YANKEE AT MIC ELECTRIC COMPANY 49 Yankee Road, Rowe, Massachusetts 01367 December 10, 2024 BYR 2024-014 Re: 10 CFR 72.4, 10 CFR 72.30, and 10 CFR 50.82(a)(7)

ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555 - 0001 Yankee Atomic Electric Company Yankee Nuclear Power Station Independent Spent Fuel Storage Installation NRC License No. DPR-3 (NRC Docket No.50-029) 7 2 - b 3 I

Subject:

Three-Year Update to the Independent Spent Fuel Storage Installation Decommissioning Funding Plan Pursuant to the requirements of 10 CFR 72.30(c) and 10 CFR 72.4, Yankee Atomic Electric Company (Y AEC) is providing a three-year update to the Independent Spent Fuel Storage Installation (ISFSI) Decommissioning Funding Plan (DFP). Enclosure 1 updates the Yankee Nuclear Power Station (YNPS) ISFSI decommissioning cost estimate and the cost estimate for the management of irradiated fuel and Greater than Class C Waste submitted with the previous YNPS ISFSI DFP on December 10, 2021 (Reference 1). It includes adjustments to account for changes in costs. The update does not include any adjustments for additional radiological contamination, because the extent of radioactive contamination at the YNPS ISFSI remains unchanged.

10 CFR 72.30(c) defines specific events that must be considered in the subsequent updates.

Since the submittal of the updated Decommissioning Funding Plan for the ISFSI in December 2021:

I. No spills of radioactive material producing additional residual radioactivity in onsite subsurface material have occurred.

2. Facility modifications that affected the ISFSI, including those that were implemented within the licensed area, were assessed for impact.
3. There were no changes in authorized possession limits.
4. No active decommissioning has occurred, thus, there have not been any actual remediation costs that exceed the previous cost estimate.

In addition, Y AEC complies with the requirements of l 0 CFR 72.30(b )( 1) through (b )( 6), as follows.

10 CFR 72.30(b)(l) requires the licensee to provide "information on how reasonable assurance will be provided that funds will be available to decommission the ISFSI." Y AEC has established NtY\\ssib

~\\'(\\ss

Yankee Atomic Electric Company BYR 2024-014/December 10, 2024/Page 2 an account within its Nuclear Decommissioning Trust (NDT) entitled, "ISFSJ Radiological Decom," that segregates the funds for decommissioning of the JSFSI from the larger balance of funds for ongoing management of irradiated fuel and GTCC waste held in the NDT. Currently, the trust has sufficient funds to meet the revised DCE for the YNPS ISFSI.

10 CFR 72.30(b )(2) requires the licensee to provide a detailed cost estimate for decommissioning. Enclosure 1 provides a revised DCE for the YNPS ISFSI that:

1. Utilizes an independent contractor to perform the decommissioning activities in accordance with 10 CFR 72.30(b )(2)(i);
2. Includes an adequate contingency factor in accordance with 10 CFR 72.30(b )(2)(ii); and
3. Includes the cost of meeting the criteria for unrestricted release in accordance with 10 CFR 72.30(b )(2)(iii).

In addition, the revised YNPS ISFSI DCE specifically considered the effects of the events described in 10 CFR 72.30( c) on the costs of decommissioning and the extent of contamination. The revised YNPS ISFSI DCE estimates the total cost to decommission the YNPS ISFSI to be $6.002 million in 2024 dollars for radiological decommissioning and $9.024 million in 2024 dollars for ISFSI site restoration that includes the additional costs for non-radiological decommissioning and site restoration costs.

10 CFR 72.30(b )(3) requires the licensee to identify and justify the key assumptions contained in the DCE. Enclosure 1 provides the revised DCE for the YNPS ISFSI, including the key assumptions and the justification for their use.

10 CFR 72.30(b)(4) requires the licensee to provide a description of the method of assuring funds for decommissioning from 10 CFR 72.30(e), including means for adjusting cost estimates and associated funding levels periodically over the life of the facility. Y AEC will periodically reassess the decommissioning cost estimate in accordance with 10 CFR 72.30( c ). On a periodic basis, YAEC will submit rate cases to the Federal Energy Regulatory Commission (FERC) that will include revised cost estimates for decommissioning and the management of irradiated fuel and GTCC waste. If necessary, additional funds may be recovered from the purchasers.

