-for-condition-monitoring-test-techniques-of-aged-low-voltage-cables-in-nuclear-power-plants.

[160] Chang, Y.-S. 2017. Predictive Model of the Degradation of Cable Insulation Subject to Heat and Radiation. PhD dissertation, Department of Materials Science and Engineering, University of California, Los Angeles.

https://www.iapsam.org/psam14/proceedings/paper/paper_312_1.pdf.

[161] Zhang, Z., P. D. S. Assala, and L. Wu. 2018. Residual Life Assessment of 110 kV XLPE Cable. Electric Power Systems Research 163(B): 572-580.

https://doi.org/10.1016/j.epsr.2017.12.027.

[162] Gillen, K. T., and M. Celina. 2018. Predicting Polymer Degradation and Mechanical Property Changes for Combined Radiation-Thermal Aging Environments. Rubber Chemistry and Technology 91(1): 27-63. https://doi.org/10.5254/rct.18.81679.

[163] Ji, G. H., Y. H. Lee, H. Lim, J. Ahn, and Y.-J. Shin. 2023. Aging Monitoring of I&C Cable in Nuclear Power Plant via Parameter Estimation of Time-Frequency Domain Reflectometry. 11th International Conference on Insulated Power Cables (Jicable23),

Lyon, France, June 18-22, 2023.

https://www.jicable.org/TOUT_JICABLE_FIRST_PAGE/2023/2023-E7-4_page1.pdf.

[164] Denny, B. and A. Kononenko, Kinetics of Thermal and Radiation Aging and Prediction of PVC Cable Service Life, Research Institute of Scientific Instruments.

Appendix 48 7.0 Appendix Table 4. Activation energy (Ea) values reported in literature.

Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

96.30 43 to 110 PVC EAB e/e0=0.4, dose rate 0.1-100 Gy/h

[127]

87.92 70 to 140 Neoprene EAB

[128]

121.56 115 EPR EAB in-plant aged

[129]

145.68 115 Silicone EAB in-plant aged 128.32 132 XLPO EAB in-plant aged 92.62 132 Viton EAB in-plant aged 115.78 132 Viton EAB in-plant aged 109.50 132 EPR EAB in-plant aged 88.76 132 Nitrile EAB in-plant aged 89.73 80 to 142 CSPE Indenter

[130]

98.02 80 to 142 CSPE EAB 98.51 80 to 142 EPDM Indenter 84.52 80 to 142 EPDM IR 147.04 80 to 142 EPDM DF 60 Hz 101.11 80 to 142 EPDM DF 1 kHz 101.11 80 to 142 EPDM Indenter 96.96 80 to 142 EPDM EAB 137.48 80 to 142 EPDM IR 150.51 80 to 142 EPDM DF 1 kHz 105.55 80 to 142 CSPE Indenter 98.02 80 to 142 CSPE EAB 107.96 80 to 142 XLPO/XLPE Indenter 90.50 80 to 142 XLPO/XLPE IR 27.59 80 to 142 XLPO/XLPE DF 60 Hz 79.31 80 to 142 FPM Indenter 86.45 80 to 142 FPM EAB 111.14 80 to 142 EPDM Indenter 106.80 80 to 142 EPDM EAB 92.00 64.5 to 125 Nitrile surface modulus

[131]

149.00 110 to 150 PP CL induction time CL:

chemiluminescence

[132]

113.00 110 to 150 PP CL time to maximum 120.00 110 to 150 PP CL oxidation time time to max -

induction time 83.74 8.4 23 to 96 Nitrile O2 consumption

[133]

87.92 8.4 23 to 96 Nitrile O2 consumption 121.42 8.4 52 to 96 Nitrile CO2 production 91.27 8.4 64.5 to 125 Nitrile EAB 92.11 8.4 64.5 to 125 Nitrile surface modulus 90.43 8.4 23 to 125 Neoprene O2 consumption 90.43 8.4 71.5 to 125 Neoprene CO2 production 90.02 8.4 120.6 to 149.4 Neoprene EAB 92.11 8.4 100.1 to 149.4 Neoprene surface modulus 94.20 8.4 111 to 125 Neoprene O2 consumption induction time 109.99 80 CSPE EAB e=0.5

[134]

Appendix 49 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

130.25 91 EPDM EAB e/e0=0.6

[134]

Cont.

