ML21084A114

From kanterella
Jump to navigation Jump to search
Gutor Electronic LLC, Interim Notification of Potential Defect - 10 CFR Part 21
ML21084A114
Person / Time
Site: Comanche Peak 
Issue date: 02/12/2021
From: Schu M
Gutor Electronic LLC
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML21084A114 (1)


Text

Gutor technology U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Attention : Document Control Desk Life Is C:>n I Scb:i11eider i:, Electric GUTOR Electronic LLC Quality Assurance Hardstrasse 74, 5430 Wettingen Switzerland E-mail: marne.schu@se.com February 12th, 2021

Subject:

Interim Notification of Potential Defect - 10 CFR Part 21

Reference:

Potential Defect of Basic Components (A070) controller boards Product: (A070) Controller Board of Gutor UPS systems Gutor Electronic LLC ("Gutor") provided Class 1 E Uninterruptible Power Supplies (UPS) to US nuclear sites which 10 CFR Part 21 applies. Gutor is currently determining the affected sites.

At the time these UPS's were provided, they underwent an appropriate Class 1 E qualification testing.

However, during a recent Class 1 E qualification by a third party, the internal safety related controller board (A070) in the UPS exhibited a behavior that could potentially cause an unintentional shutdown of the UPS.

On January 19th, 2021, an independent Schneider Electric laboratory reported to Gutor that a socket of non-compliant quality was mated with aged Micro Processor Unit (MPU) chips installed on the (A070) controller boards of the Class 1 E UPS. Gutor is engaged in an intensive root cause analysis investigation of this abnormal behavior.

Within 60 days following the date of this notification, Gutor shall submit a final report or a second interim report documenting the results to date of our evaluation to determine whether this issue involving the UPS deviation could be associated with a substantial safety hazard at any of the US nuclear plants to which similar controller board were provided by Gutor.

For questions or clarifications, please contact me at 41-79-417-2803.

On behalf of Gutor Electronic LLC, I remain at your disposal for any further clarifications.

Yours sincerely, Marne Schu 1 -v Gutor Customer Satisfaction & Quality Director Schneider Electric Gutor Electronic LLC Hardstrasse 72-74 5430 Wettingen I Switzerland Phone: + 41 (0) 56 437 3434 schne1der-electnc.com/gutor