Y AEC has successfully litigated several breaches of contract damages claims against the Department of Energy (DOE) for failure to begin the removal of spent nuclear fuel (SNF) and GTCC waste from the site in 1998. Additional damages claims against the DOE relating to the government's breach of contract are expected to continue as long as the irradiated fuel and GTCC waste remain on site.

Annually, YAEC submits the reports required by 10 CFR 50.75(t)(2), 10 CFR 50.82(a)(8)(v) and 10 CFR 50.82(a)(8)(vii) to establish how it satisfies the obligations defined in those regulations regarding the assurance of decommissioning funding and the status of funding for the management of irradiated fuel.

10 CFR 72.30(b )(5) requires the licensee to define the volume of onsite subsurface material containing residual radioactivity that will require remediation to meet the criteria for license

Yankee Atomic Electric Company BYR 2024-014/December 10, 2024/Page 3 termination. No subsurface material is assumed to require remediation regarding radionuclides.

This is justified because:

1. The ISFSI area was confirmed to be clean of radiological contaminants prior to the construction of the ISFSI.
2. The ISFSI area will be maintained clean of loose radiological contaminants during the storage period.
3. The irradiated fuel and GTCC waste are stored in sealed canisters.
4. Nuclear activation of a limited number of Vertical Concrete Casks (VCCs) and VCCs liners is anticipated; the activation products will remain fixed during the storage period.
5. If contamination of subsurface occurs during decommissioning activities, the contamination is expected to remain below the decommissioning criteria of25 millirem per year Total Effective Dose Equivalent.

In addition, the site will meet the remediation standards established by the Commonwealth of Massachusetts.

10 CFR 72.30(b)(6) requires a certification that financial assurance for decommissioning has been provided in the amount of the cost estimate for decommissioning. Enclosure 2 provides the certification of financial assurance.

In addition, Enclosure 3 provides an estimate of the total costs associated with the YNPS ISFSI for the management of irradiated fuel and GTCC waste at the YNPS ISFSI through 2043.

As applicable, a summary of the revised DCE and the cost estimate for the management of irradiated fuel and GTCC waste at the YNPS ISFSI will be incorporated into the Post-Shutdown Decommissioning Activities Report (PSDAR) and the License Termination Plan (L TP) in calendar year 2025. This submittal serves as the notification required by 10 CFR 50.82(a)(7).

If you have any questions, please do not hesitate to contact me at (508) 612-3322.

Respectfully,

Yankee Atomic Electric Company BYR 2024-014/December 10, 2024/Page 4

Enclosures:

1.

Decommissioning Study of the Yankee Rowe Independent Spent Fuel Storage Installation

2.

Certification of Financial Assurance

3.

Total Costs Associated with the YNPS ISFSI, including Cost Estimate for Managing Irradiated Fuel and GTCC Waste

Reference:

1.

Letter from C. PizzelJa (Y AEC) to Document Control Desk (NRC), Three-Year Update to the Independent Spent Fuel Storage Installation Decommissioning Funding Plan, dated December 10, 2021 (BYR 2021-019) cc:

R Lorson, NRC Region I Administrator A. Dimitriadis, Chief, Decommissioning Branch, NRC, Region I Y. Diaz-Sanabria, Chief, Division of Fuel Management, Storage and Transportation Licensing Branch K. Castle, State Nuclear Planner, MEMA J. Cope-Flanagan, Assistant General Counsel, MA DPU G. Wade, Legal Counsel, MA DPU J. Rogers, Asst. Attorney General, State of MAs Office of the Attorney General A. O'Connell, Asst. Attorney General, State of MA Office of the Attorney General

