g TABLE 3.3-5-(Continu d)

ENGINEERED SAFETY FEATURES RESPONSE TIMES l

INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS '

'4.

Steam Line Pressure-Low a.

Safety Injection (ECCS) 1 27.0#/37.0##

l b.

Reactor Trip (from SI) 1 3.0 l

c.

Feedwater-Isolation 1 75.0(1)

{

d.

Containment Isolation-Phase "A" 1;22.0(3)/33.0(2)

(

f e.

Auxiliary Feedwater Pumps Not Applicable.

f.

Rx Plant River Water System 1 77.0(3)/110.0(2)

I g.

Steam Line Isolation S

8.0 5.

Containment Pressure--Hich-Hich a.

Containment Quench Spray 1 77.0 b.

Containment Isolation-Phase "B" Not Applicable c.

Control Room Ventilation Isolation 1 22,0(3)/77.0(2) l 6.

Steam Generator Water Level--Hich-High a.

Turbine Trip-Reactor Trip i

2.5 (Above P-9) b.

Feedwater Isolation g

13.0(2) 7.

Containment Pressure--Intermediate Hich-High a.

Steam Line Isolation 1 8.0 8.

Steamline Pressure Rate--High Negative a.

Steamline Isolation 1 8.0 9.

Loss of Power a.

4.16kv Emergency Bus Undervoltage i 1.3 (Loss of Voltage) b.

4.16kv and 480v Emergency Bus Under-S 95 voltage (Degraded Voltage)

BEAVER VALLEY - UNIT 1 3,

3-27 Amendment No. % MR, %

138 Correction letter dated 5/15/89 i

8905190458 890515 i

PDR-ADOCK 05000334 1

P PDC l