ML20247Q670

From kanterella
Jump to navigation Jump to search
Responds to NRC Bulletin 88-010, Nonconforming Molded-Case Circuit Breakers. Traceability Verification of All Circuit Breakers Purchased After 830801 Performed & Installed in safety-related Applications
ML20247Q670
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 06/02/1989
From: Cockfield D
PORTLAND GENERAL ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-88-010, IEB-88-10, NUDOCS 8906070009
Download: ML20247Q670 (2)


Text

_.

q.

e mmmmm.

tamm l}JG W

. S I

David W. Cockfield Vice President, Nuctaar June 2, 1989 Trojan Nucicar Plant Docket 50-344 License NPF-1 U.S. Nuclear Regulatory Commission

' ATTN: Document Control Desk Washington DC 20555

Dear $1rs:

Nuclear Regulatory Commission Bulletin (NRCB) 88-10

" Nonconforming Molded-Case Circuit Breakers" Refererce: portland Ceneral Electric (David W. Cockfield) to the Nuclear Regulatory Commission (Document. Control Desk) Letter, Dated.

April 14, 1989, Initial Response to NRCB 88-10 This report. is provided in accordance with reporting requirement 1.b of NRCB 88.10 as committed to in the referenced letter.

Reporting Requirement 1.b:

"Sumnarize the total number, manufacturer, model number, and to the extent possibic, the procurement chain of those circuit brenkers (CBs) that could not be traced to the circuit breaker manufacturer (CBM) in Items 1 and 4 of t'ne actions requested. For installed CBs, also identify each system in whic h they are/were installed. If Item 4 of the actions requested has not been completed by April 1, 1989, due to the schedule for test of the act4ons requested, this information should be updated within 30 days of the completion of Item 4 to address those additional CBs that could not be traced to the CBM."

PGE Res.ponse:

A inummary of the traceability of stored, spare CBs per Item 1 of NROB 88-10 was provided in the referenced letter.

The traceability verification, per Item 4 of NRCD 88-10, of all molded-case CBs that were purchased after August 1, 1983 and were installed in safety-related applications has been completed. Only one CB procured and installed after August 1, 1983, was found to lack traceability.

Specific information on this non-traceable CB is as follows:

Manufacturer:

ITE Model Number: HE3-A005 Procurement Procured by PGE from Consolidated Electrical Chain:

Distributors (CED), Longview, Washington. A 8906070009 890602 record of who CED procured the CB from could not PDR ADOCK 03000344 be identified.

Q PDC l

121 S.W Satrron Strwt Pomand. Oregon 97204 It 1

-._______.___.---_--__-__-___--_--_-.._.-__--.-___---Q

  • l*

(

N Getierd BectricCo Tsurif l

b.#

~

l Document Control Desk-June 2, 1989' i --

Page 2

.l l

i Equipment ID: 'B-2206 System:

480-Volt AC Auxiliary System Function:

Supplies 480-Volt AC power to MO-8111.[ Chemical and l

Volume Control System (CVCS) charging pump miniflow

{

isolation).

I Item 4 of NRCB 88-10 was completed on May 5, 1989, prior to the June 1, t

1989-commitment date provided in the referenced letter. This letter has been completed within the 30-day reporting requirement.

A qualified, traceable, replacement CB is scheduled to be installed in

-B-2206 prior to the end of the current refueling outage.

1 A report indicating that B-2206 has been replaced and that the PGE response to NRCB 88-10 has been completed will be submitted 30 days after the CB has been replaced.

Sincerely,

/>

l c:

Mr. John B. Martin Regional Administrator, Region V

.j U.S. Nuclear Regulatory Commission i

Mr. William T. Dixon l

State of Oregon

'l Department of Energy

'I Mr. R. C. Barr NRC Resident Inspector Trojan Nuclear Plant I

Mr. Russell Bell

)

Nuclear Management and Resources Council J

Washington DC Subscribed and sworn to before me this 2nd day of June 1989.

k Notary Public of Oreg6/1 Hy Commission Expires:

M f M9/

,u

]

i

_