115.78 135 EPR EAB e=0.5 91.66 148 ETFE EAB e=0.5 90.69 80 Neoprene EAB e=0.5 95.52 120 PVC electrical failure 173.66 136 Silicone EAB e/e0=0.5 112.88 200 Viton EAB e=0.5 119.64 150 XLPE/XLPO EAB e/e0=0.6 119.64 150 XLPE

[135]

96.48 150 Neoprene 106.13 98 EPR 100.34 98 CSPE 110.95 98 EPDM 119.64 98 CSPE 113.85 150 EPR 87.92 45 XLPE

[136]

87.92 45 CSPE 104.67 45 CSPE 100.48 45 CSPE 87.92 45 ETFE 96.30 45 PVC 87.92 45 Silicone 66.99 45 PE 87.92 45 Neoprene 84.00 23 to 96 Nitrile O2 consumption

[137]

92.00 64.5 to 125 Nitrile EAB, surface modulus 113.00 111 to 170 EPR EAB, surface modulus 67.00 52 to 111 EPR O2 consumption 190.07 215 XLPE OIT

[138]

181.38 215 XLPE OIT 199.71 215 XLPE OIT 157.26 225 XLPE OIT 157.26 225 XLPE OIT 161.12 225 XLPE OIT 101.30 200 XLPE OIT 138.93 200 XLPE OIT 166.91 200 XLPE OIT 176.56 210 EPR OIT 181.38 185 EPR OIT 130.25 170 EPR OIT 142.79 170 EPR OIT 140.86 170 EPR OIT 164.02 220 EPR OIT 158.23 220 EPR OIT 76.22 65 to 85 CSPE microcalorimetry heat flow unaged

[88]

101.30 65 to 85 CSPE microcalorimetry heat flow aged 95°C, 384 days 91.66 65 to 85 CSPE microcalorimetry heat flow aged 142°C, 48 days 84.90 65 to 85 CSPE microcalorimetry heat flow LOCA-aged

Appendix 50 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

79.11 65 to 85 EPDM microcalorimetry heat flow unaged

[88]

Cont.

96.48 65 to 85 EPDM microcalorimetry heat flow aged 142°C, 48 days 77.18 65 to 85 XLPE microcalorimetry heat flow unaged 91.66 65 to 85 XLPE microcalorimetry heat flow aged 142°C, 48 days 90.00 23 to 120 Nitrile O2 consumption, EAB, surface modulus

[139]

118.00 111 to 160 EPDM O2 consumption, EAB, surface modulus, force decay, density 82.00 52 to 111 EPDM O2 consumption 118.00 111 to 160 EPDM O2 consumption, EAB, surface modulus, force decay, density

[140]

82.00 52 to 111 EPDM O2 consumption 125.00 100 to 140 Nitrile IR-carbonyl Unfilled NBR

[141]

124.00 100 to 140 Nitrile Edge modulus Unfilled NBR 134.00 100 to 140 Nitrile O consumption Unfilled NBR 179.00 100 to 140 Nitrile CO formation Unfilled NBR 158.00 100 to 140 Nitrile CO formation Unfilled NBR 92.00 100 to 140 Nitrile Elongation, Edge modulus Carbon-black-filled NBR 88.00 100 to 140 Nitrile O consumption Carbon-black-filled NBR 120.00 100 to 140 Nitrile CO formation, CO formation Carbon-black-filled NBR 90.00 64.5 to 125 Nitrile EAB

[142]

118.00 111 to 160 EPDM O2 consumption, EAB, surface modulus, force decay, density 82.00 52 to 111 EPDM O2 consumption 84.00 80 to 125 Butyl Compression stress relaxation

[143]

76.00 80 to 120 EPDM O2 consumption, CO2 formation

[144]

58.00 35 to 140 EPR CL intensity 113.46 EPR/CSPE from qualification report AIW

[89]

113.46 EPR/CSPE from qualification report Anaconda 138.95 EPR/CSPE from qualification report Okonite 131.22 EPDM/CSPE from qualification report Samuel Moore 128.34 XLPE/Neoprene from qualification report Rockbestos 88.00 64.5 to 125 Nitrile EAB, O2 consumption

[145]

101.50 80 to 111.5 Butyl Force decay, O2 consumption

Appendix 51 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

75.00 25 to 80 Butyl O2 consumption

[145]

Cont.

