Discussion material for Oct 1, 2020 Vogtle Units 3 and 4 public meeting Attachments:
MOV Loss of Power public call Oct 1 2020.pdf Alina Schiller Project Manager Office of Nuclear Reactor Regulation Vogtle Project Office O-13 C10 301-415-8177
Hearing Identifier:
Vogtle_COL_Docs_Public Email Number:
590 Mail Envelope Properties (BLAPR09MB6594AD842D116CE23DFE523B96390)
Subject:
Discussion material for Oct 1, 2020 Vogtle Units 3 and 4 public meeting Sent Date:
9/24/2020 3:23:45 PM Received Date:
9/24/2020 3:23:48 PM From:
Schiller, Alina Created By:
Alina.Schiller@nrc.gov Recipients:
"Vogtle PEmails" <Vogtle.PEmails@nrc.gov>
Tracking Status: None Post Office:
BLAPR09MB6594.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 149 9/24/2020 3:23:48 PM MOV Loss of Power public call Oct 1 2020.pdf 691163 Options Priority:
Normal Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
VEGP 3&4
Motor Operated Valve
Loss of Motive Power Verification
September 24, 2020
MOV Loss of Power Verification There are 10 ITAAC that perform a Loss of Power Verification that include MOVs:
47 265 118 301 138 382 206 470 250 700
Example of Loss Power ITAAC ITAAC 118
Current MOV Test Verification
- MOVs are either positioned to the Open or Closed position depending on the valve being tested.
- Power supply to the MOV is opened
- MOV is verified to not change position
Proposed MOV Test Verification
- Setup work order verifies proper operation of the Open and Close contactors.
- Verification that the Open and Close contactors operate properly ensures that upon a loss of power to the MOV, that the MOV will fail As-Is. Power to operate the valve motor come through contacts from the Open and Close contactors.