Discusses Essential Raw Cooling Water Pumphouse Foundation & ERCW Pumping Station Access Cells,Per Insp Repts 50-327/88-12 & 50-328/88-12.Max Grouting Pressure in Pumping Station of 15 Lbs Per Square Inch Established
ML20246F685
Person / Time
Site: Sequoyah  
Issue date: 07/10/1989
From: Michael Ray
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 8907130357
Download: ML20246F685 (2)


Text

-_

S TENNESSEE VALLEY AUTHORITY

, CHATTANOOGA. TENNESSEE 37401 SN 1578 Lookout Place JUL 10.1989 U.S._ Nuclear Regulatory Commission ATTN: Document Control Desk i

i

'Hashington, D.C.

20555 Gcntlemen:

In the Matter of

)

Docket Nos. 50-327 Tennessee Valley Authority.

)

50-328 SEQUOYAH NUCLEAR PLANT (SQN) - ESSENTIAL RAW COOLING WATER (ERCW) PUMPHOUSE FOUNDATION AND ERCH PUMPING STATION ACCESS CELLS

References:

1.

TVA letter to NRC dated October 20, 1988 2.

TVA letter to NRC dated December 28, 1988 This submittal provides.TVA's schedule for work associated with the resolution of Inspection Report 50-327, 328/88-12, unresolved items 88-12-05 and 88-12-09.. It.also provides two refinements to the action plan as it'was described in the enclosure to Reference 1.

TVA's anticipated schedule for starting to drill at the roadway access cells is July 24, 1989. Completion is expected approximately one month later. The drilling would then start in element D of the pumping station on approximately August 28, 1989. Completion of the pumping station work is expected by l

approximately October 16, 1989.

The two refinements of the original plan involve the definition of the grouting pressure'to be used for the pumping station and the hole drilling i

depth into rock.

These refinements have been agreed to by TVA's consultants.

l TVA has established a maximum grouting pressure in the pumping station of l

15 pounds per square inch at elevation 625.0 feet, the bottom of the intake liner. This will ensure that grouting does not develop pressures exceeding the calculated allowable stress for the steel intake liner.

TVA will drill five feet into sound rock at each location to investigate the concrete / rock interface. Coring five feet into sound rock will provide sufficient information for evaluating the interface to meet the program requirements.

As required by TVA's commitment No. 3 in Enclosure 1 of Reference 2, NRC's written concurrence with the two proposed program refinements is requested.

n h h, 7

3 0 An Equal opportunity Employer

. 0

to.

f

': j;,' J '

[

U.S.'NuclearRe0ulatoryCommission-JUL 10198 L

. No new ' commitments.are contained in.this submittal..Please direct questions-g.

concerning'this. issue to Kathy S. Whitaker at (615) 843-7748.

Very truly yours, TENNESSEE VALLEY AUTHORITY Q

[-'

Ma aged, Nuclea censing

~

and Regulatory Affairs cc: Ms. S. C.' Black, Assistant Director s-for Projects TVA Projects Division U.S. Nuclear Regulatory Commission One White. Flint, North.'

11555 Rockville Pike Rockville, Maryland. 20852,-

Mr. B. A. Wilson ~,. Assistant Director for Inspection Programs

.TVA Projects Division-U.S. Nuclear Regulatory Commission Region'II 101 Marietta Street,.NH, Suite 2900

. Atlanta, Georgia 30323 NRC Resident Inspector Sequoyah' Nuclear P1 ant 2600 Igou Ferry Road Soddy Daisy, Tennessee 37379 mum __m.m____a_

_a.s__-_.

A. -...

_:..