GEH BWRX-300 SMR TR RAI - FW Re NRC Staff Clarification Comments on Steel-Composite Containment Vessel and Reactor Building Structural Design Topical Report NEDO-33926 RAI Question 6 (RAI 5.8-1)
ML24081A160
Person / Time
Site: 99900003
Issue date: 03/21/2024
From:
NRC
To:
NRC/NRR/DNRL/NRLB
References
Download: ML24081A160 (5)


Text

From:

Jordan Glisan Sent:

Thursday, March 21, 2024 1:02 PM To:

GEH-BWRX-300RAIsPEm Resource Cc:

Jim Shea

Subject:

FW: RE: NRC Staff Clarification Comments on Question 6 (RAI 5.8-1)

From: Karkour, Suzanne (GE Vernova) <SUZANNE.KARKOUR@ge.com>

Sent: Wednesday, March 13, 2024 2:38 PM To: Jordan Glisan <Jordan.Glisan@nrc.gov>; Montgomery, Richard (GE Vernova) <Richard.Montgomery@ge.com>

Cc: Jim Shea <James.Shea@nrc.gov>; Michelle Hayes <Michelle.Hayes@nrc.gov>

Subject:

[External_Sender] RE: NRC Staff Clarification Comments on Question 6 (RAI 5.8-1)

Good afternoon Jordan, Thank you; we managed to include the clarifications in the package that you will receive today for the responses to the second set of RAIs.

You should see them come through in about 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or so.

Regards, Suzanne Suzanne Karkour Manager, Canadian Product Regulatory Affairs GE Hitachi Nuclear Energy Suzanne.Karkour@ge.com Cell: 289-385-1935 From: Jordan Glisan <Jordan.Glisan@nrc.gov>

Sent: Tuesday, March 12, 2024 11:14 AM To: Montgomery, Richard (GE Vernova) <Richard.Montgomery@ge.com>

Cc: Karkour, Suzanne (GE Vernova) <SUZANNE.KARKOUR@ge.com>; Jim Shea <James.Shea@nrc.gov>; Michelle Hayes <Michelle.Hayes@nrc.gov>

Subject:

EXT: NRC Staff Clarification Comments on Question 6 (RAI 5.8-1)

WARNING: This email originated from outside of GE. Please validate the sender's email address before clicking on links or attachments as they may not be safe.

Good morning Richard, NRC review staff pointed out the below and asked me to pass it on for clarification prior to Revision 2 being provided on the docket:

(1) In revised LTR Table 5-2, (a) Footnotes (1), (5) & (9) do not appear to be called out within the Table 5-2 as done for the other footnotes.

(b) In the last row for [DP-SC?] Shear Walls, and Diaphragms element types, from the descriptions in column 2, it is unclear regarding In-plane Shear, whether the first sub-row with value 3.0 in the 4th column is intended to be for In-plane Shear for DP-SC Walls and the second sub-row with value 1.5 intended to be for In-plane Shear for DP-SC Diaphragms. Similarly, the row for In-plane flexure is unclear if it is for DP-SC shear walls or DP-SC diaphragms or both.

(c) It is unclear if footnote (8) should refer to RG 1.243 regulatory position C11.1.5 in its entirety (to cover the range of compression levels) rather than just C11.1.5.1.

(2) In revised LTR Table 5-3 footnote (1), the first word Conservatively does not appear to belong in the first phrase Conservatively, the triaxiality factor, TF, is defined as.

Best Regards,

Jordan Glisan Project Manager U.S. Nuclear Regulatory Commission NRR/DNRL/NLIB Phone: 301-415-3478 Unsubscribe from GE Vernova's commercial electronic messages: http://sc.ge.com/*casl-unsubscribe Désabonner des messages électroniques commerciaux de GE Vernova: http://sc.ge.com/*lcap-desabonnement

Hearing Identifier:

GEH_BWRX300_RAIs_Public Email Number:

21 Mail Envelope Properties (DM6PR09MB5416142283673F24F72D1E37F9322)

Subject:

FW RE NRC Staff Clarification Comments on Question 6 (RAI 5.8-1)

Sent Date:

3/21/2024 1:01:42 PM Received Date:

3/21/2024 1:01:45 PM From:

Jordan Glisan Created By:

Jordan.Glisan@nrc.gov Recipients:

"Jim Shea" <James.Shea@nrc.gov>

Tracking Status: None "GEH-BWRX-300RAIsPEm Resource" <GEH-BWRX-300RAIsPEm.Resource@usnrc.onmicrosoft.com>

Tracking Status: None Post Office:

DM6PR09MB5416.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 3143 3/21/2024 1:01:45 PM image001.jpg 3305 image002.png 8571 Options Priority:

Normal Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date: