ML21306A180

From kanterella
Jump to navigation Jump to search
United Controls International - Part 21 Notification for York Pin: TCM-1 a Temperature Control Modules
ML21306A180
Person / Time
Site: South Texas  STP Nuclear Operating Company icon.png
Issue date: 10/28/2021
From: Hale R
United Controls International
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
55551
Download: ML21306A180 (3)


Text

Oct 28 21 05:11 p Kulkarni 7704109610 p.1 LIN11EO CONTROLS INTERNATIONAL I0CFR21 NOTIFICATION LETTER October 28, 2021 U.S. Nuclear Regulatory Commission Document Control Desk Washington D.C. 20555-0001

Subject:

1 0CFR21 Notification for York PIN: TCM-1 A Temperature Control Modules The purpose of this letter is to provide the NRC with a report in general conformity of the requirements of 1 0CFR Part 21.21. On June 18, 2021 S TP Nuclear Operating Company returned a York PIN: TCM-lA temperature control module with the reported issue that the module would not respond in auto or manual vane control and that internal relays IR and 2R would not pick up.

The subject temperature control module was previously supplied by STP Nuclear Operating Company to UCI for refurbishment and modification, after which was supplied by UCI on March 13, 2017. Troubleshooting performed by UCI identified that the secondary of the Basler Electric BE13410001 transformer (component Tl) that is used to isolate and step down the input voltage from 115V AC to 22V AC had an open circuit. When the subject transformer was bypassed the module operated as designed. UCI is unable to determine the cause of the transformer failure. Post refurbishment/modification testing performed by UCI included verifying functionality of the unit before and after performance of a 48 hr. burn-in period.

Required information as per 10CFRPart 21.2l(d)(4) follows:

(i)

Name and Address of the individual or individuals informing the Commission Rob Hale President United Controls International 205 Scientific Drive Norcross, GA 30092 (ii)

Identification of the facility, the activity, or the basic component supplied for such facility or such activity within the United States which fails to comply or contains a deject.

Basler Electric BE13410001 115/22V Transformer installed in York TCM-lA Temperature Control Module (iii)

Identification of the firm constructing the facility or supplying the basic component which fails to comply or contains a defect.

United Controls International 205 Scientific Drive Norcross, GA 30092 Page 1 of3

Oct 28 21 05:11 p Kulkarni 7704109610 p.2 UNl-:-ED CONTROLS INTERNATIONAL (iv)

Nature of the defect or failure to comply and the safety hazard which is created or could be created by such defect or failure to comply.

Failure of the subject transformer will result in an open circuit at the input power to the temperature control module resulting in the module being inoperable.

(v)

The date on which the information of suc/1 defect or failure to comply was obtained.

UCI issued a Return Material Authorization on November 11, 2020 & the items were received at UCI for evaluation on June 18, 2021.

(i*i)

In the case of a basic component wl1ich contains a defect or fails to comply, the number and location of these components in use at, supplied for, being supplied for, or may be supplied for, manufactured or being mamifacturedfor one or more facilities or activities subject to the regulations in this Part.

I The following temperature control modules were supplied by STP Nuclear Operating Company for safety-related refurbishment and/or modification by UCI and were determined as containing or are likely to contain the subject transformer.

Part Number Utilitv Purchase Order Ouantitv TCM-lA STPNuclear 198062 5

or Operating 210878 1

UCI-TCM-lA Company 215856 I

254556 1

254559 I

(vii)

The corrective action which has been, is being, or will be taken; the name of the individual or organization responsible/or the action; and the length of time that has been or will be taken to complete the action.

UCI has implemented an increased energized burn-in test period from 48hr. to 100hr. to provide greater assurance that the transformers installed on the modules will not fail in the manor described here-in. Prior to and following the burn-in period the modules are subjected to functional testing.

(viii)

Any Advice related to the defect or failure to comply about the facility, activity, or basic component that has been, is being, or will be given to purchasers or licensees.

None.

(ix)

In the case of an early site permit, the entities to whom an early site permit was transferred.

Not Applicable.

Page 2 of3

Oct 28 21 05:11 p Kulkarni 7704109610 UNITED CONTROLS INTERNATIONAL If you have any questions or wish to discuss this matter or this report, please contact:

Wesley Hick.le Engineering Manager whickle@.unitedcontrols.com 470-610-0870

~r:~JN Rob Hale President United Controls International p.3 Page 3 of3