Seismic data to support public meeting with Dominion regarding NRC staff evaluation of seismic risk at V.C. Summer Generating Station.
Table 1 GMRS and UHRS for Summer Frequency (Hz) UHRS 1E-4 (g) GMRS (g) UHRS 1E-5 (g) 0.100 0.010393 0.011400 0.022166 0.133 0.014814 0.016600 0.032301 0.200 0.024351 0.027200 0.053002 0.250 0.032217 0.036000 0.070069 0.333 0.046749 0.053600 0.104969 0.500 0.075534 0.088500 0.174311 0.667 0.099759 0.118200 0.233517 1.000 0.139904 0.171000 0.340474 1.333 0.176104 0.216400 0.431340 2.000 0.232316 0.287400 0.574054 2.500 0.279711 0.347600 0.694912 3.333 0.351728 0.439200 0.879098 4.000 0.407119 0.512300 1.027593 5.000 0.460551 0.576500 1.154844 6.667 0.555101 0.697000 1.397110 10.000 0.680901 0.881300 1.780175 13.333 0.706396 0.951900 1.942059 20.000 0.649357 0.920500 1.902157 25.000 0.591304 0.853100 1.770523 33.333 0.505417 0.745200 1.554968 40.000 0.457539 0.682000 1.427137 50.000 0.399905 0.599700 1.256728 100.000 0.280781 0.425200 0.893201 PGA 0.251260 0.374200 0.782801
Table A-1 Control Point Total Mean Hazard Curves for F=0.100 to 1.000 Hz SA(g)
F0.100Hz F0.133Hz F0.200Hz F0.250Hz F0.333Hz F0.500Hz F0.667Hz F1.000Hz 0.00100 3.28009E-03 4.13911E-03 5.36478E-03 6.33062E-03 7.81626E-03 1.21837E-02 1.63253E-02 2.44156E-02 0.00126 2.76783E-03 3.62802E-03 4.81956E-03 5.71168E-03 7.01474E-03 1.06772E-02 1.41483E-02 2.13275E-02 0.00158 2.34382E-03 3.18874E-03 4.33940E-03 5.16426E-03 6.30956E-03 9.38275E-03 1.22981E-02 1.86824E-02 0.00200 1.97109E-03 2.78766E-03 3.89007E-03 4.64980E-03 5.65033E-03 8.20101E-03 1.06277E-02 1.62754E-02 0.00251 1.52832E-03 2.30203E-03 3.38016E-03 4.11520E-03 5.05387E-03 7.26225E-03 9.26133E-03 1.40149E-02 0.00316 1.15162E-03 1.85793E-03 2.89430E-03 3.60194E-03 4.48831E-03 6.41578E-03 8.05824E-03 1.20307E-02 0.00398 7.95767E-04 1.39806E-03 2.37149E-03 3.05187E-03 3.90956E-03 5.65357E-03 7.01865E-03 1.02878E-02 0.00501 5.49597E-04 1.05134E-03 1.94201E-03 2.58461E-03 3.40452E-03 4.98194E-03 6.11417E-03 8.79997E-03 0.00631 3.23433E-04 6.78991E-04 1.40973E-03 1.98294E-03 2.76550E-03 4.24155E-03 5.22164E-03 7.45809E-03 0.00794 1.90741E-04 4.39284E-04 1.02466E-03 1.52295E-03 2.24829E-03 3.61351E-03 4.46222E-03 6.32501E-03 0.01000 1.12257E-04 2.83721E-04 7.43841E-04 1.16847E-03 1.82633E-03 3.07654E-03 3.81091E-03 5.36063E-03 0.01260 5.61613E-05 1.53659E-04 4.54553E-04 7.62794E-04 1.29965E-03 2.38192E-03 3.02968E-03 4.35056E-03 0.01580 2.85041E-05 8.42856E-05 2.80627E-04 