ML20246E670

From kanterella
Jump to navigation Jump to search
Supplemental Deficiency Rept CP-87-085 Re Degradation of Class 1E Circuits.Initially Reported on 870903.Fault at Logic Panel Will Not Affect Class 1E Field Contacts or Devices.Condition Not Reportable Per 10CFR50.55(e)
ML20246E670
Person / Time
Site: Comanche Peak  
Issue date: 08/24/1989
From: William Cahill
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CP-87-085, CP-87-85, TXX-89588, NUDOCS 8908290255
Download: ML20246E670 (2)


Text

.

-G:

y

.f a Nme=

.E Log #.TXX-89588 File # 10110 -

,_r 907:

' 1UELECTRIC

^" "8 WWbm J. ChhE Jr.

Executive Vice l* resident U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.

C.-

20555

SUBJECT:

COMANCHE

'.AK STEAM ELECTRIC STATION (CPSES)

DOCKET N0o. 50-445 AND 50-446 DEGRADATION OF CLASS 1E CIRCUITS SDAR: CP-87-085 (SUPPLEMENTAL REPORT) 3entlemen:

On September'3,1987, TV Electric verbally notified the NRC of a del sciency involving the degradation of Class IE circuits. This deficiency was subsequently determined to be reportable as stated in TXX-7124. dated December 23, 1987. The latest report was logged TXX-89568, dated August 4, 1989. This report:is being submitted to provide additional information, revised corrective actions, and a change in deportability for this issue.

In TXX-7124. TU Electric indicated that the non-Class IE Safety System Inoperable Indication (SSII) panel was directly connected to Class IE circuits without isolation devices or an appropriate analysis.

In addition, the cable which makes these connections was discovered to be routed with Class ?E cable without appropriate qualification documentation. This condition is contrary to the requirements of Regulatory Guide 1.75 for isolation and cable qualification.

The corrective action as described in TXX-7124 was to consist of the addition of approved isolation devices betweem the SSII panel and the affected Class IE circuits, or an appropriate analysis to demonstrate why the absence of isolation devices would not result in.the potential degradation of the Class IE circuits. An analysis demonstrating why an' isolation device is not required between the non-Class 1E circuits in the SSII logic panel and the associated cable that is connected to the field device is provided below.

The. output of the SSII power pack is 115V DC which is protected by a 0.5 amp fuse. The circuit to the individual field contact is current limited at the logic card to a value of 0.767 amp by means of a series resistor.

In i

addition,-logic panel input power is protected by two 3 amp fuses in series.

Field contacts at Class IE devices are rated for 250V DC and 5 amp, which is more than adequate to handle the current. As such, a fault at the logic panel 1-will not affect the Class 1E field contacts or devices.

~

-8908290255 890824

"'/

PDR ADOCK 05000445 g

PDC 4@ Nonh Olive Street LB B1 Dallas, Texas 75201 OL.

I t

r L

TXX-89588

' August 24, 1989 L

Page 2 of 2' The multiconductor cable between the SSII logic panel located in the control room and the te Snation cabinet in the cable spreading roca meets the requirements of agalatory Guide 1.75, Revision 1, Regulatory Position C.4, except for'envis..aental qualification. The cable insulation materials meet IEEE 383-1974 for the attributes of flame and radiation resistance..The cable is installed in a mild environment. One cable-is used per Engineered Safegaurds Feature (ESF) train. The insulation is rated at 600V. Any individual conductor is sized at a minimum #18 AWG while carrying a maximum 0.767 amps (current is limited at the SSII logic card as noted above). The system is protected by a 0.5 amp fuse at the 115 VDC SSII power supply. Based-on-this analysis, a fault at the SSII logic panel will not impact the availability of adjacent Class IE cables with which these associated cables are routed. This supports the exception taken to environmental qualification I

for these associated cables.

Given the above analyses, the present installation configuration is considered acceptable and no corrective brtions are required. The analyses for the circuits / equipment described above have been documented by advanced FSAR submittal, logged as TXX-89576, dated August 15, 1989.

Since the installed configuration is acceptable, this issue has been determined to be not reportable under the provisions of.10CFR50.55(e). This-completes the evaluation of this issue.

Sincerely.

4

$ff' WilliamJ.Eahill,Jr.

FAM/vid c - Mr. R. D. Martin, Region IV Resident Inspectors, CPSES (3)

_ - ____-_ _ -______ -