Amend 101 to License NPF-7,modifying Tech Spec Table 3.8-1 by Deleting Components from Table Previously Removed & by Correcting One Typo
ML20246F351
Person / Time
Site: North Anna 
(NPF-07-A-101-01, NPF-7-A-101-1)
Issue date: 07/07/1989
From: Berkow H
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20246F355 List:
References
NUDOCS 8907130229
Download: ML20246F351 (5)


Text

_ - _ _ - _ _ - _

'o#

j UNITED STATES e

NUCLEAR REGULATORY COMMISSION j

j WASHINGTON, D. C. 20656 e

VIRGINIA ELECTRIC AND POWER COMPANY 01DDOMINIONELECTRICCOOPERATIVE DOCKET NO. 50-339 NORTH ANNA POWER STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.101 License No. NPF-7 1.

The Fuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Virginia Electric and Power Company, et al., (the licensee) dated February 23, 1989, complies with the standards and requirements of the Atomic Energy Act of 1954, as asended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the riles and regulations-of the Commission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Consission's regulations; D.

The issuance of this amendment will not be inimical to the connon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

8907130229 890707 PDR i', DOCK 05000339 P

ppc

e

, 2.

Accordingly, the license is amended by changes to the Technical Speci-fications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License.No. NPF-7 is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.101

, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective at of the date of issuance and shall be implemented within 30 day!.

FOR THE NUCLEAR REGULATORY COMMISSION H rbert N. Berkow, Director Project Directorate II-2 Division of Reactor Projects-I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: July 7,1989 I

I

i 3.

b ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2.

By verifying the OPERABILITY of molded case circuit breakers, by selecting and functionally testing a representative sample of at least 10% of all the circuit breakers of that type.

Circuit breakers selected for functional testing shall be selected on a rotating basis.

The functional test shall consist of injecting a current input at the specified setpoint to each selected circuit breaker and verifying that each circuit breaker functions as des' 1ed. Circuit breakers found inoperable during functional testing shall be restored to OPERABLE status prior to resuming operation.

For each circuit breaker found inoperable during these functional tests, an additional repre-sentative sample of at least 10% of all the circuit breakers of the inoperable type shall also be functionally tested until no more failures are found or all circuit breakers of that type have been functionally tested, 3.

By verifying the OPERABILITY of fuses, by selecting and function-ally testing a representative sample of each type of. fuse on a rotating basis.

Each representative sample of fuses shall include at least 10% of all fuses of that type. The functional test shall consist of a non-destructive resistance measurement test which demonstrates that the fuse meets its manufacturer's design criteria. Fuses found inoperable during these functional tests shall be replaced with OPERABLE fuses prior to resuming operation.

For each fuse found inoperable during these func-tional tests, an additional representative sample of at least 10% of all fuses of that type shall be functionally tested until no more failures are found or all fuses of that type have been functionally tested.

b.

At least once per 60 months by subjecting each circuit breaker to an inspection and preventive maintenance in accordance with procedures prepared in conjunction with its manufacturer's recommendations.

NORTH ANNA - UNIT 2 3/4 8-17

' 5..

h-i TABLE 3.8-1 (Continued) l CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Nominal.

Nominal Device Number Trip

Response

System and Location Setpoint Time Powered (BK NO)

(Amperes)

(Sec (Mark No) 281-2 AIL 800 0.060 RHR Cub. Pwr. Recepts.

2B1-2A2R 800 0.060 Loop 2 Pwr. Recepts.

2B1-2A2L 500 0.060 Incore Inst. Drive B 281-2A3 2000 0.060 React. Cont. Crane 2B1-2C2 250 0.060 MOV-CC-2008 281-2E3 250 0.060 2-HV-F-03B 2B1-2E4 250 0.060 2-RC-P-01B1 281-2E5 250 0.060 2-DA-P-048 2B1-2F2 500 0.060 2-RC-P-0182 281-2F4 250 0.060 2-DG-P-01A 2Cl-1A3L 800 0.060 Cont. Elevator 2C1.-183R 500 0.060 Incore Inst. Drive C 2Cl-183L 500 0.060 Monorail Fdr.

2C1-1C2 500 0.060 2-RC-P-0102 2C1-103 250 0.060 2-RC-P-01C1 2C1-1E3 250 0.060 2-DA-P-05 2C1-1E4 250 0.060 2-DG-P-018 l

2Cl-1A2L 800 0.060 Loop 3 Pwr. Recepts.

2Cl-4A1 250 0.060 2-NS-P-01A I

2C2-1A2R 800 0.060 Port Crane Recepts.

2C2-1C1 250 0.060 2-NS-P-01B 2H1-2NA1 2000 0.060 2-HV-F-37A 2H1-2NA3 500 0.060 2-IA-C-02A 2H1-2NB1 2000 0.060 2-HV-F-378 2H1-2NC4 2000 0.060 2-HV-F-37C 2H1-2NH4 500 0.060 MOV-28658 2H1-2NK1 500 0.060 2-IA-C-02A 2H1-2NL3 500 0.060 MOV-2865A 2H1-25B4 250 0.060 MOV-2536 2H1-2SC1 500 0.060 MOV-2720A 2H1-2501 250 0.060 MOV-2700 l

I NORTH ANNA - UNIT 2 3/4 8-19 Amendment No.101

.)

.]

i.

TO FACILITY OPERATING LICENSE NO. NPF-7 DOCKET NO. 50-339 j

l

. Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages as indicated. The revised pages are identified by i

amendment number and contain vertical lines indicating the area of change.

The corresponding overleaf pages a're also provided to maintain document completeness.

Pages.

3/4 8-18 3/4 8-19 l

i

.