110.00 91 to 170 XLPO EAB

[32]

98.00 80 to 110 Neoprene EAB 107.00 100 to 150 CSPE EAB 112.00 109 to 138 CPE EAB 106.00 100.9 to 170 EPR EAB 100.00 52 to 139 EPR EAB within induction period, O2 consumption 128.00 99 to 139 EPR EAB induction time 106.00 109 to 160 EPR EAB 88.00 99 to 138 EPR EAB 76.00 99 to 109 XLPO EAB 130.00 124 to 151 XLPO EAB 96.00 80 to 110 Neoprene EAB, O2 consumption 76.00 25 to 80 Neoprene O2 consumption 72.00 48 to 138 XLPO EAB, O2 consumption 119.00 80 to 120 PU thermal degradation, from reference

[31]

65.00 20 to 50 PU thermal degradation, from reference 127.00 130 to 160 EPDM from reference 78.00 50 to 120 EPDM from reference 100.00 60 to 110 Butyl from reference 60.00 25 to 50 Butyl from reference 107.00 100 to 155 PP from reference 41.00 40 to 70 PP from reference 156.00 100 to 130 PP from reference 36.00 50 to 80 PP from reference 121.00 100 to 140 PP from reference 49.00 40 to 70 PP from reference 146.00 85 to 105 PP from reference 41.00 35 to 60 PP from reference 218.00 150 XLPE 144.00 to 150 XLPE 115.00 110 EPDM 75.00 to 110 EPDM 120.00 70 PU 70.00 to 70 PU 100.00 80 Butyl 75.00 to 80 Butyl 89.00 70 Neoprene 71.00 to 70 Neoprene 102.00 100 CSPE 31.40 25 to 50 EPDM O2 permeability

[146]

18.90 140 to 175 EPDM O2 permeability 56.20 25 to 50 Viton O2 permeability 17.40 175 to 220 Viton O2 permeability 37.80 25 to 50 Neoprene O2 permeability 25.60 95 to 125 Neoprene O2 permeability 26.90 25 to 50 PU O2 permeability

Appendix 52 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

13.70 85 to 115 PU O2 permeability

[146]

Cont.

54.10 25 to 40 butyl O2 permeability 30.30 85 to 105 butyl O2 permeability 42.50 25 to 50 nitrile O2 permeability 21.60 86 to 125 nitrile O2 permeability

-32.00 150 to 240 Epoxy TOL F655-2, TOL=thickness of oxidation layer

[147]

16.00 150 to 240 Epoxy O2 diffusion F655-2 80.00 150 to 240 Epoxy O2 consumption F655-2

-30.00 150 to 240 Epoxy TOL 977-2 18.00 150 to 240 Epoxy O2 diffusion 977-2 78.00 150 to 240 Epoxy O2 consumption 977-2

-23.00 150 to 240 CF/epoxy TOL, direction 1 T800H/F655-2

-14.00 150 to 240 CF/epoxy TOL, direction 2 or 3 T800H/F655-2 35.00 150 to 240 CF/epoxy O2 diffusion, direction 1

T800H/F655-2 53.00 150 to 240 CF/epoxy O2 diffusion, direction 2 or 3 T800H/F655-2

-38.00 150 to 240 CF/epoxy TOL, direction 1 IM7/977-2

-14.00 150 to 240 CF/epoxy TOL, direction 2 or 3 IM7/977-2 3.00 150 to 240 CF/epoxy O2 diffusion, direction 1

IM7/977-2 50.00 150 to 240 CF/epoxy O2 diffusion, direction 2 or 3 IM7/977-2 90.00 150 to 240 Epoxy Crack propagation IM7/977-2 94.39 130 Neoprene TGA

[148]

88.00 CSPE EAB, from reference

[149]

