NPDES Noncompliance Notification:On 890822,fish Kill Discovered in Circulating Water Discharge Bay.Caused by Temp Fluctuation in Circulating Water Discharge Bay
ML20246K258
Person / Time
Site: Summer 
Issue date: 08/28/1989
From: Bradham O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Krecker W
SOUTH CAROLINA, STATE OF
References
NUDOCS 8909050418
Download: ML20246K258 (7)


Text

- _ -

South Carolina Electnc & Gas Comptny OH.e S Bradnam

.$ S N N sc coats

? eT?C.n j...

m 3:sa a

' August 28, 1989 Mr. William R. Krecker Environmental Quality Manager Water Quality Assessments & Enforcement Division South Carolina Department of Health

& Environmental Control 2600 Bull Street Columbia, South Carolina 29201

Subject:

Virgil C. Summer Nuclear Station Docket No. 50-395 Operating License No. NPF-12 Fish Kill - August 22, 1989

Dear Mr. Krecker:

South Carolina Electric & Gas Company (SCE&G) herein submits a report concerning a fish kill in the Virgil C. Summer Nuclear Station (VCSNS) dischtcge bay which occurred on August 22, 1989. The enclosed report describes the current event and probable cause. Actions to be taken to investigate and. determine appropriate measures to prevent these events were provided to your office in a letter dated August 23, 1989.

In accordance with the VCSNS Operating License NPF-12, Appendix B, a copy of this report is being provided to the Nuclear Regulatory Commission.

Additionally, a copy of this report will also be provided to the South Carolina Department of Wildlife & Marine Resources per the request of Mr. H.

J. Logan, Chief of Fisheries.

Should you require any further information, please contact Mr. Charles McKinney of my staff at your convenience.

Very truly yours,

0. S. Bradham

-CJM/OSB: led Attachment c:

M. B. Williams

.E.,B._McDowell _, _

W. R. Baehr iDocument-Controll(NRC)),:

S. E. Summer R. L. Prevatte W. R. Higgins NPCF W. F. Bacon RTS (0NO 890075)

W. M. Lide, Jr.'

Files (818.05 & 809.06-1) 65EN I

8909050418 890828 PDR ADOCK 05000395 s

FDC.

FISH Kil1 REPORT August 22,1989 On August 22, 1989, a fish kill was discovered in the circulating water discharge bay at the V. C. Summer Nuclear Station (see Figure 1). The numbers and species of fish found are presented below.

Number of Fish identification Size 17 white catfish 7-11 inches 6

channel catfish 11-15 inches 1

bluegill 6 inches I

2 unidentified sunfish

< 6 inches 30 threadfin shad 2 inches The fish were bloated and appearea to have been killed during the night of August 21, 1989. The cause of the kill appears to have been a temperature fluctuation in the circulating water discharge bay., A review of temperature data recorded in the discharge bay showed a temperature fluctuation of 10*F on August 21,1989. This temperature fluctuation coincided with a fluctuation in Monticello Reservoir level (see Table 1). This phenomenon is consistent with data gathered during previous kills this summer. Dissolved oxygen (surface 5.2 mg/l, bottom 4.95 mg/l) and pH (surface 6.7) readings in the discharge bay also support the conclusion that the kill was thermalin nature. Although there have been problems with high pH values in wastewater treatraent ponds this summer, this does not appear to be a contributing factor.

S. E. Summer 8/25/89

)

o

i l.:

FISH KILL REPORT -

l,.-

8/22/89 MONTICELLO RESERVOIR SERVICE WATER POND LOCATION OF FISH KILL t

J CIRCULATio2 WATER DISCHARGE FIGURE 1

TABLE 1 TEMPERATURE vs RESERVOIRLEVEL AUGUST 22,1989 FISH KILL Circulatir.g Water Discharge Hourly Average Discharg)e BayMonticello Reservoir Date/ Time Te nperature(A) *F Bottom Temperature (B "F Level (O 8/19 0100 106.1 99 423.6 0200 106.1 99 423.8 0300 106.0 97 423.9 0400 105.8 100 424.1 0500 105.8 97 424.4 0600 105.7 99 424.6 0700 105.6 97 425.0 0800 105.5 97 425.0 0900 105.4 97 425.0 1000 105.3 96 425.0 1100 105.3 96 424.9 1200 105.8 96 424.9 1300 106.2 96 424.8 1400 106.5 95 424.8 1500 106.5 95 424.7 1600 106.6 97 424.6 1700 106.7 96 424.5 1800 106.5 97 424.3 1900 106.5 97 424.1 2000 106.8 99 423.9 I

