ML23150A026

From kanterella
Jump to navigation Jump to search
0c - Working Group
ML23150A026
Person / Time
Issue date: 05/17/2023
From: Markhenry Salley
Office of Nuclear Regulatory Research
To:
Hamburger K
Shared Package
ML23150A023 List:
References
Download: ML23150A026 (14)


Text

May 17, 2023 MarkHenry Salley P.E Office of Nuclear Regulatory Research Rockville, MD High Energy Arcing Fault PRA Methodology Workshop Introduction of NRC Members on the Joint NRC/EPRI HEAF Working Group (WG)

2 Mission Statement To advance the state of knowledge and improve understanding of risk from electrical arcing fault hazards in nuclear power plants (NPPs).

Goal Statements Characterize the primary factors that influence the occurrence and severity of arcing fault events (arc flash, arc blast, or HEAF).

Develop a risk model for arcing fault events based on experimental data, operating experience, and engineering judgement.

Analyze the plant impact of and quantify the change in risk from arcing fault events involving copper and aluminum.

NRC/EPRI HEAF Working Group (WG) Charter

3 Gabriel J. Taylor PE. Sr. Fire Protection Engineer (FXHAB)

Post-Fire Safe-Shutdown Analysis

Education:

Penn State University BS Electrical Engineering 2004

University of Maryland MS Fire Protection Engineering 2012

Joined NRC 2005, Graduated NRC Nuclear Safety Professional Development Program (NSPDP) 2007

NRC Federal Engineer of the Year 2015

NRC Meritorious service award 2019.

Code/Standards

NFPA 550, Guide for the Fire Safety Concepts Tree

NFPA 551, Guide for the Evaluation of Fire Risk Assessment

NFPA 801, Standard for Fire Protection for Facilities Handling Radioactive Materials

NFPA 803, Standard for Fire Protection for Light Water Nuclear Power Plants

NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric Generating Plants

NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants

NFPA 806, Performance-Based Standard for Fire Protection for Advanced Nuclear Reactor Electric Generating Plants Change Process

IEEE 383, Class 1E Cables for Nuclear Plants

IEEE 634, Cable Penetration Fire Stop Qualification Test

IEEE 1202, Vertical Tray Flame Test Protocol

IEEE 1844, Standard for Testing Fire Resistive Cables For Use in Nuclear Facilities

IEEE 2412, Standard Test Procedures for Determining Circuit Integrity Performance of Fire Resistive Cable in Tunnels and Safety Critical Transit Applications

Past Chair of IEEE Insulated Conductor Committee (ICC) Subcommittee D, Generating Station and Industrial Cables NRC WG Members - Office Nuclear Regulatory Research

4 Nicholas B. Melly PE. Fire Protection Engineer (FXHAB)

Fire Risk/PRA Development and Application Education:

University of Maryland BS Fire Protection Engineering 2008 Joined NRC in 2009,Graduated NRC Nuclear Safety Professional Development Program (NSPDP) in 2011 NRC Federal Engineer of Year 2023, Made Top 10 Professional Engineers in Federal Government Code/Standards NFPA 550, Guide for the Fire Safety Concepts Tree NFPA 551, Guide for the Evaluation of Fire Risk Assessments OECD/NEA NRC Representative FIRE International Fire Events Database HEAF International Working Group NRC WG Members - Office Nuclear Regulatory Research

5 Kenneth A. Hamburger PE. Fire Protection Engineer (FXHAB)

Computational Fire Modeling/Fire Dynamics Education:

University of Maryland BS Fire Protection Engineering 2012 University of Maryland MS Fire Protection Engineering 2013 Joined NRC in 2014, Graduated NRC Nuclear Safety Professional Development Program (NSPDP) in 2016 NRC Federal Engineer of the Year 2020 Code/Standards NFPA 801, Standard for Fire Protection for Facilities Handling Radioactive Materials NFPA 803, Standard for Fire Protection for Light Water Nuclear Power Plants NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric Generating Plants NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants NFPA 806, Performance-Based Standard for Fire Protection for Advanced Nuclear Reactor Electric Generating Plants Change Process OECD/NEA NRC Representative PRISME International Fire Modeling Program FAIR International Fire Modeling Program NRC WG Members - Office Nuclear Regulatory Research

6 Kenneth A. Miller Sr. Electrical Engineer (Electrical Team Lead)

Education West Virginia Institute of Technology BS Electrical Engineering 1983 Joined NRC in 2007 Baltimore Gan and Electric - Calvert Cliffs 1987-2007 Naval Surface Warfare Center 1984 - 1987 Past NRC Liaison for NERC and FERC (Electrical Grid)

Code/Standards IEEE NPEC Sub Committee 4 (past Chair and current member)

IEEE 308 Standard Criteria for Class 1E Power IEEE 741 Standard for Criteria for the Protection of Class 1E Power Systems and Equipment in Nuclear Power Generating Stations.