105.00 CSPE EAB, from reference 88.00 Silicone EAB, from reference 109.69 XLPO EAB, from reference 87.92 XLPO EAB, from reference 88.00 ETFE EAB, from reference 88.00 EPR EAB, from reference 92.04 Neoprene EAB, from reference 117.71 EPDM EAB, from reference 129.00 unaged PVC OIT 1-15K/min

[150]

128.00 unaged PVC OIT 180-250°C 111.00 120 to 180 PVC OIT 50% decrease 114.00 120 to 180 PVC EAB 50% decrease 107.00 120 to 180 PVC TS 50% decrease 103.00 120 to 180 PVC Stiffness 50% decrease 113.00 120 to 180 PVC color 50% decrease 123.00 unaged XLPE OIT 1-15K/min 123.00 unaged XLPE OIT 180-250°C 97.00 120 to 180 XLPE OIT 50% decrease 104.00 120 to 180 XLPE EAB 50% decrease 119.00 120 to 180 XLPE Stiffness 50% decrease 130.00 120 to 180 XLPE color 50% decrease 125.00 unaged PVC OIT 1-15K/min 116.00 120 to 180 PVC OIT 50% decrease 104.00 120 to 180 PVC EAB 50% decrease

Appendix 53 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

119.00 120 to 180 PVC Stiffness 50% decrease

[150]

Cont.

146.00 120 to 180 PVC color 50% decrease 114.00 unaged PVC OIT 1-15K/min 121.00 120 to 180 PVC OIT 50% decrease 116.00 120 to 180 PVC Stiffness 50% decrease 154.00 unaged XLPE OIT 1-15K/min 151.00 unaged XLPE OIT 180-250°C 82.00 120 to 180 XLPE OIT 50% decrease 81.00 120 to 180 XLPE color 50% decrease 164.00 120 XLPE OIT 1-15K/min 119.00 120 to 180 XLPE OIT 50% decrease 127.00 120 to 180 XLPE Stiffness 50% decrease 113.00 120 to 180 XLPE color 50% decrease 124.00 unaged XLPE OIT 1-15K/min 76.00 120 to 180 XLPE OIT 50% decrease 152.00 120 to 180 XLPE Stiffness 50% decrease 109.00 unaged PVC OIT 1-15K/min 130.00 unaged PVC OIT 180-250°C 104.00 120 to 180 PVC OIT 50% decrease 90.00 120 to 180 PVC Stiffness 50% decrease 91.00 120 to 180 PVC OIT 50% decrease 117.00 120 to 180 PVC Stiffness 50% decrease 109.00 120 to 180 PVC color 50% decrease 95.00 120 to 180 PVC OIT 50% decrease 103.00 120 to 180 PVC Stiffness 50% decrease 119.00 120 to 180 PVC color 50% decrease 125.00 120 to 180 PVC OIT 50% decrease 105.00 120 to 180 PVC Stiffness 50% decrease 115.00 120 to 180 PVC color 50% decrease 96.00 unaged PVC OIT 1-15K/min 118.00 unaged PVC OIT 180-250°C 113.00 120 to 180 PVC EAB 50% decrease 113.00 120 to 180 PVC TS 50% decrease 139.00 120 to 180 PVC OIT 50% decrease 115.00 120 to 180 PVC EAB 50% decrease 107.00 120 to 180 PVC TS 50% decrease 103.00 120 to 180 PVC Stiffness 50% decrease 217.10 20 unaged PVC TGA 1-15K/min

[28]

192.80 19 unaged PVC TGA 1-15K/min 174.60 17 unaged PVC TGA 1-15K/min 106.13 140 to 170 EPR EAB

[151]

124.46 unaged EPR TGA 5-20°C/min 84.90 LOCA EPR TGA 5-20°C/min 128.32 XLPE from qualification report

[152]

104.20 110 to 120 Hypalon EAB

[153]

109.50 110 to 120 EPR/CSPE EAB, IM 104.20 110 to 120 CSPE IM 109.50 110 to 120 Kerite EAB, IM 87.00 27 Epoxy resin from reference

[154]

115.00 66 Epoxy from reference

Appendix 54 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

141.00 55 Epoxy-glass from reference

[154]

Cont.