2100 106.4 100 423.6 2200 106.3 100 423.3 i

2300 106.3 100 423.2 2400 106.2 100 423.2 A

Measured at the condenser outlet.

B Measured in the discharge bay at the approximate depth of 30 feet.

i C

Feet above mean sea level.

l

L TABLE 1 TEMPERATURE vs RESERVOIR LEVEL AUGUST 22,1989 FISH KILL (continued)

{

Date/ Time Circulating Water Discharge Hourly Average Discharge Bay Monticello Reservoir Temperature (A) F Bottom Temperature (B) *F Level (C) 8/20 0100 104.4 101 423.2 l-0200 104.4 102 423.2 0300 105.0 101 423.3 0400 105.4 101 423.5 0500 105.8 100 423.7

{

0600 105.8 100 423.9 0700 105.8 97 424.1 0800 105.5 97 424.2 0900 105.3 97 424.3 1000 105.3 97 424.3 1100 105.3 97 424.3 1200 105.8 96 424.3 1300 106.4 96 424.3 1400 106.6 96 424.1 1500 106.7 96 423.8 1600 106.2 97 423.7 1700 106.2 96 423.5 1800 106.2 97 423.3 1900 106.1 99 423.2 2000 105.8 101 423.1 2100 105.5 101 423.1

~

2200 105.5 101 423.1 2300 105.4 101 423.1 2400 105.3 101 423.3 A

Measured at the condenser outlet.

B Measured in the discharge bay at the approximate depth of 30 feet.

C Feet above mean sea level.

4

i TABLE 1 1

TEMPERATURE vs RESERVOIR LEVEL AUGUST 22,1989 FISH KILL (continued)

Date / Time Circulating Water Discharge Hourly Average Dischar e Bay Monticello Reservoiri Temperature @) *F Bottom Temperature ( ) F Level (C) 8/21 0100 105.3 99 423.5 0200 105.3 100 423.8 0300 105.3 100 424.1 0400 105.3 39 424.3 0500 105.4 99 424.5 0600 105.3 97 424.7 0700 105.4 96 424.9 0800 105.3 96 424.9 0900 105.3 96 425.0 1000 105.1 96 425.0 1100 106.2 96 424.9 1200 106.1 97 424.8 1300 105.1 97 424.6 1400 106.3 97 424.3

~

1500 106.6 97 424.1 1600 106.8 100 423.4

~

1700 107.0 99 423.0 1800 107.1 100 422.6 1900 107.9 102 422.3 2000 108.2 104 422.0 2100 108.0 104 421.5 2200 107.9 106 421.4

~

1 2300 107.8 106 421.4 l

2400 107.7 104 421.5 A

Measured at the condenser outlet.

B Measured in the discharge bay at the approximate depth of 30 feet.

C Feet above mean sea level.

(

l l

- ~.

TABLE 1 TEMPERATURE vs RESERVOIR LEVEL AUGUST 22,1989 FISH KILL (continued)

Date / Time Circulating Water DiscFarge Hourly Average Dischar e Bay Monticello Reservoir Temperature (A) *F Bottom Temperature )*F t.evel(C) 8/22 0100 107.1 104 421.8 0200

$107.1 103 422.2 0300 106.8 104 422.5 0400 106.8 102 423.0 0500 106.6 101 423.5 0600 106.5 100 424.0 l

l l

l l

A Measured at the conder1ser outlet.

B Measured in the discharge bay at the approximate depth of 30 feet.

C Feet above mean sea level.

.