ENCLOSURE 1 TO BYR 2024-014 DECOMMISSIONING STUDY OF THE YANKEE ROWE INDEPENDENT SPENT FUEL STORAGE INST ALLA TI ON

Mr. Todd Smith Mr. Stan Day The Yankees Companies 362 lnjun Hollow Road East Hampton, CT 06424 TLG Services, LLC 148 New Milford Rd. East Bridgewater, CT 06752 (860) 355-2300 www.tlgservices.com July 19, 2024 Y03-1833-001

Subject:

2024 Decommissioning Cost Estimates for the Connecticut Yankee Atomic Power Company, Maine Yankee Atomic Power Company, and the Yankee Atomic Electric Company

Dear Mr. Smith:

Attached please find TLG's Final copies of the 2024 cost estimates for decommissioning the Connecticut Yankee Atomic Power Company, Maine Yankee Atomic Power Company, and the Yankee Atomic Electric Company ISFSls.

If you have any questions, please call me at (716) 432-8659.

Attachments:

2024 Connecticut Yankee ISFSI Letter 2024 Maine Yankee ISFSI Letter 2024 Yankee Rowe ISFSI Letter cc:

Lori Glander Angela Bouton Rich Threlkeld John Carlson Sincerely, TLG Services, LLC

  1. JL Adam Kaczmarek Sr. Manager, Decommissioning

Yankee Atomic Electric Company Yankee Rowe ISFSI Page 1 of 11 10 CFR 72.30 ISFSI Decommissioning Cost Estimate

1.

Background and Introduction The Nuclear Regulatory Commission (NRC) issued its final rule on Decommissioning Planning on June 17, 2011,[11 with the rule becoming effective on December 17, 2012. Subpart 72.30, "Financial assurance and recordkeeping for decommissioning," requires that each holder of, or applicant for, a license under this part must submit for NRC review and approval a decommissioning funding plan that contains information on how reasonable assurance will be provided that funds will be available to decommission the Independent Spent Fuel Storage Installation (ISFSI).

In accordance with the rule, this letter provides a detailed cost estimate for decommissioning the Yankee Rowe (YR) Independent Spent Fuel Storage Installation (ISFSI) in an amount reflecting:

1. The work is performed by an independent contractor;
2. An adequate contingency factor; and
3. Release of the facility and dry storage systems for unrestricted use, as specified in 10 CFR Part 20.1402 This letter also provides:
1. Identification of the key assumptions contained in the cost estimate; and
2. The volume of onsite subsurface material containing residual radioactivity, if any, that will require remediation to meet the criteria for license termination.
2.

Spent Fuel Management Strategy Yankee Rowe (YR) was successfully decommissioned between 1992 and 2007.

During decommissioning all 533 spent fuel assemblies were transferred from the spent fuel pool to 15 spent fuel storage casks. In addition, 1 GTCC cask containing segmented sections of the reactor internals are stored on the spent fuel storage pad. The ISFSI is operated under a Part 50 General License.

1 U.S. Code of Federal Regulations, Title 10, Parts 20, 30, 40, 50, 70 and 72 "Decommissioning Planning," Nuclear Regulatory Commission, Federal Register Volume 76, Number 117 (p 35512 et seq.), June 17, 2011 TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Page2of 11 Completion of the ISFSI decommissioning process is dependent upon the DOE's ability to remove spent fuel from the site. DOE's repository program assumes that spent fuel allocations will be accepted for disposal from the nation's commercial nuclear plants, with limited exceptions, in the order (the "queue") in which it was discharged from the reactorJ2l

3.

ISFSI Decommissioning Strategy At the conclusion of the DOE spent fuel transfer process the ISFSI will be promptly decommissioned (similar to the power reactor DECON alternative) by removing and disposing of residual radioactivity and verifying that remaining materials satisfy NRC and the Commonwealth of Massachusetts release criteria.

4.

ISFSI Description The YR ISFSI is located on approximately 2 acres of the 1800-acre site. The ISFSI consists of 15 dry storage casks containing 533 spent nuclear fuel assemblies used during operations. The NAC-MPC fuel storage and transport canister system was chosen by YR and is licensed by the NRC for both storage and transportation. The NAC-MPC system consists of a multi-purpose spent fuel storage canister and a vertical concrete and steel overpack. Each vertical concrete cask has a three-and-a-half-inch steel liner surrounded by 21 inches of reinforced concrete. Construction of the concrete storage pad and vertical concrete and steel storage was completed during decommissioning.