104.00 10 unaged Epoxy, BPA TGA, 200-350°C degradation stage 1 72.00 10 unaged Epoxy, BPA TGA, 200-350°C degradation stage 2 85.00 12 irradiated 135 kGy Epoxy, BPA TGA, 200-350°C degradation stage 1 77.00 21 irradiated 135 kGy Epoxy, BPA TGA, 200-350°C degradation stage 2 90.00 12 unaged

Epoxy, Cycloaliphatic TGA, 150-225°C degradation stage 1 92.00 14 unaged
Epoxy, Cycloaliphatic TGA, 150-225°C degradation stage 2 107.00 irradiated 135 kGy
Epoxy, Cycloaliphatic TGA, 150-225°C degradation stage 1 100.00 irradiated 135 kGy
Epoxy, Cycloaliphatic TGA, 150-225°C degradation stage 2 89.00 70 to 131 Neoprene EAB

[82]

71.00 24 to 70 Neoprene EAB 96.00 80 to 110 Neoprene EAB, O2 consumption 76.00 25 to 80 Neoprene O2 consumption 107.00 100 to 150 CSPE EAB, O2 consumption 91.00 37 to 100 CSPE O2 consumption 106.00 100 to 170 EPR EAB 100.00 52 to 125 EPR O2 consumption 88.00 99 to 139 EPR EAB 100.00 99 to 139 EPR EAB early degradation 128.00 99 to 139 EPR EAB late degradation 72.00 48 to 138 XLPO EAB, O2 consumption 110.00 91 to 170 XLPO EAB 128.32 120 to 160 XLPE EAB

[155]

106.13 120 to 160 EPR EAB 202.61 120 to 160 Silicone EAB 130.00 120 to 175 EPR EAB

[156]

63.00 100 to 120 EPR EAB 115.00 15 120 to 150 PE, EPR, CSPE, PVC from reference

[71]

65.00 5

100 PE, EPR, CSPE, PVC from reference 41.90 100 Silicone from reference 97.00 13 110 to 120 EPR from reference 130.00 120 EPR from reference 62.80 to 100 EPR from reference 76.00 80 to 120 EPDM O2 consumption 58.00 40 to 140 EPR O2 consumption 110.00 100 to 120 XLPE EAB

[157]

100.00 100 to 120 XLPE EAB 66.10 100 to 120 XLPE EAB 83.80 100 to 120 XLPE EAB 94.50 100 to 120 XLPE EAB 94.50 100 to 120 EPR EAB 110.00 100 to 120 EPR EAB 102.00 100 to 120 EPR EAB 95.90 100 to 120 EPR EAB

Appendix 55 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

84.00 100 to 120 EPR EAB

[157]

Cont.

85.10 100 to 120 EPR EAB 87.30 100 to 120 EPR EAB 87.20 100 to 120 EPR EAB 83.80 100 to 120 EPR EAB 85.40 100 to 120 EPR EAB 47.10 135 to 175 Silicone EAB 41.50 135 to 175 Silicone EAB 50.40 135 to 175 Silicone EAB 72.20 100 to 120 PVC EAB 71.20 100 to 120 PVC EAB 71.90 100 to 120 PVC EAB 89.00 100 to 120 PVC EAB 160.00 170 to 210 EPDM induction time, 1%

weight loss

[29]

113.00 110 to 170 EPDM EAB 91.00 50 to 100 CSPE EAB, O2 consumption

[61]

107.00 100 to 150 CSPE EAB 106.00 104 to 170 EPR EAB 100.00 52 to 125 EPR O2 consumption 98.00 48 to 124 XLPO O2 consumption 135.00 124 to 151 XLPO EAB, O2 consumption 55.00 135 to 175 Silicone from reference

[72]

58.00 175 to 235 Silicone from reference 37.90 40 to 70 PP FTIR CI induction period with UV

[21]

42.40 40 to 70 PP FTIR CI induction period with UV 57.80 40 to 70 PP FTIR CI induction period with UV 116.00 111 to 155 EPDM induction time of EAB, density, modulus, force decay

[15]

