ND-22-0658, ITAAC Closure Notification on Completion of ITAAC 2.2.03.08c.iii (Index Number 182)

From kanterella
(Redirected from ML22230D050)
Jump to navigation Jump to search
ITAAC Closure Notification on Completion of ITAAC 2.2.03.08c.iii (Index Number 182)
ML22230D050
Person / Time
Site: Vogtle 
Issue date: 08/18/2022
From: Coleman J
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ITAAC 2.2.03.08C.iii, ND-22-0658
Download: ML22230D050 (6)


Text

>-. Southern Nuclear Jamie M. Coleman Regulatory Affairs Director Vogtle 3 & 4 AUG 1 8 2022 Docket No.:

52-026 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 4 7825 River Road Waynesboro, GA 30830 706-848-6926 tel ND-22-0658 10 CFR 52.99(c)(1)

ITAAC Closure Notification on Completion of ITAAC 2.2.03.08c.iii [Index Number 182)

Ladies and Gentlemen:

In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP) Unit 4 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.2.03.08c.iii [Index Number 182) for verifying that the routing of the Core Makeup Tank (CMT) inlet lines from the cold leg and Passive Residual Heat Removal Heat Exchanger (PRHR HX) inlet line from the hot leg have no downward sloping sections between the connection to the Reactor Coolant System (RCS) and the high point of the lines. The closure process for this ITAAC is based on the guidance described in NEI 08-01, "Industry Guideline for the ITAAC Closure Process under 1 O CFR Part 52," which was endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 1 O CFR 52.99.

If there are any questions, please contact Kelli Roberts at 706-848-6991.

Respectfully submitted,

~=ma~~

Regulatory Affairs Director Vogtle 3 & 4

Enclosure:

JMC/GES/sfr Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.2.03.08c.iii [Index Number 182)

U.S. Nuclear Regulatory Commission ND-22-0658 Enclosure Page 2 of 3 To:

Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena Ill Mr. D. L. McKinney Mr. H. Nieh Mr. G. Chick Mr. S. Stimac Mr. P. Martino Mr. D. Pitts Mr. J.B. Williams Mr. A. S. Parton Ms. K. A. Roberts Ms. J.M. Coleman Mr. C. T. Defnall Mr. C. E. Morrow Mr. K. J. Drudy Mr. J. M. Fisher Mr. R. L. Beilke Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 Nuclear Regulatory Commission Mr. M. King Mr. G. Bowman Ms. A. Veil Mr. C. P. Patel Mr. G. J. Khouri Mr. C. J. Even Mr. B. J. Kemker Ms. N. C. Coovert Mr. C. Welch Mr. J. Gaslevic Mr. 0. Lopez-Santiago Mr. G. Armstrong Mr. M. Webb Mr. T. Fredette Mr. C. Santos Mr. B. Davis Mr. J. Vasquez Mr. J. Eargle Ms. K. Mccurry Mr. J. Parent Mr. B. Griman Mr. V. Hall

U.S. Nuclear Regulatory Commission ND-22-0658 Enclosure Page 3 of 3 Oglethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. S. M. Jackson Dalton Utilities Mr. T. Bundros Westinghouse Electric Company, LLC Dr. L. Oriani Mr. D. C. Durham Mr. M. M. Corletti Mr. Z. S. Harper Ms. S.L. Zwack Other Mr. S. W. Kline, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.

Dr. W. R. Jacobs, Jr., Ph.D., GOS Associates, Inc.

Mr. S. Roetger, Georgia Public Service Commission Mr. R. L. Trokey, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. S. Blanton, Balch Bingham

U.S. Nuclear Regulatory Commission ND-22-0658 Enclosure Page 1 of 3 Southern Nuclear Operating Company ND-22-0658 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.2.03.0Bc.iii [Index Number 182]

U.S. Nuclear Regulatory Commission ND-22-0658 Enclosure Page 2 of 3 ITAAC Statement Design Commitment 8.c) The PXS provides RCS makeup, boration, and safety injection during design basis events.

Inspections/Tests/ Analyses iii) Inspections of the routing of the following pipe lines will be conducted:

CMT inlet line, cold leg to high point PRHR HX inlet line, hot leg to high point Acceptance Criteria iii) These lines have no downward sloping sections between the connection to the RCS and the high point of the line.

ITAAC Determination Basis Multiple IT AAC are performed to demonstrate that the Passive Core Cooling System (PXS) provides Reactor Coolant System (RCS) makeup, boration, and safety injection during design basis events. This ITAAC requires that inspections be conducted to verify that the routing of the Core Makeup Tank (CMT) inlet lines from the cold leg and the Passive Residual Heat Removal Heat Exchanger (PRHR HX) inlet line from the hot leg have no downward sloping sections between the connection to the RCS and the high point of the lines.

The inspection of the routing of each CMT and PRHR HX inlet lines was performed during a walk-down of the as-built lines in accordance with the site walk down inspection procedure (Reference 1). When required to confirm the downward slope or lack of a downward slope, the slope of the lines was determined using Measurement and Test Equipment in accordance with site procedures (Reference 2).

The inspection results are documented in the Unit 4 inspection report (Reference 3) and determined that each CMT and the PRHR HX inlet lines have no downward sloping sections between their connection to the RCS and their respective high point of the line which meets the ITAAC acceptance criteria.

References 1 through 3 are available for NRC inspection as part of the Unit 4 ITAAC 2.2.03.08c.iii Completion Package (Reference 4).

ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performed a review of all IT AAC findings pertaining to the subject ITAAC and associated corrective actions. This review found that there are no relevant ITAAC findings associated with this ITAAC. The ITAAC completion review is documented in the ITAAC Completion Package for ITAAC 2.2.03.0Sc.iii (Reference 4) and available for NRC review.

U.S. Nuclear Regulatory Commission ND-22-0658 Enclosure Page 3 of 3 ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 2.2.03.08c.iii was performed for VEGP Unit 4 and that the prescribed acceptance criteria are met.

Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.

References (available for NRC inspection)

1. NCSP 02-24, Rev 6.00 "ITAAC Support Activities (AP, 000)"
2. 26139-000-4MP-T81 C-N7102, Rev 9 "Control of Measuring and Test Equipment"
3. SV4-PXS-ITR-800182, Rev 0 "Unit 4 ITAAC 182 Walkdown 2.2.03.0Bc.iii NRC Index Number 182"
4. 2.2.03.08c.iii-U4-CP-Rev0, ITAAC Completion Package