Transferring the spent fuel from the spent fuel pool to the storage casks was completed in March of 2003.

In addition to the 15 spent fuel storage casks there is one cask containing segmented sections of the reactor internals classified as Greater than Class C waste. The storage overpacks used for the GTCC canisters are not expected to have any interior contamination or residual activation and can be reused or disposed of by conventional means after a final status survey. The multi-purpose canisters will be transferred directly to the DOE. After removal of the MPC canisters, the overpacks will be surveyed and any found to have residual 2

U.S. Code of Federal Regulations, Title 10, Part 961.11, Article IV - Responsibilities of the Parties, B. DOE Responsibilities, 5.(a)... DOE shall issue an annual acceptance priority ranking for receipt of SNF and/or HLW at the DOE repository. This priority ranking shall be based on the age of SNF and/or HLW as calculated from the date of discharge of such materials from the civilian nuclear power reactor. The oldest fuel or waste will have the highest priority for acceptance, except as... "

TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Page 3of 11 radioactivity due to some minor level of neutron-induced activation as a result of the long-term storage of the spent fuel will be removed as activated. The cost to dispose of residual radioactivity, and verify that the remaining facility and surrounding environs meet the NRC's radiological limits established for unrestricted use, forms the basis of the ISFSI decommissioning estimate.

Table 1 provides the significant quantities and physical dimensions used as the basis in developing the ISFSI decommissioning estimate.

5.

Key Assumptions / Estimating Approach The decommissioning estimate is based on the configuration of the ISFSI expected after all spent fuel and GTCC material has been removed from the site. The configuration of the ISFSI is based on the assumptions associated with DOE's spent fuel acceptance, as previously described.

TLG does not expect the overpacks to have any interior or exterior radioactive surface contamination. Any neutron activation of the steel and concrete is expected to be extremely small. This assumption is adopted for this analysis.

The decommissioning estimate is based on the premise that the inner steel liners of some of the concrete and steel overpacks will contain low levels of neutron-induced residual radioactivity that would necessitate remediation at the time of decommissioning. As an allowance, 3 of the 15 overpacks are assumed to be affected, i.e., contain residual radioactivity. This is conservative, because the fuel had decayed in the spent fuel pool for a few years prior to being placed into dry storage. The overpacks will be segmented and packaged for disposal as low-level radioactive waste.

It is not expected that there will be any residual contamination to be left on the concrete ISFSI pad. It would be expected that this assumption would be confirmed as a result of good radiological practice of surveying potentially impacted areas after each spent fuel transfer campaign. It is assumed for this analysis that the ISFSI pad will not be contaminated. As such, only verification surveys are included for the pad in the decommissioning estimate. An allowance is also included for surveying any transfer equipment.

The subsurface material of the ISFSI site is not expected to contain any significant residual radioactivity that will require remediation to meet the criteria for license termination.

Decommissioning is assumed to be performed by an independent contractor.

As such, essentially all labor, equipment, and material costs are based on TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Page 4of 11 national averages, i.e., costs from national publications such as RSMeans Building Construction Cost Data (adjusted for regional variations), and laboratory service costs are based on vendor price lists. Those craft labor positions are expected to be provided locally. Yankee Atomic Electric Company, as licensee, will oversee the site activities.

The Utility oversight staff is assumed to be similar in size and configuration as it is currently.

The following buildings are disposed of as clean waste in a local landfill.

ISFSI Pad Remaining Overpacks Fencing ISFSI support systems Diesel generator and building Gatehouse ISFSI support building Instrument enclosure -conduit and wire Nuisance fence Remove road inside licensed area Remove vehicle barriers Retaining wall Septic system and utilities Costs are reported in 2024 dollars. Costs do not include Massachusetts sales tax.

Contingency has been added to the ISFSI Decontamination costs at an overall rate of 25%. This is consistent with the contingency evaluation criteria referenced by the NRC in NUREG-1757.l31 Contingency has been added to the Site Restoration costs at a rate of 25%.