IEEE 387 Standard for Criteria for Diesel Generator Units Applied as Standby Power Supplies for Nuclear Power Generating Stations IEEE 765 Standard for Preferred Power Supply (PPS) for Nuclear Power Generating Stations (NPGS)

NRC Representative NEA/CNSI WGELEC NRC WG Members-Office Nuclear Regulatory Research

7 Thinh Dinh Fire Protection Engineer/Reliability & Risk Analyst Education Old Dominion University BS Electrical Engineering 1988 Joined NRC in 2006 Federal Aviation Administration 1995 - 2006 NUS Appendix R Consultant 1988 - 1995 JS Hyslop PhD.(Retired April 2023)

Sr. Reliability and Risk Engineer Education PhD Physics Virginia Tech 1990 Joined NRC in 1990 NRC Intern Development Program Worked in NRR and RES Fire Significance Determination Process (SDP)

NUREG/CR-6850 NFPA-805 Reviews NFPA-805 FAQ Program NRC WG Members - Office of Nuclear Reactor Regulation

8 Chris LaFleur PhD, PE Manager of the Risk & Reliability Analysis Department Education University of Rochester BS ME and Geology 1990 University of Maryland MS Fire Protection Engineering 1998 University of Michigan, Doctorate of Engineering 2007 Employment Sandia National Labs 2010 - present General Motors Corporation 1998 - 2010 Parsons Engineering Science 1991 - 1998 Codes & Standards Committee NFPA 2 Hydrogen Technology Code, Chair NFPA 13 Standard for the Installation of Sprinkler Systems 2018 C3E Award 2021 Society of Women Engineers Award NRC WG Members - Sandia National Laboratory

9 LIC 504 Reinaldo Rodriguez Sunil Weerakkody PhD Jen Whitman Antonios Zoulis Charles Moulton Duke Energy Constellation Additional RES Support Kevin Coyne PE., PhD Additional NRC NRR & RES Support to HEAF WG

10 Kevin McGrattan PhD Fire Dynamics Simulator (FDS) HEAF modeling Anthony D. Putorti Jr. PhD, PE Leads the HEAF experimental measurement program Additional NIST technical support:

Scott Bareham Edward Hnetkovsky Christopher Brown, PhD Wai Cheong Tam Eric Link Andre Thompson Michael Selepak Philip Deardorff Stephen Fink Michael Heck Ryan Falkenstein-Smith Additional NRC Support - National Institute for Standards and Technology (NIST) to HEAF WG

11 Additional Sandia National Laboratory support:

Anthony Tanbakuchi, PhD High speed photometrics and videography Austin Glover Small scale testing Kenneth Armijo, PhD Alvaro Augusto Cruz-Cabrera Paul Clem, PhD Byron Demosthenous Ryan Flanagan Raymond Martinez Jamal Mohmand James Taylor Rana Weaver Caroline Winters, PhD Additional NRC Support - Sandia National Laboratory (SNL) to HEAF WG

12 KEMA High Power Test Laboratory Frank Cielo Joe Duffy Matthew Muthard Samuel Andris Victor Savulyak Luiz Almada Alex Feldman Caren Yost Brendan Stanton Inc.(BSI) Electrical Contractors Robert Taylor, PE Benjamin Lee John Jones Jeff McKnight Additional NRC Support to HEAF WG

13 BelV, Belgium Canadian Nuclear Safety Commission (CNSC), Canada The Institut de Radioprotection et de Sûreté Nucléaire (IRSN), France The Gesellschaft für Anlagen-und Reaktorsicherheit (GRS) gGmbH, Germany Nuclear Regulation Authority (NRA), Japan Central Research Institute of Electric Power Industry (CRIEPI), Japan Korea Institute of Nuclear Safety (KINS), Korea Authority for Nuclear Safety and Radiation Protection (ANVS), the Netherlands Consejo de Seguridad Nuclear (CSN), Spain United States Nuclear Regulatory Commission (US NRC), USA Chairman-Koji SHIRAI, Dr. Eng., Distinguished Research Scientist

Nuclear Risk Research Center (NRRC) Central Research Institute of Electric Power Industry (CRIEPI)

Vice Chairman-Sylvain Suard, Head of the fire test laboratory, Institut de radioprotection et de sûreté nucléaire, IRSN Program Secretariat -Dr. Markus Beilmann NEAs Division of Nuclear Safety Technology and Regulation Additional NRC Support to HEAF WG OECD/NEA Member Countries HEAF Phase II

14 NRC/EPRI HEAF Working Group + Support = Total Team Effort "The way a team plays as a whole determines its success.

You may have the greatest bunch of individual stars in the world, but if they dont play together, the club wont be worth a dime." - Babe Ruth "A group becomes a team when each member is sure enough of himself and his contribution to praise the skills of others."

- Norman Shidle "It is amazing what you can accomplish if you do not care who gets the credit." - Harry Truman