82.00 52 to 111 EPDM O2 consumption 90.00 64.5 to 125 Nitrile EAB, surface modulus 80.00 23 to 64.5 Nitrile O2 consumption 71.00 24 to 70 Neoprene EAB 89.00 70 to 121 Neoprene EAB 107.00 104 to 150 CSPE EAB 91.00 40 to 104 CSPE O2 consumption 80.00 72 to 127 Butyl Sealing force 105.00 82 to 127 Butyl Sealing force 135.00 125 to 152 XLPO EAB 98.00 99 to 109 XLPO EAB 96.00 100 to 138 PA TS 30.00 37 to 138 PA TS 21.00 20 to 50 Silicone water sorption 16.00 20 to 50 Silicone water sorption 18.00 20 to 50 Silicone water sorption 89.00 50 to 97 PU water sorption

Appendix 56 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

116.00 111.5 to 161.6 EPDM Tensile Elongation, Density, Modulus, Force Decay

[16]

118.00 111 to 161.6 EPDM Elongation, Density, Oxygen Consumption 82.00 49.4 to 111 EPDM Oxygen Consumption 90.00 64.5 to 125 Nitrile Elongation, Surface Modulus 80.00 21 to 64.5 Nitrile Oxygen Consumption 89.00 70 to 121 Neoprene Ultimate Tensile Elongation 71.00 24 to 70 Neoprene Ultimate Tensile Elongation 107.00 97.2 to 161.6 CSPE Elongation, Oxygen Consumption 91.00 39.4 to 97.2 CSPE Elongation, Oxygen Consumption 80.00 71.7 to 126.9 Butyl Time to 75% Force Loss 105.00 80.2 to 126.9 Butyl Time to 50% Loss in Sealing Force 96.00 100 to 138 PA Tensile Strength 30.00 37 to 100 PA Tensile Strength 109.99 CSPE from reference

[158]

130.25 EPDM from reference 115.78 EPR from reference 86.83 ETFE from reference 90.69 Neoprene from reference 95.52 PVC from reference 173.66 Silicone from reference 112.88 Viton from reference 119.64 XLPE/XLPO from reference 106.13 EPR from reference 109.99 Neoprene from reference 130.25 XLPE/XLPO from reference 89.00 70 to 161 Neoprene EAB

[58]

107.00 100 to 150 CSPE EAB 91.00 37 to 100 CSPE O2 consumption 86.00 37 to 80 Neoprene O2 consumption 115.78 190 PEEK from manufacturer

[159]

106.13 135 XLPO from manufacturer 116.74 135 EPR from manufacturer 130.25 120 EVA from manufacturer 83.26 190 Silicone from manufacturer 139.90 190 Silicone from manufacturer 130.25 135 XLPE from reference 107.09 120 CSPE from reference 121.66 135 EPR from manufacturer 121.18 135 EPR from manufacturer 120.60 135 XLPO from manufacturer 103.23 25 to 85 EPDM EAB with irradiation

[18]

94.57 100 to 120 XLPE EAB

[160]

Appendix 57 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

93.52 100 to 120 EPR EAB

[160]

Cont.

253.04 115 to 165 XLPE EAB

[161]

232.76 115 to 165 XLPE EAB 267.52 115 to 165 XLPE EAB 269.11 115 to 165 XLPE EAB 249.12 115 to 165 XLPE EAB 242.95 115 to 165 XLPE EAB 253.49 115 to 165 XLPE EAB 113.00 111 to 170 EPDM O2 consumption, surface modulus, EAB

[162]

89.00 70 to 161 Neoprene EAB 85.80 28 to 120 CSPE Oxidation rate

[23]

76.00 28 to 120 CSPE Oxidation rate 14.20 28 to 120 CSPE Oxidation rate 79.00 28 to 120 CSPE Oxidation rate 90.70 37 to 108 CSPE Oxidation levels 91.30 37 to 108 CSPE Oxidation levels 148.68 70 to 100 natural rubber(50%)/

butadiene rubber(50%)

EAB e/e0 = 0.55

[19]

119.01 70 to 100 natural rubber(50%)/

butadiene rubber(50%)

EAB e/e0 = 0.65 89.34 70 to 100 natural rubber(50%)/

butadiene rubber(50%)

