FERC - NERC - Regional Entity Staff Report: The February 2021 Cold Weather Outages in Texas and the South Central United States FERC/NERC/Regional Entity Inquiry Dave Huff Office of Electric Reliability Heather Polzin Office of Enforcement March 31, 2022
Disclaimer The views expressed herein are ours, and do not necessarily reflect the views of the Commission, individual Commissioners, Commission staff, or individual Commission staff members.
2
Inquiry Commencement Largest firm load shed event in U.S. history (23,418 MW)
Fourth event in the past 10 years in which cold weather-related unplanned generating unit outages jeopardized bulk-power system reliability Joint Inquiry initiated on February 16, 2021 3
Minimum Temperatures (Deg. F) and Departure from Average Daily Minimum Deviation (Deg. F.)
Cold Weather Conditions February 15, 2021 (Source: NOAA)
Deviations up to 40-50 degrees from the normal low temperatures -February 15, 2021 Actual low temperature values shown on map 4
Largest U.S. monthly decline of natural gas production on record.
Between February 8 and 17, the total natural gas production in the U.S. Lower 48 fell by 28 percent, while Texas production declined 70.1 percent (as compared to January average).
Most producing regions of the U.S. saw a sharp decline and recovery.
Effect on Natural Gas System 5
Unprecedented Generation Shortfalls 1,045 individual generating units experienced 4,124 outages, derates or failures to start, of which 604 (58 percent of all units) were natural gas-fired generators.
Less than 1% nuclear generation experienced outages or derates.
6
ERCOT, SPP, and MISO Balancing Authorities declared Energy Emergencies and ordered firm load shed at different points of time, in total 23,418 MW:
ERCOT: nearly three consecutive days and at its worst point, 20,000 MW, SPP: over four hours total and at its worst point, 2,718 MW, and MISO (MISO South):
over two hours and at its worst point, 700 MW.
Generation Shortfalls Led to Energy Emergencies ERCOT Low Frequency Excursion 7
Causes of Generation Shortfalls 75 percent of the generating unit outages, derates, and failures to start, were caused by:
- Freezing Issues (44 percent)
- Fuel Issues (31 percent).
Out of all outages and derates caused by Fuel Issues, 87 percent were:
- Natural Gas Fuel Supply issues (27 percent of total outages, derates, etc.).
8
28 Recommendations Nine key recommendations, including recommendations for NERC Reliability Standards changes that go above and beyond the Reliability Standards revisions to address cold weather accepted by the Commission in August 2021. (See 176 FERC ¶ 61,119 (2021))
Five recommendations for further study, which includes study of ERCOT black start unit availability during cold weather Each have recommended timeframes for implementation (e.g.,
before Winter 2022/2023, before Winter 2023/2024)
Some could extend beyond winter 2023-2024, but should be completed as soon as possible 9
Recommendations:
New or revised Reliability Standards Identification and protection of cold weather critical components Account for effects of precipitation and cooling effect of wind Corrective action plans for generating units that fail due to freezing issues Annual training for cold weather preparedness Retrofit or design (if building new) generating units to operate to specific extreme cold weather conditions 10
GOs/GOPs to provide percentage of total unit capacity that BA can rely on during local forecasted cold weather, including reliability risks related to natural gas fuel contracts Entities involved in load shedding to take actions to protect critical natural gas infrastructure from losing power during demand response and load shedding events Separation of circuits used for manual load shedding from UFLS/UVLS circuits, use UFLS/UVLS circuits for manual load shedding as last resort Recommendations:
New or revised Reliability Standards 11
Recommendations:
Natural Gas Infrastructure Reliability Congress, state legislatures and regulators with jurisdiction over natural gas infrastructure should require those natural gas infrastructure facilities to have cold weather preparedness plans, including measures to prepare to operate during a weather emergency. (Key Rec. 5)
Natural gas infrastructure entities undertake voluntary measures to prepare for cold weather (Report provides a list of measures that can performed with long-or short-lead-times) (Key Rec. 6) 12
Team proposed a forum in which representatives of state legislatures and/or regulators with jurisdiction over natural gas infrastructure, in cooperation with FERC, NERC, and the Regional Entities, and with input from the grid operators and gas infrastructure entities, identify concrete actions (consistent with the forum participants jurisdiction) to improve the reliability of the natural gas infrastructure system necessary to support bulk-power system reliability.
(Key Rec. 7)
Recommendation:
Natural Gas - Electric Forum 13
24 other recommendations, including:
- Identify and communicate reliability risks of natural gas fuel contracts.
- Conduct technical conference to discuss how to improve generator winter readiness - planned for April 27-28, 2022.
- Inspection and maintenance of freeze protection measures at specific winter weather timeframes.
- Improve reserve margin projections for winter peak conditions.
Other Recommendation Areas 14
https://www.ferc.gov/media/february-2021-cold-weather-outages-texas-and-south-central-united-states-ferc-nerc-and The full report can be found at: