I PRELIMINARY NOTIFICATION October 29, 1976 PRELIMINARY NOTIFICATION OF EVENT Gk UNUSUAL OCCURRENCE-PNO-76-178 M e preliminary notification constitutes EARLY notice of an event of ti ld3SIBLE sof-ty or pcblic interest significance. The information gr_asented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.
j Fecility: Portland General Electric Company (Trojan)
Subjecti Failure of Redundant Safety Injection (SI) Valves to Open in Response to Spurious SI Initiation Signal While Plant was Shutdown The licensee informed the Region V (Walnut Creek, CA) office by telephone on October 28, 1976 that in response to a spurious SI initiation signal at approximately 8:00 a.m. on October 28 one of two redundant valves between the Refueling Water Storage Tank (RWST) and the suction to the charging pumps failed to open. The second valve open9d only partially. The plant was shutdown at the time of the SI initiation.
(See Preliminary Notification PNO 76-174, dtd 10/21/76.)
Investigation by the licensee has revealed a burned out coil in the electrical circuit of one valve and an overload breaker trip in the second valve.
Investigation is continuing.
A Region V inspector is to be onsite on November 1, 1976 to follow licensee's investigation, and; corrective actions.
The licensee's.
current schedule is to resume plant operation on November 6 or 7, 1976, following completion of ongoing repairs to the main station generator.
The licensee issued a press release covering the occurrence on October 29, 1976. Local news media interest is expected in light of the Nuclear Initiative issue in the upcoming general election.
4 NRC Region V 3rsceivid notification of this occurrence by telephone l
from the Assistant Plant Superintendent at 4:00 p.m. on October 28, l
I 1976.