Notifies of Potential Significant Deficiency Re Atomospheric Dump Valves.Decision Based on Assumption That Capability of Actuator Was 20,000 Lbs Which Is Incorrect.Max Actuator Load Available Is 13,620 Lbs
ML20246C615
Person / Time
Site: Vogtle  
Issue date: 06/28/1989
From: Sterud C
CONTROL COMPONENTS, INC.
To: Cross D
GEORGIA POWER CO.
References
REF-PT21-89 NUDOCS 8907110083
Download: ML20246C615 (2)


Text

,

.y '

3.

Control Components Inc.

AnIMIvalvecompany Fi.": yerm,. W s

June 28, 1989 0 bN Tl.':,3Q0 dtYfs'

~

Mr. Don Cross Georgia Power Company Alvin W. Vogtle Nuclear Plant

Subject:

Atmospheric Dump Valves CCI W.O.# 23469-1,2 Potential Significant Deficiency Under 10CFR-21

Reference:

APS - Palo Verde Telecon 3/28/89

Dear Mr. Cross:

We are hereby notifying you of a potential significant deficiency that may be reportable under the requirements of 10CFR-21.

We are not re-porting this directly to the Nuclear Regulatory Commission (NRC).

We at CCI do not have the systems expertise that would permit us to de-cide if this is a significant deficiency.

However, because of the NRC's interest and their prior contact for information regarding plants with a similar design, we have sent a copy to Rich Lobel of the Events Assessments group in Washington D.C.

On March 28, 1989 we sent you a letter stating that there was suffi-cient actuator force to overcome a potential high load required to open the subject valve.

This was based on the assumption that the ca-pability of the actuator was 20,000 lbs.

The 20,000 lbs is in error.

The maximum actuator load available is 13,620 lbs.

The actuator load g

required (worst case) is approximately 13,408 lbs.

It is necessary to modify the trin inside the valve to reduce the maximum potential load required to open.

We have a modified trim design with which the maxi-

,d i

mum load required to open (worst case) would be approximately 5,800 lbs.

i I

i I

t 4

I g

s997110083 890628 PDR ADOCK 05000424 g 0 g

PDC 1

22591 Avenda Empresa O Rancho Santa Marganta. Cahfornia 92688 Telephone. (714) 858-1877 O FAX (714) 858-18n O Teler 685500

}

i

,:'FOgo 2 l..,

, C@o,rgio POwcr'Compnny n.,<

ls; l

.Please contact myself, Ron Adams,-Larry Stratton or Herbert Miller at CCI if you should have any questions or need additional information.

L-Sincerely, CONTROL' COMPONENTS INC.

h sl1 A

f/

Curtis G. Sterud-Principal Engineer