The estimate is limited to costs necessary to terminate the ISFSl's NRC license and meet the §20.1402 criteria for unrestricted use. Disposition of released material and structures is outside the scope of the estimate.

3 "Consolidated Decommissioning Guidance, Financial Assurance, Recordkeeping, and Timeliness," U.S. Nuclear Regulatory Commission's Office of Federal and State Materials and Environmental Management Programs, NUREG-1757, Volume 3, Revision 1, February 2012 TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Page 5 of 11 The effects, if any, since the last submittal of the ISFSI decommissioning funding plan of the following events listed in 10 CFR 72.30(c)(l)-(4) have been specifically considered in the decommissioning cost estimate:

(1) Spills of radioactive material producing additional residual radioactivity in onsite subsurface material: There have been no spills at the ISFSI.

(2) Facility modifications: There have been no facility modifications in the past three years that affect the decommissioning cost estimate.

(3) Changes in authorized possession limits: There are no changes in authorized possession limits that affect the decommissioning cost estimate.

(4) Actual remediation costs that exceed the previous cost estimate: No actual remediation costs have been incurred, therefore; actual remediation costs do not exceed the previous cost estimate.

6.

Cost Estimate The estimated cost to decommission the ISFSI and release the facility for unrestricted use is provided in Table 2. The cost has been organized into four phases, including:

  • An initial planning phase - empty overpacks are characterized and the specifications and work procedures for the decontamination (liner removal) developed.

The remediation phase - residual radioactivity is removed, packaged in certified waste containers, transported to the low-level waste site, and disposed of as low-level waste.

The license termination phase - license termination surveys, independent surveys are completed, and an application for license termination submitted.

Site restoration - While not required by the NRC this estimate includes the cost to remove and dispose of all non-contaminated structures. A list of all structures included in this estimate is provided in Table 3.

In addition to the direct costs associated with a contractor providing the decommissioning services, the estimate also contains costs for the NRC (and NRC contractor), YR's oversight staff, site security (industrial), and other site operating costs.

TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Page 6of 11 For estimating purposes, it should be conservatively assumed that all expenditures will be incurred in the year following all spent fuel removal.

TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Table 1 Page 7 of 11 Significant Quantities and Physical Dimensions ISFSI Pad Residual Item Length (ft)

Width (ft)

Radioactivity ISFSI Pad (dimensions are for current pad) 180 48 No ISFSI Overpack Item Value Notes (all dimensions are nominal)

DPC/Y ankee-MPC Overall Height (inches) 158.4 Dimensions are nominal Overall Diameter (inches) 128.0 Dimensions are nominal Inside Diameter (inches) 79.0 Dimensions are nominal Inner Liner Thickness (inches) 3.50 Dimensions are nominal Quantity (total) 16 15 spent fuel+ 1 GTCC Quantity (with residual radioactivity) 3 Total Surface Area of overpack interior with Residual 819 Radioactivity (square feet)

Low-Level Radioactive Waste (cubic feet) 4,796 Low-Level Radioactive Waste (buried density) 95 TLG Services, LLC

Yankee Atomic Electric Company Yankee Rowe ISFSI Table 2 ISFSI Decommissioning Costs and Waste Volumes (Thousands of 2024 Dollars)

LLRW Removal Packaging Transport Disposal Other Total Costs Costs Costs Costs Costs Costs Activity Description Decommissioning Contractor Planning (characterization, specs and procedures)

I

- I

- I 191 191 Decontamination (activated I

liner and concrete removal) 94 71 127 291 License Termination I

(radiololrical survevs)

-l

- ~-

983 983 Subtotal I

94 71 127 1,174 1,465 Supporting Costs NRC and NRC Contractor Fees 323 323 and Costs Insurance 181 181 Property taxes 133 133 NRC Fees 149 149 Site O&M Cost 551 551 Security Staff Cost 400 400 DOC Staff Cost 592 592 Utility Staff Cost 1,007 1,007 Subtotal 3,336 3,336 TLG Services, LLC Burial Volume Class A (cubic feet)