EAB e/e0 = 0.75 59.67 70 to 100 natural rubber(50%)/

butadiene rubber(50%)

EAB e/e0 = 0.85 89.00 70 to 161 Neoprene EAB

[17]

71.00 24 to 70 Neoprene EAB 105.00 100.4 to 149.5 CSPE EAB 91.00 60 to 100.4 CSPE EAB 50.00 75 to 100 EPDM Compression stress relaxation

[30]

131.00 125 to 150 EPDM Compression stress relaxation 78.00 75 to 100 EPDM EAB, O2 consumption 127.00 125 to 150 EPDM EAB, O2 consumption 92.00 75 to 150 EPDM Sealing force 71.00 24 Neoprene from reference

[54]

98.00 25 Neoprene from reference 107.00 100 CSPE from reference 112.00 109 CPE from reference 106.00 50 EPR from reference 128.00 50 EPR from reference 88.00 50 EPR from reference

Appendix 58 Ea (kJ/mol)

+/-

Temperature range (°C)

Polymer*

Dataset Notes Ref.

106.00 50 EPR from reference

[54]

Cont.

110.00 50 XLPO from reference 130.00 50 XLPO from reference 112.20 7.1 121 to 165 EPR EAB

[24]

138.00 19 121 to 165 EPR Eab*

109.60 9.8 121 to 165 XLPE EAB 78.00 12 121 to 165 XLPE Eab*

101.40 13 121 to 165 XLPE EAB 121.00 18 121 to 165 XLPE Eab*

112.88 2.9 55 to 81 EPR EAB 50% abs. EAB

[25]

99.37 11 55 to 81 EPR EAB 50% abs. EAB 109.99 13 55 to 81 EPR EAB 50% abs. EAB 89.73 18 55 to 81 XLPE EAB 50% abs. EAB 106.00 2

90 to 160 XLPE Absorbance 1720cm-1

[20]

97.00 1

50 to 90 XLPE Absorbance 1720cm-1 110.00 2

90 to 160 EPR Absorbance 1714cm-1 71.00 1

50 to 90 EPR Absorbance 1714cm-1 105.00 3

70 to 160 XLPE EAB 42.70 4.2 unaged PE TGA 10-50°C/min, N

[27]

40.10 2

unaged PE TGA 10-50°C/min, O 72.80 4.6 60kGy PE TGA 10-50°C/min, N 67.00 1.7 250kGy PE TGA 10-50°C/min, N 51.40 3.4 60kGy PE TGA 10-50°C/min, O 112.50 12 250kGy PE TGA 10-50°C/min, O 269.38 unaged XLPE TGA Coast Redfern integral method

[26]

181.59 15 yr service life XLPE TGA Coast Redfern integral method 167.44 30 yr service life XLPE TGA Coast Redfern integral method 126.00 XLPO from reference

[126]

125.42 EPR from reference

[163]

98.30 3.3 75 to 105 PVC TGA plasticizer desorption [164]

  • PVC = polyvinyl chloride ; neoprene = polychloroprene ; XLPO = crosslinked polyolefin; Viton = FPM =

fluorocarbon elastomer; nitrile = NBR = nitrile butadiene rubber; CSPE = chlorosulphonated polyethylene; EPDM = ethylene propylene diene M-type rubber; XLPE = crosslinked polyethylene; EPR = ethylene propylene rubber; PP = polypropylene; ETFE = ethylene tetrafluoroethylene; butyl = IIR = butyl rubber; PU

polyurethane; BPA = bisphenol A; PA = polyamide = nylon; PEEK = polyetheretherketone EAB = elongation at break; IR = insulation resistance; DF = dissipation factor = tangent delta; CL

chemiluminescence; OIT = oxygen induce time; IR - carbonyl = Fourier transform infrared spectroscopy (FTIR)-determined carbonyl index; TOL = TGA = thermogravimetric analysis; IM = indenter = indenter modulus; TS = tensile strength

Pacific Northwest National Laboratory 902 Battelle Boulevard P.O. Box 999 Richland, WA 99354 1-888-375-PNNL (7665) www.pnnl.gov l www.nrc.gov