COL Docs - Discussion Material for Oct 1, 2020 Vogtle Units 3 and 4 Public Meeting
ML20268C252
Person / Time
Site: Vogtle  
Issue date: 09/24/2020
From:
NRC
To:
NRC/NRR/DNRL
References
Download: ML20268C252 (7)


Text

From:

Schiller, Alina Sent:

Thursday, September 24, 2020 3:24 PM To:

Vogtle PEmails

Subject:

Discussion material for Oct 1, 2020 Vogtle Units 3 and 4 public meeting Attachments:

MOV Loss of Power public call Oct 1 2020.pdf Alina Schiller Project Manager Office of Nuclear Reactor Regulation Vogtle Project Office O-13 C10 301-415-8177

Hearing Identifier:

Vogtle_COL_Docs_Public Email Number:

590 Mail Envelope Properties (BLAPR09MB6594AD842D116CE23DFE523B96390)

Subject:

Discussion material for Oct 1, 2020 Vogtle Units 3 and 4 public meeting Sent Date:

9/24/2020 3:23:45 PM Received Date:

9/24/2020 3:23:48 PM From:

Schiller, Alina Created By:

Alina.Schiller@nrc.gov Recipients:

"Vogtle PEmails" <Vogtle.PEmails@nrc.gov>

Tracking Status: None Post Office:

BLAPR09MB6594.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 149 9/24/2020 3:23:48 PM MOV Loss of Power public call Oct 1 2020.pdf 691163 Options Priority:

Normal Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

VEGP 3&4

Motor Operated Valve

Loss of Motive Power Verification

September 24, 2020

MOV Loss of Power Verification There are 10 ITAAC that perform a Loss of Power Verification that include MOVs:

47 265 118 301 138 382 206 470 250 700

Example of Loss Power ITAAC ITAAC 118

Current MOV Test Verification

  • MOVs are either positioned to the Open or Closed position depending on the valve being tested.
  • Power supply to the MOV is opened
  • MOV is verified to not change position

Proposed MOV Test Verification

  • Use MOV setup work order to verify proper operation of the MOV
  • Setup work order verifies proper operation of the Open and Close contactors.
  • Verification that the Open and Close contactors operate properly ensures that upon a loss of power to the MOV, that the MOV will fail As-Is. Power to operate the valve motor come through contacts from the Open and Close contactors.