L-21-053, Supplemental Information Regarding Application to Revise Technical Specifications to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements

From kanterella
(Redirected from ML21034A417)
Jump to navigation Jump to search

Supplemental Information Regarding Application to Revise Technical Specifications to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements
ML21034A417
Person / Time
Site: Perry 
Issue date: 02/02/2021
From: Penfield R
Energy Harbor Nuclear Corp
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-21-053
Download: ML21034A417 (24)


Text

Energy Harbor Nuclear Corp.

Perry Nuclear Power Plant 10 Center Road P.O. Box 97 Perry, Ohio 44081 Rod L. Penfield Site Vice President, Perry Nuclear 440-280-5382 February 2, 2020 L-21-053 10 CFR 50.90 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

SUBJECT:

Perry Nuclear Power Plant, Unit No. 1 Docket No. 50-440, License No. NPF-58 Supplemental Information Regarding Application to Revise Technical Specifications to Adopt TSTF-582, "Reactor Pressure Vessel Water Inventory Control (RPV WIC)

Enhancements" By [[letter::L-20-166, Application to Revise Technical Specifications to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements|letter dated September 24, 2020]] (Accession No. ML20268C198), Energy Harbor Nuclear Corp. submitted a request for an amendment to the Perry Nuclear Power Plant, Unit No. 1 (PNPP) Technical Specifications (TSs) to incorporate the Nuclear Regulatory Commission (NRC)-approved TSTF-582, Reactor Pressure Vessel Water Inventory Control Enhancements.

By electronic communication dated January 21, 2021, the NRC requested clarification of items marked for change in Surveillance Requirement (SR) 3.8.2.1 within the subject amendment. This letter provides the information to clarify SR 3.8.2.1. Additionally, an administrative change to comply with the use of logical connectors as described in Section 1.2 of the TSs was made to the Required Actions of Condition A in TS 3.3.5.2.

Because the additional information includes changes to the proposed TS pages that were previously provided, new mark-up pages of the existing TS and revised (clean) TS pages are provided in Attachments 1 and 2, respectively. These new TS pages supersede the pages previously provided under Accession No. ML20268C198. The information provided has no impact on the no significant hazards consideration analysis.

There are no regulatory commitments contained in this submittal. If there are any questions or if additional information is required, please contact Mr. Phil H. Lashley, Manager - Fleet Licensing, at (330) 696-7208.

Perry Nuclear Power Plant, Unit No. 1 L-21-053 Page 2 I declare under penalty of perjury that the foregoing is true and correct. Executed on February 2, 2020.

Sincerely, Rod L. Penfield Attachments:

1. Proposed Technical Specification Changes (Mark-up)
2. Proposed Technical Specification Changes (Re-typed) [Provided for Information Only]

cc:

NRC Region III Administrator NRC Resident Inspector NRR Project Manager Executive Director, Ohio Emergency Management Agency Utility Radiological Safety Board L-21-053 Proposed Technical Specification Changes (Mark-Up)

(11 pages follow)

Definitions 1.1 PERRY - UNIT 1 1.0-2a Amendment No. 184 1.1 Definitions (continued)

DRAIN TIME The DRAIN TIME is the time it would take for the water inventory in and above the Reactor Pressure Vessel (RPV) to drain to the top of the active fuel (TAF) seated in the RPV assuming:

a)

The water inventory above the TAF is divided by the limiting drain rate; b)

The limiting drain rate is the larger of the drain rate through a single penetration flow path with the highest flow rate, or the sum of the drain rates through multiple penetration flow paths susceptible to a common mode failure (e.g., seismic event, loss of normal power, single human error), for all penetration flow paths below the TAF except;

1. Penetration flow paths connected to an intact closed system, or isolated by manual or automatic valves that are closed and administratively controlled locked, sealed, or otherwise secured in the closed position, blank flanges, or other devices that prevent flow of reactor coolant through the penetration flow paths;
2. Penetration flow paths capable of being isolated by valves that will close automatically without offsite power prior to the RPV water level being equal to the TAF when actuated by RPV water level isolation instrumentation; or
3. Penetration flow paths with isolation devices that can be closed prior to the RPV water level being equal to the TAF by a dedicated operator trained in the task, who is in continuous communication with the control room, is stationed at the controls, and is capable of closing the penetration flow path isolation devices without offsite power.

c)

The penetration flow paths required to be evaluated per paragraph b) are assumed to open instantaneously and are not subsequently isolated, and no water is assumed to be subsequently added to the RPV water inventory; (continued)

Technical Specification Mark-up

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43a Amendment No. 184 3.3 INSTRUMENTATION 3.3.5.2 Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation LCO 3.3.5.2 The RPV Water Inventory Control instrumentation for each Function in Table 3.3.5.2-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.5.2-1.