-I 4,796

- I 4,796 Page 8 of 11 Oversight Craft and Manhours Contractor Manhours

- I 952 390 7 6,269 6,659 952 1,153 11,625 4,787 7,066 24,631

Yankee Atomic Electric Company Yankee Rowe ISFSI Table 2 (continued)

ISFSI Decommissioning Costs and Waste Volumes (Thousands of 2024 Dollars)

LLRW Removal Packaging Transport Disposal Other Total Costs Costs Costs Costs Costs Activitv Description Costs ISFSI Decontamination Total 94 71 127 4,510 4,801 (w/o contingency)

ISFSI Decontamination Total 117 88 159 5,638 6,002 (with 25% contine:encv)

ISFSI Site Restoration Remove Fencing (linear foot) 9 9

Remove Asphalt Paving 15 15 ISFSI Cask & Pad Demolition 339 89 429 and Removal ISFSI Support systems 48 48 Demolition of Remaining Site Buildings Diesel Generator and Building 0.3 0.3 Gatehouse 17 17 ISFSI Support Building 36 36 Instrument Enclosure -conduit 0.1 0.1 and wire Nuisance Fence 147 147 Remove road inside licensed 48 48 area Remove vehicle barriers 1

1 Retaining Wall 11 11 Septic System and Utilities 3

3 TLG Services, LLC Burial Volume Class A (cubic feet) 4,796 4,796 Page 9 of 11 Oversight Craft and Manhours Contractor Manhours 6,659 25,583 6,659 25,583 99 131 1,910 614 1

166 252 0.5 1,571 430 8

51 17

Yankee Atomic Electric Company Yankee Rowe ISFSI Table 2 (continued)

ISFSI Decommissioning Costs and Waste Volumes (Thousands of 2024 Dollars)

LLRW Removal Packaging Transport Disposal Other Total Costs Costs Costs Costs Costs Activity Description Costs Construction Debris 27 27 Grade and Landscape 3

3 Subtotal 676 116 792 Supporting Costs NRC and NRC Contractor Fees 26 26 and Costs Property truces 33 33 Site O&M Cost 138 138 Security Staff Cost 100 100 DOC Staff Cost 148 148 Utility Staff Cost 252 252 Severance 929 929 Subtotal 1,626 1,626 ISFSI Site Restoration Total 676 1,742 2,418 (w/o continl!ency)

ISFSI Site Restoration Total 845 2,177 3,023 (with 25% contine:ency)

Total (w/o contingency) 770 71 127 6,252 7,219 Total (with contingency) 962 88 159 7,815 9,024 TLG Services, LLC Burial Volume Class A (cubic feet) 4,796 4,796 Page 10 of 11 Oversight Craft and Manhours Contractor Manhours 12 5,262 160 2,906 1,197 1,767 6,030 5,262 6,030 5,262 6,030 11,922 31,613 11,992 31,613

Yankee Atomic Electric Company Yankee Rowe ISFSI Table 3 ISFSI Decommissioning - Structures Included Contaminated Removal Cask inner liner Cask lid Cask base & misc. Internal fixtures VCC concrete Clean Removal ISFSI concrete pad Non-activated overpacks Remove fencing (linear foot)

ISFSI support systems Diesel generator and building Gatehouse ISFSI support building Instrument enclosure -conduit and wire Nuisance Fence Remove road inside licensed area Remove vehicle barriers Retaining wall Septic system and utilities TLG Services, LLC Page 11 of 11

ENCLOSURE 2 TO BYR 2024-014 CERTIFICATION OF FINANCIAL ASSURANCE

CERTIFICATION OF FINANCIAL ASSURANCE NRC Licensee:

Yankee Atomic Electric Company Yankee Rowe Independent Spent Fuel Storage Installation NRC License No. DPR-3 (NRC Docket No.50-029) 49 Yankee Road Rowe, MA O 1367 Issued to: U.S. Nuclear Regulatory Commission Certification:

I hereby certify that Yankee Atomic Electric Company (Y AEC) is the licensee for the Yankee Nuclear Power Station Independent Spent Fuel Storage Installation (YNPS ISFSI) and that I, the undersigned, am authorized to provide this Certification of Financial Assurance with respect to the radiological decommissioning of the YNPS ISFSI.

