ML22131A336
| ML22131A336 | |
| Person / Time | |
|---|---|
| Issue date: | 05/13/2022 |
| From: | Office of Nuclear Regulatory Research |
| To: | |
| References | |
| DG-1402, RG-1.250 | |
| Download: ML22131A336 (12) | |
Text
Draft Regulatory Guide DG-1402 Proposed new Regulatory Guide 1.250 Dedication of Commercial-Grade Digital I&C Items for Use in Nuclear Power Plants" April 13, 2022 - Public Meeting 1
Webinar Ground Rules
- Meeting Leader: Michael Eudy
- Keep phones on mute
- Video encouraged for NRC staff
- Raise hand during public session
- Send email for attendance records
- Contact Michael.Eudy@nrc.gov
- Slides can be sent via email 2
Meeting Agenda for 3-5pm
- Opening Remarks - NRC
- Status, Purpose & Scope of DG-1402 - NRC
- NRC Clarifications on NEI 17-06, Rev. 1 - NRC
- DG-1402 Milestone Schedule - NRC
- NEI Comments on DG-1402 - NEI
- Public comments on DG-1402 - Others
- Adjourn - NRC 3
DG-1402 Status
- Issued for public comment 3/18/2022
- Comment period ends 4/18/2022
- FederalRegister.gov search 87 FR 15456 or DG-1402
- DG-1402 is newly proposed RG 1.250
- Meeting and comment contact:
- Michael.Eudy@nrc.gov 4
Opening remarks on DG-1402 Eric Benner, Director Division of Engineering
& External Hazards Office of Nuclear Reactor Regulation 5
Purpose & Scope of DG-1402 - Dinesh Taneja
- Endorse NEI 17-06, Revision 1
- Endorse applicable parts of the industry consensus Std. IEC 61508, 2.0 Edition
- Endorse applicable parts of the industry consensus Std. ISO/IEC 17065:2012
Clarifications on NEI 17-06, Rev. 1 (1 of 3)
- The NRC staff considers SIL certification to be a commercial grade survey for the purposes of Part 21
- The NRC staff considers dedication of the Certifying Bodys (CBs) services and verification of SIL certification to be adequate for verifying dependability critical characteristics
- Each dedicating entity should dedicate the services of each CB and should not rely on dedication by, e.g., another NRC licensee 7
Clarifications on NEI 17-06, Rev. 1 (2 of 3)
- In keeping with NRC staff-accepted practices, the CBs SIL certification process should be observed every 3 years
- In accordance with 10 CFR 21.3, the NRC use of the term basic component includes dedicated commercial grade items
- Dedicating entities should take measures to avoid the acceptance of expired, counterfeit or fraudulent SIL certificates 8
Clarifications on NEI 17-06, Rev. 1 (3 of 3)
- The NRC staff is not endorsing the use of SIL certification by CBs that have not been accredited in conformance with IEC 61508
- Dedicating entities should verify that the substantive requirements of the later editions related to the dependability characteristics remain unchanged from the IEC 61508, 2.0 Edition
- The NRC staff endorses the use of ISO/IEC 17065:2012 by CBs to perform commercial grade surveys as described in NEI 17-06 9
DG-1402/RG 1.250 Milestones Public meeting for comments on DG-1402 13-Apr-2022 Comment period ends 18-Apr-2022 NRC staffs resolution of comments on DG-1402 Late May-2022 Internal reviews complete for RG 1.205 Mid July-2022 Meeting with the Advisory Committee on Reactor Safeguards TBD Issuance of RG 1.205 Fall 2022 10
Public Comment Discussion 11
Meeting Adjourned
Contact:
Michael.Eudy@nrc.gov at 301-415-3104 12