ACTIONS


NOTE---------------------------------------------------------

Separate Condition entry is allowed for each channel.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more channels inoperable.

A.1 Enter the Condition referenced in Table 3.3.5.2-1 for the channel.

Immediately AB. One or more channels inoperable.As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

A.1 Initiate action to place channel in trip.

OR AB.2.1 Declare associated penetration flow path(s) incapable of automatic isolation.

AND AB.2.2 Initiate action to cCalculate DRAIN TIME.

Immediately Immediately Immediately C. As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

C.1 Place channel in trip.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> (continued)

Technical Specification Mark-up

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43b Amendment No. 184 ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D. As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

D.1 Declare HPCS system inoperable.

OR D.2 Align the HPCS pump suction to the suppression pool.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 1 hour E. As required by Required Action A.1 and referenced in Table 3.3.5.2-1.

E.1 Restore channel to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> F. Required Action and associated Completion Time of Condition C, D, or E not met.

F.1 Declare associated ECCS injection/spray subsystem inoperable.

Immediately Technical Specification Mark-up

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43c Amendment No. 184 SURVEILLANCE REQUIREMENTS


NOTE---------------------------------------------------------

These SRs apply to each Function in Refer to Table 3.3.5.2-1 to determine which SRs apply for each ECCS Function.

SURVEILLANCE FREQUENCY SR 3.3.5.2.1 Perform CHANNEL CHECK.

In accordance with the Surveillance Frequency Control Program SR 3.3.5.2.2 Perform CHANNEL FUNCTIONAL TEST.

In accordance with the Surveillance Frequency Control Program SR 3.3.5.2.3 Perform LOGIC SYSTEM FUNCTIONAL TEST.

In accordance with the Surveillance Frequency Control Program Technical Specification Mark-up

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43d Amendment No. 184 Table 3.3.5.2-1 (page 1 of 12)

RPV Water Inventory Control Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS PER FUNCTION CONDITIONS REFERENCED FROM REQUIRED ACTION A.1 SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE

1. Low Pressure Coolant Injection-A (LPCI) and Low Pressure Core Spray (LPCS) Subsystems
a. Reactor Vessel Pressure - Low (LPCS Injection Valve Permissive) 4, 5 1(a)

C SR 3.3.5.2.1 SR 3.3.5.2.2 482.7 psig and 607.7 psig

b. LPCS Pump Discharge Flow - Low (Bypass) 4, 5 1(a)

E SR 3.3.5.2.1 SR 3.3.5.2.2 1200 gpm

c. Reactor Vessel Pressure - Low (LPCI Injection Valve Permissive) 4, 5 1(a)

C SR 3.3.5.2.1 SR 3.3.5.2.2 490.0 psig and 537.1 psig

d. LPCI Pump A Discharge Flow - Low (Bypass) 4, 5 1(a)

E SR 3.3.5.2.1 SR 3.3.5.2.2 1450 gpm

e. Manual Initiation 4, 5 1(a)

E SR 3.3.5.2.3 NA

2. LPCI B and LPCI C Subsystems
a. Reactor Vessel Pressure - Low (LPCI Injection Valve Permissive) 4, 5 1 per subsystem (a)

C SR 3.3.5.2.1 SR 3.3.5.2.2 490.0 psig and 537.1 psig for LPCI B; and 490.0 psig and 537.1 psig for LPCI C

b. LPCI Pump B and LPCI Pump C Discharge Flow - Low (Bypass) 4, 5 1 per pump (a)

E SR 3.3.5.2.1 SR 3.3.5.2.2 1450 gpm

c. Manual Initiation 4, 5 1(a)

E SR 3.3.5.2.3 NA (continued)

(a)

Associated with an ECCS subsystem required to be OPERABLE by LCO 3.5.2, Reactor Pressure Vessel (RPV) Water Inventory Control.