5.02393E-04 9.31414E-04 1.85395E-03 2.42009E-03 3.54615E-03 0.02000 1.40647E-05 4.50927E-05 1.69812E-04 3.25192E-04 6.58328E-04 1.42805E-03 1.91519E-03 2.86600E-03 0.02510 6.62081E-06 2.22294E-05 9.21777E-05 1.87990E-04 4.18352E-04 1.00066E-03 1.40228E-03 2.18830E-03 0.03160 3.07553E-06 1.07501E-05 4.87239E-05 1.05600E-04 2.58396E-04 6.83280E-04 1.00375E-03 1.63930E-03 0.03980 1.41286E-06 5.02695E-06 2.41730E-05 5.51102E-05 1.47764E-04 4.33876E-04 6.74248E-04 1.16440E-03 0.05010 6.50325E-07 2.35502E-06 1.20079E-05 2.87867E-05 8.45366E-05 2.75533E-04 4.52920E-04 8.27067E-04 0.06310 3.01861E-07 1.10142E-06 5.67347E-06 1.39124E-05 4.35924E-05 1.55895E-04 2.73073E-04 5.33723E-04 0.07940 1.40546E-07 5.16695E-07 2.68863E-06 6.74333E-06 2.25386E-05 8.84062E-05 1.64974E-04 3.45025E-04 0.10000 6.52432E-08 2.41677E-07 1.27043E-06 3.25929E-06 1.16233E-05 5.00234E-05 9.94716E-05 2.22663E-04 0.12600 2.94152E-08 1.12785E-07 6.01562E-07 1.54886E-06 5.67566E-06 2.56080E-05 5.36977E-05 1.28343E-04 0.15800 1.34832E-08 5.34741E-08 2.89301E-07 7.47496E-07 2.81298E-06 1.32928E-05 2.93611E-05 7.48278E-05 0.20000 5.98310E-09 2.45787E-08 1.34959E-07 3.49987E-07 1.35407E-06 6.71456E-06 1.56562E-05 4.26592E-05 0.25100 2.59840E-09 1.11501E-08 6.41824E-08 1.69355E-07 6.72694E-07 3.37094E-06 8.11476E-06 2.31301E-05 0.31600 1.10417E-09 4.94944E-09 2.99464E-08 8.07021E-08 3.30793E-07 1.67677E-06 4.15794E-06 1.23491E-05 0.39800 4.52377E-10 2.11410E-09 1.35390E-08 3.77165E-08 1.62177E-07 8.33956E-07 2.11073E-06 6.43021E-06 0.50100 1.85627E-10 9.04368E-10 6.12945E-09 1.76500E-08 7.96132E-08 4.15428E-07 1.07317E-06 3.35304E-06 0.63100 7.10342E-11 3.62429E-10 2.60000E-09 7.76398E-09 3.72090E-08 2.04025E-07 5.40914E-07 1.71812E-06 0.79400 2.72874E-11 1.45777E-10 1.10666E-09 3.42649E-09 1.74434E-08 1.00486E-07 2.73386E-07 8.82736E-07
Table A-1 Control Point Total Mean Hazard Curves for F=0.100 to 1.000 Hz SA(g)
F0.100Hz F0.133Hz F0.200Hz F0.250Hz F0.333Hz F0.500Hz F0.667Hz F1.000Hz 1.00000 1.04434E-11 5.84272E-11 4.69473E-10 1.50741E-09 8.15334E-09 4.93550E-08 1.37807E-07 4.52358E-07 1.26000 3.58674E-12 2.13530E-11 1.83597E-10 6.12001E-10 3.50794E-09 2.27739E-08 6.61661E-08 2.23747E-07 1.58000 1.25949E-12 7.96853E-12 7.32126E-11 2.53164E-10 1.53594E-09 1.06786E-08 3.22564E-08 1.12300E-07 2.00000 4.23444E-13 2.85431E-12 2.81000E-11 1.00952E-10 6.49804E-10 4.85199E-09 1.52624E-08 5.47713E-08 2.51000 1.32412E-13 9.66422E-13 1.03615E-11 3.87933E-11 2.64541E-10 2.12792E-09 6.99002E-09 2.60951E-08 3.16000 3.96942E-14 3.14995E-13 3.70069E-12 1.44773E-11 1.04763E-10 9.09517E-10 3.12448E-09 1.21611E-08 3.98000 1.08552E-14 9.46615E-14 1.23983E-12 5.10449E-12 3.93175E-11 3.69520E-10 1.33148E-09 5.43475E-09 5.01000 2.97350E-15 2.84911E-14 4.15992E-13 1.80247E-12 1.47777E-11 1.50331E-10 5.68115E-10 2.43173E-09 6.31000 6.87024E-16 7.31539E-15 1.22002E-13 5.65491E-13 5.01046E-12 5.55339E-11 2.20696E-10 1.00000E-09 7.94000 1.59669E-16 1.88854E-15 3.59566E-14 1.78236E-13 1.70619E-12 2.05966E-11 8.60586E-11 4.12695E-10 10.00000 3.68979E-17 4.84983E-16 1.05469E-14 5.59260E-14 5.78568E-13 7.60951E-12 3.34351E-11 1.69731E-10 Table A-2 Control Point Total Mean Hazard Curves for F=1.333 to 10.000 Hz SA(g)
F1.333Hz F2.000Hz F2.500Hz F3.333Hz F4.000Hz F5.000Hz F6.667Hz F10.000Hz 0.00100 2.97600E-02 3.48493E-02 3.62723E-02 3.75224E-02 3.77930E-02 3.81645E-02 3.82202E-02 3.77313E-02 0.00126 2.65506E-02 3.21114E-02 3.38195E-02 3.53947E-02 3.57773E-02 3.63123E-02 3.64411E-02 3.59214E-02 0.00158 2.37435E-02 2.96389E-02 3.15785E-02 3.34282E-02 3.39076E-02 3.45857E-02 3.47792E-02 3.42332E-02 0.00200 2.11348E-02 2.72658E-02 2.94020E-02 3.14960E-02 3.20640E-02 3.28745E-02 3.31287E-02 3.25592E-02 0.00251 1.83447E-02 2.42503E-02 2.64580E-02 2.87093E-02 2.93694E-02 3.03214E-02 3.06797E-02 3.01801E-02 0.00316 1.58370E-02 2.13995E-02 2.36122E-02 2.59493E-02 2.66784E-02 2.77417E-02 2.81938E-02 2.77761E-02 0.00398 1.35072E-02 1.84798E-02 2.05792E-02 2.28808E-02 2.36454E-02 2.47780E-02 2.53207E-02 2.50312E-02 0.00501 1.15233E-02 1.59602E-02 1.79364E-02 2.01743E-02 2.09557E-02 2.21287E-02 2.27380E-02 2.25556E-02 0.00631 9.69875E-03 1.33993E-02 1.51075E-02 1.70948E-02 1.78182E-02 1.89352E-02 1.95730E-02 1.95529E-02 0.00794 8.16871E-03 1.12572E-02 1.27335E-02 1.44950E-02 1.51602E-02 1.62126E-02 1.68587E-02 1.69597E-02 0.01000 6.87544E-03 9.45107E-03 1.07255E-02 1.22826E-02 1.28907E-02 1.38731E-02 1.45124E-02 1.47022E-02 0.01260 5.59934E-03 7.66580E-03 8.69878E-03 9.96405E-03 1.04737E-02 1.13152E-02 1.19210E-02 1.22217E-02 0.01580 4.57957E-03 6.24485E-03 7.08579E-03 8.11832E-03 8.54675E-03 9.26810E-03 9.83240E-03 1.01988E-02 0.02000 3.71435E-03 5.04411E-03 5.72288E-03 6.55840E-03 6.91559E-03 7.52859E-03 8.04505E-03 8.44690E-03 0.02510 2.88090E-03 3.94078E-03 4.49628E-03 5.17424E-03 5.48415E-03 6.00598E-03 6.49472E-03 6.91526E-03
Table A-2 Control Point Total Mean Hazard Curves for F=1.333 to 10.000 Hz SA(g)