During the operation of this ISFSI, spent nuclear fuel and Greater than Class C waste will be stored at the YNPS ISFSI in storage casks licensed under IO CFR 72. Pursuant to contracts with the Department of Energy the spent fuel will ultimately be removed from the ISFSI location, and Y AEC will dispose of other radiological waste in accordance with NRC regulations, at which time the YNPS ISFSI will be decommissioned in accordance with NRC regulations.

I further certify that financial assurance in an amount sufficient to fund YNPS ISFSI radiological decommissioning at the time of such decommissioning has been provided, pursuant to 10 CFR 72.30, as described in the letter to which this Certification is attached. That radiological decommissioning funding assurance is premised on a site-specific decommissioning cost estimate and funding methodology described therein, in the amount of:

YNPS ISFSI

$6.002 million (in 2024 dollars, inclusive of contingency)

Tim onry Y. kee Atomic Electric Company Treasurer Phone (508) 612-3322 Corporate Seal Date December I 0, 2024

ENCLOSURE 3 TO BYR 2024-014 TOTAL COSTS ASSOCIATED WITH THE YNPS ISFSI, INCLUDING COST ESTIMATE FOR MANAGING IRRADIATED FUEL AND GTCC WASTE

Yankee Atomic Electric Company Irradiated Fuel & GTCC Waste Management and ISFSI Decom Estimate Represented In 2024 Dollars Row labels Contingency Federal Excise Tax Insurance Labor - Non-Manual Labor - Non-Manual-Succession Planning Labor - Security Materials & Supplies Miscellaneous Outside Services - A&G Outside Services - Fuel Loading Outside Services - IAGE Outside Services - ISFSI OP's Outside Services - Legal Outside Services - NON-RAD D&D of ISFSI Outside Services - RAD D&D of ISFSI Property Taxes Regulatory Fees Utilities (blank)

Grand Total Sumof2024 Sum of2025 598,029 571,733 4,500 4,500 556,380 557,350 3,638,030 3,462,792 60,000 336,525 3,600,000 3,900,000 391,750 149,000 191,000 157,000 855,715 811,995 80,000 80,000 621,200 513,500 875,000 450,000 300,000 300,000 661,500 586,500 125,500 125,500 12,558,604 12,006,395 25,117,208 24,012,790 Sum of 2026 Sum of 2027 Sum of 2028 Sum of 2029 Sum of 2030 Sum of 2031 Sum of 2032 Sum of 2033 541,205 550,740 561,395 528,223 528,390 531,673 561,801 517,325 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4,500 558,880 556,380 557,350 558,880 556,380 557,350 558,880 556,380 3,191,757 3,113,761 3,089,309 3,041,609 2,978,199 2,949,294 2,961,894 2,949,294 90,525 153,833 111,790 131,350 39,763 3,900,000 3,900,000 3,900,000 3,900,000 3,900,000 3,900,000 3,900,000 3,900,000 147,000 128,000 78,000 78,000 188,000 78,000 118,000 78,000 157,000 157,000 157,000 157,000 157,000 157,000 157,000 157,000 854,930 862,625 805,250 862,625 805,250 862,625 805,250 812,625 80,000 80,000 80,000 80,000 80,000 80,000 780,000 130,000 427,500 546,700 932,700 538,500 446,700 532,700 438,500 546,700 400,000 500,000 500,000 200,000 400,000 500,000 500,000 200,000 300,000 300,000 300,000 300,000 300,000 300,000 300,000 300,000 586,500 586,500 586,500 586,500 586,500 586,500 586,500 586,500 125,500 125,500 125,500 125,500 125,500 125,500 125,500 125,500 11,365,297 11,565,539 11,789,294 11,092,687 11,096,182 11,165,142 11,797,825 10,863,824 22,730,594 23,131,078 23,578,588 22,185,374 22,192,364 22,330,284 23,595,650 21,727,648

Yankee Atomic Electric Company Irradiated Fuel & GTCC Waste Management and ISFSI Decom Estimate Represented In 2024 Dollars Row labels Contingency Federal Excise Tax Insurance Sum of Totals Sum of 2034 Sum of 2035 Sum of 2036 Sum of 2037 Sum of 20311 Sum of 2039 Sum of 2040 Sum of 2041 Sum of 2042 Sum of 2043 Sum of 2044 2024

  • 2044 Labor - Non-Manual Labor - Non-Manual-Succession Planning Labor - Security Materials & Supplies Miscellaneous Outside Services - A&G Outside Services - Fuel Loading Outside Services - IAGE Outside Services
  • ISFSI OPs Outside Services - Legal Outside Services - NON-RAO D&O of ISFSI Outside Services - RAD D&D of ISFSI 530,514 4,500 557,350 2,965,144 118,334 3,900,000 78,000 157,000 905,250 80,000 432,700 400,000 529,278 4,500 558,880 2,941,558 22,500 3,900,000 78,000 157,000 812,625 80,000 518,500 500,000 Property Taxes 300,000 300,000 RegulatOl)I Fees 586,500 586,500 UtBities 125,500 125,500 (blank) 11,140,792 11,114,641 Grand Total 22,2111,584 22,229,11112 (A)
  • Soun:t 2024 Dnlft FERC Budget - Years 2024
  • 2044 526,199 498,387 507,014 4,500 4,500 4,500 556,380 557,350 558,880 2,954,158 2,913,558 2,926,158 3,900,000 3,900,000 3,900,000 78,000 118,000 78,000 157,000 157,000 157,000 855,250 812,625 805,250 80,000 80,000 80,000 426,700 212,700 218,500 500,000 200,000 400,000 300,000 300,000 300,000 586,500 586,500 586,500 125,500 125,500 125,500 11,050,187 10,466,120 10,647,302 22,100,374 20,832,240 21,294,604 Note 1: The cost of management of irradiated fuel and GTCC waste Is calculated as follows:

474,527,597 (2,683,760)

(4,233,760) 467,610,097 514,538 511,648 1,025,243 1,046,293 642,145 4,500 4,500 4,500 4,500 4,500 556,380 557,350 558,880 556,380 558,380 2,913,558 2,926,158 2,913,558 2,576,662 2,576,662 3,900,000 3,900,000 3,900,000 3,900,000 500,000 78,000 78,000 78,000 78,000 37,000 157,000 157,000 157,000 157,000 108,000 862,625 605,250 862,625 750,250 780,205 273,163 735,438 80,000 80,000 80,000 80,000 80,000 226,700 212,700 212,700 212,700 192,700 500,000 500,000 200,000 400,000 500,000 2,319,353 4,067,954 300,000 300,000 300,000 300,000 300,000 586,500 586,500 586,500 586,500 660,500 125,500 125,500 125,500 125,500 125,500 10,805,301 10,744,606 11,277,669 11,509,223 13,450,899 21,610,602 21,489,212 22,555,338 23,018,446 26,901,788 Note 2: The cost of RAD and NON-RAD D&D of the ISFSI In 2024 dollars as provided in the column labeled "Sum of 2043" is from TLG 2024 cost estimate Note 3: This Summary Combines YR's 2024 Draft FERG Rate Case with the TLG Services 2024 RAD and NON-Rad ISFSI Decom Cost Estimate 862,816 $

4,500 $

1,010,660 $

2,576,662 $

500,000 32,000 106,500 822,135 780,000 110,200 1,750,000 150,000 660,000 125,500 9,490,973 111,981,946 12,664,589 94,500 12,159,080 62,559,775 1,064,620 74,600,000 2,244,750 3,231,500 17,412,980 1,008,601 3,130,000 8,521,500 10,375,000 2,319,353 4,067,954 6,150,000 12,539,000 2,635,500 238,998,702 473,897,404 {A)

{2,319,353) 2021 TLG in 2024$

{4,067,954) 2021 TLG In 2024$

2,683,750 2024 TLG 41233.750 2024 11.G 474,527,597 (BJ