Technical Specification Mark-up

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43e Amendment No. 184 Table 3.3.5.2-1 (page 2 of 2)

RPV Water Inventory Control Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS PER FUNCTION CONDITIONS REFERENCED FROM REQUIRED ACTION A.1 SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE

3. High Pressure Core Spray (HPCS) System
a. Condensate Storage Tank Level - Low 4(b), 5(b) 2(a)

D SR 3.3.5.2.1 SR 3.3.5.2.2 90,300 gallons

b. HPCS Pump Discharge Pressure - High (Bypass) 4, 5 1(a)

E SR 3.3.5.2.1 SR 3.3.5.2.2 120 psig

c. HPCS System Flow Rate - Low (Bypass) 4, 5 1(a)

E SR 3.3.5.2.1 SR 3.3.5.2.2 600 gpm

14. RHR System Isolation
a. Reactor Vessel Water Level - Low, Level 3 (ac) 2 in one trip system B

SR 3.3.5.2.1 SR 3.3.5.2.2 177.1 inches

25. Reactor Water Cleanup (RWCU) System Isolation
a. Reactor Vessel Water Level - Low Low, Level 2 (ac) 2 in one trip system B

SR 3.3.5.2.1 SR 3.3.5.2.2 127.6 inches (a)

Associated with an ECCS subsystem required to be OPERABLE by LCO 3.5.2, Reactor Pressure Vessel (RPV) Water Inventory Control.

(b)

When HPCS is OPERABLE for compliance with LCO 3.5.2, Reactor Pressure Vessel (RPV) Water Inventory Control, and aligned to the condensate storage tank.

(ac) When automatic isolation of the associated penetration flow path(s) is credited in calculating DRAIN TIME.

Technical Specification Mark-up

LOP Instrumentation 3.3.8.1 PERRY - UNIT 1 3.3-74 Amendment No. 69 3.3 INSTRUMENTATION 3.3.8.1 Loss of Power (LOP) Instrumentation LCO 3.3.8.1 The LOP instrumentation for each Function in Table 3.3.8.1-1 shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3, When the associated diesel generator (DG) is required to be OPERABLE by LCO 3.8.2, AC Sources - Shutdown.

ACTIONS


NOTE----------------------------------------------------------

Separate Condition entry is allowed for each channel.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more channels inoperable.

A.1 Place channel in trip.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> B. Required Action and associated Completion Time not met.

B.1 Declare associated DG inoperable.

Immediately Technical Specification Mark-up

ECCS - Operating 3.5.1 PERRY - UNIT 1 3.5-1 Amendment No. 184 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS), RPV WATER INVENTORY CONTROL, AND REACTOR CORE ISOLATION COOLING (RCIC) SYSTEM 3.5.1 ECCS - Operating LCO 3.5.1 Each ECCS injection/spray subsystem and the Automatic Depressurization System (ADS) function of eight safety/relief valves shall be OPERABLE.

APPLICABILITY:

MODE 1, MODES 2 and 3, except ADS valves are not required to be OPERABLE with reactor steam dome pressure 150 psig.

ACTIONS


NOTE-----------------------------------------------------------

LCO 3.0.4.b is not applicable to High Pressure Core Spray (HPCS).

CONDITION REQUIRED ACTION COMPLETION TIME A. One low pressure ECCS injection/spray subsystem inoperable.

A.1 Restore low pressure ECCS injection/spray subsystem to OPERABLE status.

7 days B. High Pressure Core Spray (HPCS) System inoperable.

B.1 Verify by administrative means RCIC System is OPERABLE when RCIC is required to be OPERABLE.

AND B.2 Restore HPCS System to OPERABLE status.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 14 days (continued)

Technical Specification Mark-up

RPV Water Inventory Control 3.5.2 PERRY - UNIT 1 3.5-8 Amendment No. 184 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.5.2.3 Verify, for a required High Pressure Core Spray (HPCS) System, the:

a. Suppression pool water level is 16 ft 6 in; or
b. Condensate storage tank water volume is 249,700 gal.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.4 Verify, for the required ECCS injection/spray subsystem, the piping is filled with water from the pump discharge valve to the injection valve.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.5 Verify, for the required ECCS injection/spray subsystem, each manual, power operated, and automatic valve in the flow path, that is not locked, sealed, or otherwise secured in position, is in the correct position.

In accordance with the Surveillance Frequency Control Program (continued)

Technical Specification Mark-up

RPV Water Inventory Control 3.5.2 PERRY - UNIT 1 3.5-9 Amendment No. 184 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.5.2.56


NOTES--------------------------------

1.

Operation may be through the test return line.

2.

Credit may be taken for normal system operation to satisfy this SR.