F1.333Hz F2.000Hz F2.500Hz F3.333Hz F4.000Hz F5.000Hz F6.667Hz F10.000Hz 0.03160 2.19740E-03 3.03781E-03 3.49461E-03 4.04965E-03 4.32206E-03 4.76765E-03 5.22432E-03 5.64124E-03 0.03980 1.60091E-03 2.26175E-03 2.64612E-03 3.11708E-03 3.36987E-03 3.75954E-03 4.19169E-03 4.58792E-03 0.05010 1.16637E-03 1.68416E-03 2.00409E-03 2.40011E-03 2.62849E-03 2.96578E-03 3.36457E-03 3.73278E-03 0.06310 7.80127E-04 1.17225E-03 1.44093E-03 1.78792E-03 2.00140E-03 2.29256E-03 2.66382E-03 3.00374E-03 0.07940 5.22628E-04 8.17128E-04 1.03739E-03 1.33346E-03 1.52558E-03 1.77398E-03 2.11098E-03 2.41919E-03 0.10000 3.49578E-04 5.68786E-04 7.45904E-04 9.93374E-04 1.16166E-03 1.37134E-03 1.67136E-03 1.94675E-03 0.12600 2.09684E-04 3.58382E-04 4.89382E-04 6.84061E-04 8.23498E-04 9.87571E-04 1.24215E-03 1.49067E-03 0.15800 1.27114E-04 2.27986E-04 3.23901E-04 4.74724E-04 5.87963E-04 7.16066E-04 9.28865E-04 1.14777E-03 0.20000 7.54722E-05 1.42333E-04 2.10730E-04 3.24482E-04 4.13956E-04 5.12310E-04 6.86253E-04 8.74205E-04 0.25100 4.23115E-05 8.33354E-05 1.27794E-04 2.06297E-04 2.71582E-04 3.41172E-04 4.72434E-04 6.27582E-04 0.31600 2.33202E-05 4.78599E-05 7.58637E-05 1.28168E-04 1.74102E-04 2.22113E-04 3.17950E-04 4.41229E-04 0.39800 1.24479E-05 2.63605E-05 4.28226E-05 7.51000E-05 1.05090E-04 1.36280E-04 2.01360E-04 2.93150E-04 0.50100 6.65314E-06 1.45351E-05 2.41945E-05 4.40334E-05 6.34627E-05 8.36514E-05 1.27563E-04 1.94802E-04 0.63100 3.46882E-06 7.71155E-06 1.29763E-05 2.39689E-05 3.51409E-05 4.70793E-05 7.37687E-05 1.17989E-04 0.79400 1.81329E-06 4.10172E-06 6.97699E-06 1.30788E-05 1.95045E-05 2.65573E-05 4.27535E-05 7.16072E-05 1.00000 9.45489E-07 2.17633E-06 3.74227E-06 7.11976E-06 1.08009E-05 1.49476E-05 2.47258E-05 4.33740E-05 1.26000 4.76574E-07 1.11479E-06 1.93389E-06 3.68763E-06 5.61501E-06 7.84019E-06 1.32263E-05 2.40916E-05 1.58000 2.43659E-07 5.79015E-07 1.01317E-06 1.93625E-06 2.95896E-06 4.16774E-06 7.16756E-06 1.35458E-05 2.00000 1.21149E-07 2.92658E-07 5.16722E-07 9.89788E-07 1.51831E-06 2.15807E-06 3.78652E-06 7.43612E-06 2.51000 5.89780E-08 1.45111E-07 2.59326E-07 4.98841E-07 7.66768E-07 1.09536E-06 1.95446E-06 3.96121E-06 3.16000 2.81076E-08 7.04748E-08 1.27535E-07 2.46494E-07 3.79723E-07 5.45075E-07 9.89517E-07 2.07141E-06 3.98000 1.28687E-08 3.29136E-08 6.03765E-08 1.17438E-07 1.81403E-07 2.61407E-07 4.83215E-07 1.04616E-06 5.01000 5.89885E-09 1.53899E-08 2.86168E-08 5.60187E-08 8.67651E-08 1.25512E-07 2.36235E-07 5.28922E-07 6.31000 2.49628E-09 6.67335E-09 1.26149E-08 2.49329E-08 3.87615E-08 5.61937E-08 1.07575E-07 2.49836E-07 7.94000 1.06001E-09 2.90338E-09 5.57914E-09 1.11331E-08 1.73722E-08 2.52396E-08 4.91405E-08 1.18364E-07 10.00000 4.48623E-10 1.25909E-09 2.45964E-09 4.95561E-09 7.76162E-09 1.13012E-08 2.23792E-08 5.59141E-08
