Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation
ML23338A183
Person / Time
Site: LaSalle 
Issue date: 12/04/2023
From: Casey Smith
Constellation Energy Generation
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
RA23-067 LER 2023-002-00
Download: ML23338A183 (1)


LER-2023-002, Turbine Stop Valve Limit Switch Failure Due to Lubricant Degradation
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3732023002R00 - NRC Website

text

Constellation~

RA23-067 December 4, 2023 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001

.. ~

--~t

,)

f **

....: ~

LaSalle County Station, Unit 1 Renewed Facility Operating License No. NPF-11 NRC Docket No. 50-373 LdSalle County Station 2601 North 21 " Road Marseilles. IL 61341 815-415-2000 Telephone 10 CFR 50.73

Subject:

Licensee Event Report 2023-002-00, Turbine Stop Valve Limit Switch Failure due to Lubricant Degradation In accordance with 10 CFR 50.73(a)(2)(i)(B), Exelon Generation Company, LLC (EGC) is submitting Licensee Event Report (LER) Number 2023-002-00 for LaSalle County Station, Unit 1.

There are no regulatory commitments in this letter. Should you have any questions concerning this report, please contact Ms. Laura Ekern, Regulatory Assurance Manager, at (815) 415-2800.

Respectfully,

&U---

Christopher J. Smith Plant Manager LaSalle County Station

Enclosure:

Licensee Event Report cc:

Regional Administrator-NRC Region Ill NRC Senior Resident Inspector - LaSalle County Station

Abstract

On 9/7/2023 during surveillances of the turbine stop valves (TSV), limit switch 1 C71-N006G failed. The component was sent offsite for failure analysis. Component failure analysis was complete on 10/18/2023 and determined that the cause was attributed to degradation of switch lubricant which established firm evidence that a past inoperability condition existed.

The component 1 C71-N006G is the TSV-4 closure Reactor Protection System (RPS) channel A2 scram limit switch.

This device is required by technical specifications to support LCO 3.3.1.1 function 8 (RPS) and LCO 3.3.4.1 (End of Cycle - Recirculation Pump Trip or EOC-RPT). Each TSV position is monitored by two limit switches (for TSV-4, A2 and 82 channels). This condition results in the TSV-4 input to RPS A2 as well as one channel of the EOC-RPT trip being INOPERABLE. The appropriate LCO Conditions and Required Actions were entered and tracked. The RPS and EOC-RPT functions were maintained due to the redundant channels remaining OPERABLE. There were no reportability thresholds applicable to this issue at the time of the event, and there was no loss of safety function. The condition is reportable in accordance with 10 CFR 50.73(a)(2)(i)(B) for operation or condition prohibited by Technical Specifications.

Immediate corrective actions were taken to replace the component and restore the associated channel to OPERABLE.

Plant and System Identification

LaSalle Country Station Unit 1 is a General Electric Boiling Water Reactor with 3546 Megawatts Thermal Rated Core Power. The affected system was the main turbine system. The affected component was the turbine stop valve (TSV) limit switch 1C71-N006G. This is the limit switch for the TSV number 4 Closure Reactor Protection System (RPS) A2 channel.

Condition Prior to Event

Unit(s): 1 Reactor Mode(s): 1

Description

Date:

October 18, 2023 Mode(s) Name: Power Operation Time:

00:00 CDT Power Level: 100 percent On 09/07/2023 the limit switch on Unit 1 TSV-4 failed to actuate during surveillance testing. The limit switch is normally held in the actuated position during unit operation and only allowed to return to the relaxed, shelf state position, upon closure of the turbine stop valve. The failed limit switch, 1C71-N006G, was replaced and sent offsite for component testing and failure analysis. The component failure analysis (documented in report dated October 18, 2023) verified the limit switch malfunction and determined the cause was attributed to degradation of switch lubricant.

Cause

Analysis attributed the failure to the switch shaft and shaft bearing degraded lubrication causing the shaft to bind in the actuated (Turbine Stop Valve open) position.

The cause of the limit switch lubricant degradation was elevated temperatures due to a steam leak in close proximity. This steam leak has circumvented previous corrective actions such as use of high temperature switches and limit switch housing modifications.

Reportability and Safety Analysis

The component 1C71-N006G is the TSV-4 Closure RPS channel A2 scram limit switch. This device is required to be OPERABLE per LCO 3.3.1.1 Function 8 (RPS) and LCO 3.3.4.1 (EOC-RPT). TSV-4 was fully closed during the surveillance, which should have resulted in the 1 C71-N006G switch being open. Each TSV position is monitored by two limit switches (for TSV-4, A2 and B2 channels). This condition results in the TSV-4 input to RPS A2 as well as one channel of the EOC-RPT trip being INOPERABLE. The appropriate LCO Conditions and Required Actions were entered and tracked. The RPS and EOC-RPT functions were maintained due to the redundant channels remaining OPERABLE. There were no reportability thresholds applicable to this issue at the time of the event, and there was no loss of safety function.