Operate the required ECCS injection/spray subsystem through the recirculation line for 10 minutes.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.67 Verify each valve credited for automatically isolating a penetration flow path actuates to the isolation position on an actual or simulated isolation signal.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.78


NOTE---------------------------------

Vessel injection/spray may be excluded.

Verify the required ECCSLPCI or LPCS injection/spray subsystem actuates on a manual injection signal, or the required HPCS subsystem can be manually operated.

In accordance with the Surveillance Frequency Control Program Technical Specification Mark-up

AC Sources - Shutdown 3.8.2 PERRY - UNIT 1 3.8-20 Amendment No. 184 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.2.1


NOTES-----------------------------

1. The following SRs are not required to be performed: SR 3.8.1.3, SR 3.8.1.89, SR 3.8.1.10, SR 3.8.1.14, andthrough SR 3.8.1.16,. SR 3.8.1.18, and SR 3.8.1.19.
2. SR 3.8.1.12 and SR 3.8.1.19 are not required to be met when the associated ECCS subsystem(s) are not required to be OPERABLE per LCO 3.5.2, ECCS - Shutdown.

The following SRs are applicable forFor AC sources required to be OPERABLE, the following SRs are applicable:

SR 3.8.1.1 SR 3.8.1.7 SR 3.8.1.14 SR 3.8.1.2 SR 3.8.1.9 SR 3.8.1.15 SR 3.8.1.3 SR 3.8.1.10 SR 3.8.1.16 SR 3.8.1.4 SR 3.8.1.11 SR 3.8.1.18 SR 3.8.1.5 SR 3.8.1.12 SR 3.8.1.19 SR 3.8.1.6 SR 3.8.1.13 In accordance with applicable SRs Technical Specification Mark-up L-21-053 Proposed Technical Specification Changes (Re-Typed)

[Provided for Information Only]

(9 pages follow)

Definitions 1.1 PERRY - UNIT 1 1.0-2a Amendment No. 184 1.1 Definitions (continued)

DRAIN TIME The DRAIN TIME is the time it would take for the water inventory in and above the Reactor Pressure Vessel (RPV) to drain to the top of the active fuel (TAF) seated in the RPV assuming:

a)

The water inventory above the TAF is divided by the limiting drain rate; b)

The limiting drain rate is the larger of the drain rate through a single penetration flow path with the highest flow rate, or the sum of the drain rates through multiple penetration flow paths susceptible to a common mode failure, for all penetration flow paths below the TAF except;

1. Penetration flow paths connected to an intact closed system, or isolated by manual or automatic valves that are closed and administratively controlled in the closed position, blank flanges, or other devices that prevent flow of reactor coolant through the penetration flow paths;
2. Penetration flow paths capable of being isolated by valves that will close automatically without offsite power prior to the RPV water level being equal to the TAF when actuated by RPV water level isolation instrumentation; or
3. Penetration flow paths with isolation devices that can be closed prior to the RPV water level being equal to the TAF by a dedicated operator trained in the task, who is in continuous communication with the control room, is stationed at the controls, and is capable of closing the penetration flow path isolation devices without offsite power.

c)

The penetration flow paths required to be evaluated per paragraph b) are assumed to open instantaneously and are not subsequently isolated, and no water is assumed to be subsequently added to the RPV water inventory; (continued)

TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43a Amendment No. 184 3.3 INSTRUMENTATION 3.3.5.2 Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation LCO 3.3.5.2 The RPV Water Inventory Control instrumentation for each Function in Table 3.3.5.2-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.5.2-1.

ACTIONS


NOTE---------------------------------------------------------

Separate Condition entry is allowed for each channel.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more channels inoperable.

A.1 Initiate action to place channel in trip.

OR A.2.1 Declare associated penetration flow path(s) incapable of automatic isolation.

AND A.2.2 Initiate action to calculate DRAIN TIME.

Immediately Immediately Immediately TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43b Amendment No. 184 SURVEILLANCE REQUIREMENTS


NOTE---------------------------------------------------------

These SRs apply to each Function in Table 3.3.5.2-1.

SURVEILLANCE FREQUENCY SR 3.3.5.2.1 Perform CHANNEL CHECK.

In accordance with the Surveillance Frequency Control Program SR 3.3.5.2.2 Perform CHANNEL FUNCTIONAL TEST.