Table A-3 Control Point Total Mean Hazard Curves for F=13.333 to 100.000 Hz and PGA SA(g)
F13.333Hz F20.000Hz F25.000Hz F33.333Hz F40.000Hz F50.000Hz F100.000Hz PGA 0.00100 3.72074E-02 3.65853E-02 3.61238E-02 3.55185E-02 3.51004E-02 3.43948E-02 3.28472E-02 3.25880E-02 0.00126 3.53541E-02 3.46568E-02 3.41121E-02 3.33820E-02 3.28793E-02 3.20517E-02 3.02183E-02 2.99188E-02 0.00158 3.36288E-02 3.28670E-02 3.22508E-02 3.14145E-02 3.08406E-02 2.99120E-02 2.78479E-02 2.75170E-02 0.00200 3.19212E-02 3.11009E-02 3.04200E-02 2.94884E-02 2.88515E-02 2.78350E-02 2.55765E-02 2.52201E-02 0.00251 2.95757E-02 2.87593E-02 2.80408E-02 2.70369E-02 2.63523E-02 2.52749E-02 2.28829E-02 2.24950E-02 0.00316 2.72177E-02 2.64237E-02 2.56821E-02 2.46263E-02 2.39083E-02 2.27922E-02 2.03233E-02 1.99108E-02 0.00398 2.45575E-02 2.38322E-02 2.30932E-02 2.20146E-02 2.12834E-02 2.01600E-02 1.76904E-02 1.72542E-02 0.00501 2.21559E-02 2.14940E-02 2.07646E-02 1.96794E-02 1.89463E-02 1.78316E-02 1.53989E-02 1.49523E-02 0.00631 1.92800E-02 1.87425E-02 1.80552E-02 1.70027E-02 1.62943E-02 1.52330E-02 1.29324E-02 1.24788E-02 0.00794 1.67868E-02 1.63522E-02 1.57082E-02 1.46987E-02 1.40220E-02 1.30213E-02 1.08685E-02 1.04219E-02 0.01000 1.46081E-02 1.42591E-02 1.36589E-02 1.26997E-02 1.20596E-02 1.11239E-02 9.12780E-03 8.69801E-03 0.01260 1.22342E-02 1.19693E-02 1.14283E-02 1.05518E-02 9.96597E-03 9.12381E-03 7.33308E-03 6.93609E-03 0.01580 1.02839E-02 1.00838E-02 9.59747E-03 8.80104E-03 8.26851E-03 7.51416E-03 5.91807E-03 5.55714E-03 0.02000 8.58228E-03 8.43497E-03 8.00164E-03 7.28559E-03 6.80712E-03 6.13876E-03 4.73373E-03 4.41149E-03 0.02510 7.08252E-03 6.94635E-03 6.56082E-03 5.92756E-03 5.50516E-03 4.92179E-03 3.69711E-03 3.41908E-03 0.03160 5.81982E-03 5.68608E-03 5.34443E-03 4.78779E-03 4.41822E-03 3.91460E-03 2.85920E-03 2.62270E-03 0.03980 4.75387E-03 4.59979E-03 4.29579E-03 3.80772E-03 3.48743E-03 3.05976E-03 2.16193E-03 1.96441E-03 0.05010 3.88446E-03 3.72206E-03 3.45380E-03 3.02895E-03 2.75334E-03 2.39215E-03 1.63509E-03 1.47170E-03 0.06310 3.11747E-03 2.92979E-03 2.69136E-03 2.31966E-03 2.08674E-03 1.79251E-03 1.17647E-03 1.04501E-03 