00 Upon receipt of the failure analysis on October 18, 2023, the station was made aware that a past inoperability period existed from the test failure that occurred on September 7, 2023. The inoperability period was greater than allowed by TS LCO 3.3.1.1 and 3.3.4.1, as indicated below. This event is reportable in accordance with 10 CFR 50.73(a)(2)(i)(B) as a condition prohibited by the plant's TS.

LCO 3.3.1.1 requires that the RPS instrumentation for each function is OPERABLE, and Condition A applies to one or more required channels being inoperable requires that the channel or its associated trip system is placed in trip within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. In this case, the station had exceeded the completion time of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, when the

2. DOCKET NUMBER
3. LER NUMBER YEAR SEQUENTIAL REV 00373 2023 002 00 malfunctioning channel was found inoperable during September 2023 surveillance testing. In addition, LCO 3.3.1.1 Condition D was not entered for the Completion Time of Condition A not met.

LCO 3.3.4.1 requires that the EOC-RPT instrumentation is OPERABLE, which includes two channels of TSV closure and TCV fast closure or Minimum Critical Power Ratio (MCPR) limits are applied.

Corrective Actions

Corrective actions taken in response to the conditions were:

A work order was completed to replace the component, and to restore the associated channel to OPERABLE.

Performed component failure analysis at off-site testing facility.

Testing frequency was increased from 90 days to 45 days for the Unit 1 RPS A channel switches. Testing frequency will be reevaluated following steam leak repairs scheduled to occur in the next Unit 1 refueling outage.

Previous Occurrences

Unit 1 LER 373-2019-001-00 During quarterly surveillances of TSV limit switch 1C71-N006C, the component exhibited degraded performance on May 20, 2018 and a failure on September 9, 2018. The component was replaced; and subsequent component failure analysis determined the cause was attributed to degradation of the switch lubricant due to exposure from a high temperature environment, which established firm evidence that the sluggish performance exhibited in May 2018 was related to the failure in September 2018 and that a past inoperability condition existed. Immediate corrective actions were taken to replace the component and restore the associated channel to OPERABLE.

Additional actions included performance of a causal investigation, identification of a new limit switch model that has greater heat tolerance, with a component replacement schedule starting in 2019.

Unit 1 LER 373-2019-002-00 On March 23, 2019, during quarterly scram functional surveillances of turbine stop valves (TSV), the limit switch associated with TSV number 3 failed to return to shelf state when the lever arm was released. The failed component was replaced and sent offsite for component testing and failure analysis. The component failure analysis completed on May 3, 2019 determined the cause was attributed to insufficient lubrication in the shaft to bushing section of the limit switch. This established firm evidence that the failure mechanism and past inoperability condition may have existed since its last successful surveillance on December 15, 2018. Immediate corrective actions were taken to replace the component and restore the associated channel to OPERABLE. Additional actions included performance of a component failure analysis and to complete scheduled limit switch replacements of the current model with a new limit switch model that has greater heat tolerance.

Unit 2 LER 374-2022-002-00 On June 13, 2020, during functional testing surveillances of the turbine stop valves (TSV), the limit switch associated with TSV number 4 failed to return to shelf state when the lever arm was released. The failed component was replaced in the next available outage and sent offsite for component testing and failure analysis.

The component failure analysis completed on March 24, 2021 found only a small amount of grease on the internal components. It was determined the switch failed due to dried out and gritty grease, likely due to a missing boot which could have cause the limit switch to dry out. Immediate corrective actions were taken to restore the associated channel to OPERABLE.

Unit 1 LER 373-2022-001-00

2. DOCKET NUMBER
3. LER NUMBER YEAR SEQUENTIAL REV 00373 2023 002 00 On 12/4/21 during surveillances of TSV limit switches, 1C71-N006C failed. Component failure analysis was complete on 2/4/2022 and determined that the cause was attributed to degradation of switch lubricant which established firm evidence that a past inoperability condition existed. Immediate corrective actions were taken to replace the component and restore the associated channel to OPERABLE. Additional corrective actions included actions generated for Engineering to evaluation the surveillance frequency to determine if a frequency reduction to quarterly is appropriate.

Component Failure Data

Manufacturer: NAMCO Controls Corporation Device: Unit 1 Turbine Stop Valve limit switch (Model: EA700-80154)

Component ID: 1C71-N006G, Unit 1 Turbine Stop Valve Position Switch (Cat. ID 1791228) Page _4_ of _4 _