In accordance with the Surveillance Frequency Control Program TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

RPV Water Inventory Control Instrumentation 3.3.5.2 PERRY - UNIT 1 3.3-43c Amendment No. 184 Table 3.3.5.2-1 (page 1 of 1)

RPV Water Inventory Control Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS PER FUNCTION ALLOWABLE VALUE

1. RHR System Isolation
a. Reactor Vessel Water Level - Low, Level 3 (a) 2 in one trip system 177.1 inches
2. Reactor Water Cleanup (RWCU) System Isolation
a. Reactor Vessel Water Level - Low Low, Level 2 (a) 2 in one trip system 127.6 inches (a)

When automatic isolation of the associated penetration flow path(s) is credited in calculating DRAIN TIME.

TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

LOP Instrumentation 3.3.8.1 PERRY - UNIT 1 3.3-74 Amendment No. 69 3.3 INSTRUMENTATION 3.3.8.1 Loss of Power (LOP) Instrumentation LCO 3.3.8.1 The LOP instrumentation for each Function in Table 3.3.8.1-1 shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3 ACTIONS


NOTE----------------------------------------------------------

Separate Condition entry is allowed for each channel.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more channels inoperable.

A.1 Place channel in trip.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> B. Required Action and associated Completion Time not met.

B.1 Declare associated DG inoperable.

Immediately TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

ECCS - Operating 3.5.1 PERRY - UNIT 1 3.5-1 Amendment No. 184 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS), RPV WATER INVENTORY CONTROL, AND REACTOR CORE ISOLATION COOLING (RCIC) SYSTEM 3.5.1 ECCS - Operating LCO 3.5.1 Each ECCS injection/spray subsystem and the Automatic Depressurization System (ADS) function of eight safety/relief valves shall be OPERABLE.

APPLICABILITY:

MODE 1, MODES 2 and 3, except ADS valves are not required to be OPERABLE with reactor steam dome pressure 150 psig.

ACTIONS


NOTE-----------------------------------------------------------

LCO 3.0.4.b is not applicable to High Pressure Core Spray (HPCS).

CONDITION REQUIRED ACTION COMPLETION TIME A. One low pressure ECCS injection/spray subsystem inoperable.

A.1 Restore low pressure ECCS injection/spray subsystem to OPERABLE status.

7 days B. HPCS System inoperable.

B.1 Verify by administrative means RCIC System is OPERABLE when RCIC is required to be OPERABLE.

AND B.2 Restore HPCS System to OPERABLE status.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 14 days (continued)

TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

RPV Water Inventory Control 3.5.2 PERRY - UNIT 1 3.5-8 Amendment No. 184 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.5.2.3 Verify, for a required High Pressure Core Spray (HPCS) System, the:

a. Suppression pool water level is 16 ft 6 in; or
b. Condensate storage tank water volume is 249,700 gal.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.4 Verify, for the required ECCS injection/spray subsystem, the piping is filled with water from the pump discharge valve to the injection valve.

In accordance with the Surveillance Frequency Control Program (continued)

TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

RPV Water Inventory Control 3.5.2 PERRY - UNIT 1 3.5-9 Amendment No. 184 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.5.2.5


NOTES--------------------------------

1.

Operation may be through the test return line.

2.

Credit may be taken for normal system operation to satisfy this SR.

Operate the required ECCS injection/spray subsystem for 10 minutes.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.6 Verify each valve credited for automatically isolating a penetration flow path actuates to the isolation position on an actual or simulated isolation signal.

In accordance with the Surveillance Frequency Control Program SR 3.5.2.7


NOTE---------------------------------

Vessel injection/spray may be excluded.

Verify the required ECCS injection/spray subsystem can be manually operated.

In accordance with the Surveillance Frequency Control Program TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE

AC Sources - Shutdown 3.8.2 PERRY - UNIT 1 3.8-20 Amendment No. 184 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.2.1


NOTE------------------------------

The following SRs are not required to be performed:

SR 3.8.1.3, SR 3.8.1.9, SR 3.8.1.10, SR 3.8.1.14, and SR 3.8.1.16.

The following SRs are applicable for AC sources required to be OPERABLE:

SR 3.8.1.1 SR 3.8.1.6 SR 3.8.1.2 SR 3.8.1.9 SR 3.8.1.3 SR 3.8.1.10 SR 3.8.1.4 SR 3.8.1.14 SR 3.8.1.5 SR 3.8.1.16 In accordance with applicable SRs TECHNICAL SPECIFICATION INFORMATION ONLY CLEAN, RETYPED PAGE