Zone of Influence (ZOI)

  • NUREG/CR-6850 Definition (generic): A volume surrounding an ignition source where all intervening combustibles and targets may be adversely affected by a fire initiated by the ignition source.
  • NUREG/CR-6850 (HEAF-specific severity factors): High-energy arcing faults are modeled assuming damage to a predefined zone of influence. The severity factor is 1.0 due to the assumption that the fire will propagate and/or damage equipment within the zone of influence.

ZOI Illustration (NUREG/CR-6850 Appendix M, Figure M-1)

Does Al HEAF Require a Change to Modeled ZOI?

It is a safety concern warranting action

  • OECD non-prototypic test but no ZOI measured It is not a safety concern
  • Cables very robust
  • ~100,000 of component operating years with Al widespread
  • No op ex shows an increased ZOI
  • Actual ZOI bounded by currently modeled ZOI
  • Cables within ZOI functional
  • Robinson within modeled ZOI
  • Appendix R separation - change in ZOI would have to be very large