0.07940 2.50413E-03 2.30836E-03 2.09932E-03 1.77835E-03 1.58329E-03 1.34473E-03 8.47592E-04 7.43043E-04 0.10000 2.00975E-03 1.81706E-03 1.63594E-03 1.36196E-03 1.20001E-03 1.00768E-03 6.09875E-04 5.27634E-04 0.12600 1.53126E-03 1.35532E-03 1.20374E-03 9.78929E-04 8.52865E-04 7.06629E-04 4.11842E-04 3.50684E-04 0.15800 1.17329E-03 1.01709E-03 8.91381E-04 7.08461E-04 6.10457E-04 4.99184E-04 2.80389E-04 2.35062E-04 0.20000 8.89112E-04 7.54212E-04 6.51884E-04 5.05873E-04 4.30916E-04 3.47579E-04 1.87866E-04 1.54962E-04 0.25100 6.38794E-04 5.34739E-04 4.56381E-04 3.47112E-04 2.93223E-04 2.33629E-04 1.23329E-04 1.00200E-04 0.31600 4.50477E-04 3.73067E-04 3.14642E-04 2.35002E-04 1.97054E-04 1.55217E-04 8.01723E-05 6.41722E-05 0.39800 3.02511E-04 2.50146E-04 2.09158E-04 1.54577E-04 1.29123E-04 1.00896E-04 5.13715E-05 4.05688E-05 0.50100 2.03204E-04 1.67800E-04 1.39113E-04 1.01746E-04 8.46731E-05 6.56372E-05 3.29435E-05 2.56690E-05 0.63100 1.26230E-04 1.05889E-04 8.78596E-05 6.45536E-05 5.37565E-05 4.14714E-05 2.04731E-05 1.57676E-05 0.79400 7.85632E-05 6.69442E-05 5.55915E-05 4.10310E-05 3.41905E-05 2.62509E-05 1.27474E-05 9.70440E-06
Table A-3 Control Point Total Mean Hazard Curves for F=13.333 to 100.000 Hz and PGA SA(g)
F13.333Hz F20.000Hz F25.000Hz F33.333Hz F40.000Hz F50.000Hz F100.000Hz PGA 1.00000 4.88062E-05 4.22473E-05 3.51119E-05 2.60339E-05 2.17078E-05 1.65870E-05 7.92248E-06 5.96143E-06 1.26000 2.81031E-05 2.51690E-05 2.11246E-05 1.57759E-05 1.31185E-05 9.94258E-06 4.61374E-06 3.42504E-06 1.58000 1.63685E-05 1.51566E-05 1.28441E-05 9.65979E-06 8.01119E-06 6.02346E-06 2.71720E-06 1.99057E-06 2.00000 9.32194E-06 8.93680E-06 7.64955E-06 5.79541E-06 4.79296E-06 3.57391E-06 1.56541E-06 1.13107E-06 2.51000 5.15497E-06 5.15884E-06 4.45416E-06 3.36667E-06 2.75986E-06 2.03252E-06 8.55348E-07 6.07518E-07 3.16000 2.80001E-06 2.92724E-06 2.54637E-06 1.91573E-06 1.55451E-06 1.12956E-06 4.55724E-07 3.17985E-07 3.98000 1.46931E-06 1.60563E-06 1.40096E-06 1.04085E-06 8.32468E-07 5.95096E-07 2.28889E-07 1.56690E-07 5.01000 7.71776E-07 8.81428E-07 7.71350E-07 5.65892E-07 4.46098E-07 3.13735E-07 1.15053E-07 7.72773E-08 6.31000 3.78903E-07 4.49614E-07 3.91245E-07 2.80398E-07 2.16866E-07 1.49763E-07 5.23732E-08 3.45481E-08 7.94000 1.86552E-07 2.29964E-07 1.98987E-07 1.39327E-07 1.05731E-07 7.17013E-08 2.39158E-08 1.54951E-08 10.00000 9.15957E-08 1.17314E-07 1.00939E-07 6.90418E-08 5.14046E-08 3.42299E-08 1.08877E-08 6.92803E-09