Notice of Deviation from Insp on 890717-21.Deviation Noted: Failure to Show That Quarterly Samples from Incoming Fuel Oil Obtained & Analyzed Every 3 Months Per FSAR Requirement
ML20246G131
Person / Time
Site: Calvert Cliffs  
Issue date: 08/22/1989
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20246G126 List:
References
50-317-89-17, 50-318-89-18, NUDOCS 8908310229
Download: ML20246G131 (1)


Text

{{#Wiki_filter:__ - QL 1 l. } APPENDIX A NOTICE OF DEVIATION Baltimore Gas and Electric Company. Docket Nos. 50-317 L Calvert Cliffs Units'1 and 2 50-318 Lusby, Maryland - License Nos. DPR-53 m DPR-69 7 .As a result of the inspection conducted on July 17-21, 1989 and in accordance with the " General' Statement of Policy and Procedure for. NRC E.forcement i: L . Actions," 10. CFR Part 2, Appendix C (Enforcement Policy) (1989), the' following deviation was; identified: l -- The Calvert Cliffs FSAR, Section 8.4.1.2 (page 8-17 Rev. 6), states the-fo % ng:- L " Quarterly samples will be composited from incoming fuel' oil and analyzed for API gravity, specific gravity, flash point, sulfur, ash, Btu per gallon, and viscosity. Samples are'obtained from the - fuel cil storage tanks every 3 months and analyzed for-oxii*iM on/ deterioration products," Contrary to the above,'as of July 21, 1989 there was no~ documented ' ~ -evidence to show that quarterly samples were'obtained and analvzed as

stated in the FSAR Section.

Pursuant to the provisions of 10 CFR 2.201, the Baltimore Gas and Electric Company is'hereby requested to submit to this offict'within' thirty days of the-date of the letter which transmitted this Notice, a written statement or explanation >in reply, including: (1) the corrective steps which have been taken and the results achieved; (2) corrective steps which will be taken to avoid further deviations;.and (3) the date when full compliance will-be achieved. Where good cause is shown, consideration will be given to extending this -response time. a OFFICIAL RECORD COPY CIR CC 89-17/18 - 0002.0.0 { 8310229 890h0317 22 08/22/89 g. ADOCK 050 PDC = _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ - _ - - _ _ _ - _ _ - -. - _ - -}}